| 1 | Wiring forlighting points/fan points/exhaust fan points/call bell points with 2x1.5 sq mm FRLSPVC insulated flexible stranded copper conductor wiresin recessed or surface medium class PVC conduit, with 240V6A modular switch , modular plate, suitable GI box and earthing the point with 1x1.5 sq mm FRLSPVC insulated copper conductor single core cable (loop earthing) etc. as required. (Havells/ Polycab/ Anchor/ Finolex/KEI/RR or equivalent as directed by engineer incharge) including the cost of conduit.It also includes removal of the old wiring present on site and sucessfully handing over to the concerned department with proof. |
| 2 | Wiring forlight/power plug points (15/16A heating points) with 2x4 sq mm FRLSPVC insulated flexible stranded copper conductor wires in recessed or surface medium class PVC conduit along with 1x4 sq. mm FRLSPVC insulated copper conductor single core cable forearthing, etc. as required.(Havells/ Polycab/ Anchor/ Finolex/KEI/RR or equivalent as directed by engineer incharge) including the cost of conduit.Loop earthing can be given to maximum two points, It also includes removal of the old wiring present on site and sucessfully handing over to the concerned department with proof. |
| 3 | Wiring for2 No. AC pointswith 2x4 sq mm FRLSPVC insulated flexible stranded copper conductor wires in recessed or surface medium class PVC conduit along with 1x4 sq. mm FRLSPVC insulated copper conductor single core cable forearthing, etc. as required.(Havells/ Polycab/ Anchor/ Finolex/KEI/RR or equivalent as directed by engineer incharge) including the cost of conduit.It also includes removal of the old wiring present on site and sucessfully handing over to the concerned department with proof. |
| 4 | Supply, installation, testing and commissioning of 32A Modular plug/Socket with 32A DP MCB for ACincluding PVC enclosure boxcomplete with necessary connections, rating 240/415V,10 KA \"C\" curve MCB of Legrand/ Havells/L&T suitable for inductive load. It also includes removal of the old items present on site and sucessfully handing over to the concerned department with proof. |
| 5 | Wiring for 5-10A Socket out lets for computer (inverter) with 2X2.5 sq. mm FRLS PVC insulated flexible stranded copper conductor (Havells/ Polycab/ Anchor/ Finolex/KEI/RR equivalent as directed by engineer incharge.) wires in surface/recessedmedium class PVC conduit alongwith 1 No. 2.5 sq. mm FRLS PVC insulated copper conductor single core cable for earthing etc. as required. including the cost of conduit.Loop earthing can be given to maximum two points. It also includes removal of the old wiring present on site and sucessfully handing over to the concerned department with proof. |
| 6 | Supplying and fixing of GI box along with modular base and cover plate for modular sockets, switches in recess etc as required. (Havells/ Polycab/ Anchor/ Finolex/KEI/RR equivalent as directed by engineer incharge.)6 module (200mm x 75mm). It also includes removal of the old items present on site and sucessfully handing over to the concerned department with proof. |
| 7 | Supplying and fixing of 5pin 5-10A socket and 5-10A switch on existing modular plate, incl connections etc as required. (Havells/ Polycab/ Anchor/ Finolex/KEI/RR equivalent as directed by engineer incharge.) It also includes removal of the old items present on site and sucessfully handing over to the concerned department with proof. |
| 8 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 5 pin 5/6 A modular socket outlet including connections etc. as required.(Anchor roma plus/Legrand Mylinc /SSK/Schneider Zencelo /Crabtree athena make). It also includes removal of the old items present on site and sucessfully handing over to the concerned department with proof. |
| 9 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 5/6 pin 15/16 A modular socket outlet and 15/16 A modular switch connections etc. as required.(Anchor roma plus/Legrand Mylinc /SSK/Schneider Zencelo /Crabtree athena make).It also includes removal of the old items present on site and sucessfully handing over to the concerned department with proof. |
| 10 | Supplying and fixing ofindicators on existing modular plate and switch box , incl. connections, etc. as required.(Havells/ Polycab/ Anchor/ Finolex/KEI/RR equivalent as directed by engineer incharge) It also includes removal of the old items present on site and sucessfully handing over to the concerned department with proof. |
| 11 | Supplying and fixing modular blanking plate on the existing modular plate, switch box excluding modular plate as recquired. It also includes removal of the old items present on site and sucessfully handing over to the concerned department with proof. |
| 12 | Supply installation testing and commissioning of18 W +LEDSurface/recess, round Mountedlightluminaryfitting shape with minimum system lumen efficacy of 100 lm/W with Pressure Die cast Aluminium Heat Sink and P.F.>0.95 ,THD<10% ,CCT 5700K, CRI 80.The LED with Useful life of 50000 Hrs at L70, seperate driver, heat sink, earthing provision.. The Input voltage range shall be 150V to 270V .The Fixture should have In-built Surge Protection of 2kV. Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/ government of India. The job includes AMC (reckoned from date of successful commissioning)of lighting fixtures for a period of Two years ,which includes replacement offixtures ofPhilips/ Havel\"s /Wipro/ Crompton make / sample to be approved before installation.It also includes removal of the old items present on site and sucessfully handing over to the concerned department with proof. |
| 13 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, decorative typeceiling fan with3 No. Aluminium blades, down rod as per site requirement , 2nos. canopies, shackle kit,Power Factor not less than 0.9, Service Valueincluding safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, and including iron hook complete job. USHA striker galaxy/Havells Oyster matalic/Crompton aura/sample to be approved before installation.It also includes removal of the old items present on site and sucessfully handing over to the concerned department with proof. 3 star |
| 14 | Supply and fixing of two module stepped type electronicfan regulator on the existingmodular plate and switch box , incl. connections but excluding modular plate etc. as required. (Havells/ SSK/ Anchor/ ABB/ Schneider or equivalent make ) It also includes removal of the old items present on site and sucessfully handing over to the concerned department with proof. |
| 15 | Supply installationtesting andcomm. of 250mmsweep exhaust fan Shutter type of havell /Bajaj/Crompton/equivalent make as directed by engineer incharge, including making of space in wall/ window as per site requirement and necessary connections. It also includes removal of the old items present on site and sucessfully handing over to the concerned department with proof. 3 star. |
| 16 | Supply and fixing of 6 way (4+18) , Double door surface/ recess mounting, Horizontal type, 240V , SP&NMCB distribution board of sheet steel, dust protected, duly powder painted, inclusive oftinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs, excluding cost of MCBs and Incomer. (Havells/Legrand/SSK) It also includes removal of the old items present on site and sucessfully handing over to the concerned department with proof. |
| 17 | Supply, installation, testing and commissloning of 5-32A single pole rating 240/415V,10 KA \"C\" curve MCB of Legrand/ Havells/ L&T suitable for inductive load in the MCBdistribution board complete with necessary connections. It also includes removal of the old items present on site and sucessfully handing over to the concerned department with proof. |
| 18 | Supply, installation, testing and commissioning of 40A DP rating 240/415V,10 KA \"C\" curve MCB of Legrand/ Havells/L&T suitable for inductive load in the MCB distribution board complete with necessary connections. It also includes removal of the old items present on site and sucessfully handing over to the concerned department with proof. |
| 19 | Supply, installation, testing and commissioning of 100A DP rating 240/415V,10 KA \"C\" curve MCB of Legrand/ Havells/L&T suitable for inductive load in the MCB distribution board complete with necessary connections. It also includes removal of the old items present on site and sucessfully handing over to the concerned department with proof. |
| 20 | Supply and fixing of single pole blanking plates on existing MCB distribution boards. It also includes removal of the old items present on site and sucessfully handing over to the concerned department with proof. |
| 21 | Wiring for Circuit/Sub mains along with earth wire in FRLSPVC insulated 660/1100 volt grade flexible stranded copper conductor wiresin recessed or surface conduiting system, including the cost of conduits. (Havells/ Polycab/ Finolex/ Anchor/KEI/RR or equivalent).It also includes removal of the old wiring present on site and sucessfully handing over to the concerned department with proof. |
| 22 | 2x 2.5 sq mm + 1x 2.5 sq mm Lighting circuit |
| 23 | 2x 2.5 sq mm + 1x 2.5 sq mm Inverter circuit |
| 24 | Supply, laying, connecting and commissioning of 25 sq mm 2 core XLPE/ PVCInsulated armoured 1.1 KV grade Aluminum LT cable for Service line, incl. cost of required al. thimbles duly crimped (havells or as directed by EIC. (Over head/ under ground).It also includes removal of the old Service line present on site and sucessfully handing over to the concerned department with proof. |