| 1 | Laying of one number PVC insulated and PVC sheathed / XLPEpower cable of 1.1 KV grade of following size direct in groundincluding excavation, sand cushioning, protective covering andrefilling the trench etc as required. 70 sqmm single core cablex 4 run |
| 2 | Upto 35 sqmm |
| 3 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel,making connections etc as required 400 Amps,50KA,Four Pole |
| 4 | 200 Amps,36KA,Four Pole |
| 5 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\"curve, miniature circuit breaker suitable for inductive load offollowing poles in the existing MCB DB complete withconnections, testing and commissioning etc. as required.single pole and neutral |
| 6 | Triple pole and neutral |
| 7 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm diaincluding accessories, and providing masonry enclosure withcover plate having locking arrangement and watering pipe etc.with charcoal/ coke and salt as required. |
| 8 | Supplying and laying 6 SWG G.I. wire at 0.50 metre belowground level for conductor earth electrode, includingconnection/ termination with GI thimble etc. as required |
| 9 | Providing, laying and fixing following dia G.I. pipe (mediumclass) in ground complete with G.I. fittings including road cutting trenching (75 cm deep)and re-filling etc as required a)100 mm dia |
| 10 | Supplyof following size PVC/XLPE insulated and PVC sheathed 1.1 KV GSolid Aluminium conductor up to 10 sq mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, Armour (Aluminium f1100V grade as per IS 7908(Part 1)1988 armoured U.G. cable as specified and directed by the deptt. ( Havells/ RPG/CCI/Polycab/ Finolex make) 70Sq.mm.Single Core armoured U.G. cable |
| 11 | 25 sqmm two core cable |
| 12 | 25 sqmm three and half core cable |
| 13 | Dismantalling of existing Panel including dismantalling of the PCC and exavation of soil to dig out the exisitng cables and the dismantalling of MCCB from the exisiting panel and reconnection them in the new panel where required ,packing and handing over the materials at specified loaction as per the direction of the department |
| 14 | Supplying and fixingincluding connections of the Aluminium Lugs for following size of PVC insulated and PVC sheathed/XLPE Aluminium conductor cable of 1.1 KV grade as required.a)4 X 70 Sqmm(4 lugs) |
| 15 | 25 sq mm two core(2 lugs) |
| 16 | 25 sqmm three and half core cable(4 lugs) |
| 17 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level.1:1(1/2):3 (1 Cement :1(1/2) coarse sand (zone-III) : 3graded stone agreegate20 mm normal size |
| 18 | Supplying including installation, commissioning of vermin and dust proof totally enclosed, Phosphatised Powder Painted cubical outdoor, compartmentalize cubical typepanel board ofsuitable size made of 18 SWG sheet with a provision for 400 amps copper busbar, One 400 Amps MCCB as incomer and 15 nos DP and Three TPN as outgoing ,Ampere meter,Voltmeter and Phase selector switch,LED indication lamps etc as specified and directed by the deptt. The panel board is to be erected in 1 : 3 : 6 PCC foundation including excavation of trenchand brick soling etc. complete . confirming to IP 65 protection and the height should be atleast 50 cm from ground level .The drawing should be approved by the deptt. |