Tender For Renovation Of Control Room Building And Other Civil Works For Yard At 33 Kv S/S Hudla Gwarki And Norangwada - 1 PART-A (Bldg.) 2 Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth upto 30 cm measured at a height of 1 m above ground level and removal of rubbish upto a distance of 50 m outside the periphery of the area cleared.(B 1.31) 3 B 1.8Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including taking out the excavated soil and depositing and refilling of jhiri with watering & ramming and disposal of surplus excavated soil as directed with in a lead of 50 meter.All kinds of soils 4 B 3.1.6 Providing & Laying in position cement concrete i/c curing, compaction etc. complete in specified grade excluding the cost of centering and shuttering – All work up to plinth level.: (A) 1:4:8 (1 cement:4 course sand: 8 graded stone aggregate 40 mm nominal size). 5 6.1.6/B-6Random Rubble stone masonry for with hard stone in foundation and plinth in Cement Sand mortar above 30 CM thick wall in:l in Cement sand Mortar 1:6 (1- Cement: 6- Sand). 6 B 6.2.6 Random Rubble stone masonry with hard stone in superstructure aboveplinth level and upto five levelabove 30cm. thick walls in : 7 5.2.2/B-5Brick masonry with F.P.S. bricks of class designation 75 in Super structure above plinth level upto floor 5th level in all shapes and sizes in cement mortar 1:6 (1- cement: 6- coarse sand). 8 5.8.3/B-5Half brick masonry in super structure, above plinth levelupto 5th level using bricks of designation 75 in Cement mortar 1: 6 (1- Cement: 6- Coarse sand). 9 Add extra for Random Rubble stone masonry with hard stone in(A) Wall upto 30cm. and less thickness. (B 6.3.4) 10 (B)Square or Rectangular pillars (B 6.3.1) 11 3.8/B-3P/F precast cement concrete coping 1:2:4 mix 50 mm thick complete as per specifications 50mm 12 Pointingonstonemasonryincementsandmortar 1:3 (1 cement : 3 sand) : Raised and cut pointing.(B 12.31.2) 13 8.13.2.1/B-8Providing and fixing external grade board solid core single leaf flush door shutters ISI 2202-67 marked using Phenol formal dehyderesin in glue both sides with approved steel fittings complete as per annexure ‘A’ 30mm thick. Commercial veneer both side. 14 B 8.14 Extra for providing external lipping with 2ndclass teak wood battens 6 mm minimum depth on all edges of shutters (over all area of door shutter to be measured) Over item no. 8.13. 15 9.17.1/B-9Providing and fixing M.S. sheet 1mm thicksingle leaf door shutter in angle iron frame 35x35x5mm suitabilly diagonally braced with 25x3mm flat iron above and below lock rail of size 50x5mm beading extra including all fittings, as per direction of Engg. incharge but excluding cost of chowkhats: including two coats of anit-corrosive red oxide primer paint add extra for double leaf 16 12.3.2/B-12Plaster on new surface on walls in cement sand mortar 1:6 including racking of joint etc. complete fine finished: (A) 20mm thick 17 (B) 12mm thick (B 12.3.3) 18 9.26/B-9Supplyingand fixing fixed wire gauge of 14 mesh X 24 gauge to the metal frame of rolled section by metal beading 20X3 mm with suitable screw at not exceeding 150 mm distance. 19 B 13.4.1. Renewing glass panes,with putty and nails wherever necessaryFloat glass panes of thickness 4 mm 20 12.5/B-126mm thick cement plaster to celling of mix 1:3 (1 cement : 3 fine sand) 21 B 10.17.1 Grading roof for water proofing treatment withwater proffing compoundCement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) 22 11.3.2 /B-11Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement including cement slurry, making of lines or groove etc complete but excluding the cost of nosing of steps etc. complete.(A) 75mmthickwith20mmthicknominalsizeaggregate. 23 Dismantling old plaster or skirting, raking out joints and cleaning the surface for plaster including disposal of rubbish to the dumping ground within 50 meter lead.(B 14.55) 24 B 13.29Repair to damaged RCC slabs, beams and columns etc for strengtheing with cement mortar 1 : 2 in following stepsi) Choping losse and cracked concrete to required depth, cleaning the exposed surface of steel and concrete with wire brush and sand papering , cleaning of concrete surface with water as necessary and getting dried.ii) Applying Epoxy primer on the exposed steel bars.iii) Applying Epoxy hardener and resin mix (as per manufectureds specification) on concrete and steel bars with brush.iv)Speading dry cement mortar 1 : 2 mix over epoxy treated wet surface and allow it to dry for one day.v) Plastering the surface with cement sand mortar 1 : 3 upto depth of 30mm complete.vi) Cure the plastered surface for 15 days All work including scaffolding etc. complete in all respect. 25 B 13.1Repairs to plaster of thickness 12mm to 20mm in patches of area 2.5 sq. metres and under including cutting the patch in proper shape, raking out joints and preparing and plastering the surface of the walls complete including disposal of rubbish to the dumping ground within 50 m lead :With cement mortar 1 :4 ( 1 cement : 4 coarse sand) 26 9.8.1/B-9Providing and fixing steel gate, grating , and grills made of angles, tees, square bars, flats,or black pipe with holdfast and fittings complete as per design and drawing including cutting welding and fabrication with priming coat of red oxide 27 9.8.2/B-9Extra if square,rectangular hollow tubularsections are used or grill made by flats only 28 B 12.45.1Applying priming coat :With ready mix pink or gray primer of approved brand and manufacture on wood work hard and soft wood. 29 B 12.46.1Painting with synthetic enamel paint of approved brand and manufacture to give an even shade: (A) Two or more coats on new work. 30 R/6.7 (iii) (a)P & l of Interlocking M-30 grade concrete Block pavements having thickness 80 mm as per drawings & MoRD Specification Clause 1504 with M-30 Grade 0.30 Mtr X 0.30 Mtr X 0.15 Mtr Edge Blocks. Category A Dentated units to key into each other on all four faces zigzag shape as per IRC: SP:63-2004. 31 12.37.1 /B-12Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade including all scaffolding: (A) old work(two or more coats) over and i/c scrapping and priming coat with cement primer.Colur Same 32 B 12.43.2 Painting exterior surface ofWallwith 100% acrylic exterior paint of approved brand and manufacture to give an even shade with two or more coats including prepartion of base with sand papering, primer, putty,etc complete in all respect including scaffolding and safety provision old work 33 B 13.12Repair to stone masonary in cement sand mortar 1:6 with old and new stone. 34 Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminummaterial with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass coverand secondary lens on each LED & should be SMD type of 3 to 5 watt each . The System efficacy >=125 lm/ wt and potted driver& has a unique BIS R number withInput Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety , Power Factor >0.95 driverEfficiency >85%,THD(I) <10%Humidity 10% to 90% RH Working Temp -5C to 45C .driver current <750mA. The luminaireshall be BIS certified and Trade mark certified. Life ExpectancyEqual or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs.Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR .(A) LED Street Light fixture with Minimum lumen output 11225 lm. (E 18.12.6) 35 (B) LED Street Light fixture with Minimum lumen output 2450 lm. (E 18.12.1) 36 1.14.3/S-1P & F Ist quality WVC urinal (IS : 2556 mark) with 25 mm dia G.I. waste pipe, dome waste couplings, concealed iron brackets or screws etc: complete Mini stall size 455x385x350mm. 37 1.20.2/S-3P & F Low level Flushing Cistern of 10 litres capacity (IS : 2556mark). Of approved make with complete fittings C.I. brackets duly painted, brass ball cock with ball, (IS: 1703 mark) complete including cutting and making good the wall: PVC with PVC bend as per IS : 7231 . 38 1.36.3/S-1P & F WVC Wash basin (Ist quality IS:2556 Mark) of approved make with C.I. brackets duly painted 1 No. 15 mm C.P. Pillar cock (IS:8934 Mark) & 32 mm C.P. brass waste coupling of approved make, P.V.C Waste pipe with PVC nut 32 mm complete including cutting & making good the wall :size 550x400 mm 39 2.13.2/S-2P &F 15mm Dia Connection Pipe of approved quality/make PVC pipe with C.P. brass nuts upto length, 370mm 40 2.7.3 /S-2P & F Bib cock (IS: 8931 Mark), Superior quality of approved make:(A) C.P. brass bib cock 15mm nominal bore. 41 2.11.2/S-2P & F Ball Cock (IS: 1703 Mark) with Rod & P.V.C. Ball complete: Brass wt. not less than 400gm 20mm 42 2.12.1/S-2P & F Inlet Connection (Angle Valves) Superior quality, of approved make, for Wash basin, Gyser etc. C.P. inlet connection 15mm Brass(Is: 8931 marked) 43 2.15.1 /S-2P & F Full - way Valve (IS: 778 Mark) or wheel valve of approved make:(A) Gun metal 15 mm nominal bore 44 (B) Gun metal 25 mm nominal bore (S 2.15.3) 45 2.26.3/S-2P & F PVC Storage Tank ( IS: 12701 marked indicating the BIS license No), of approved make with cover, 25mm dia 1M long G.I. over-flow pipe & 25 CM long wash out pipe with plug & socket, including making connection etc., complete of approvrd design: 500 ltr capacity 46 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes (IS 15778 : 2007 code) having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1 metre spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. (Internal work Exposed on wall) (A) 20mm nominal size (S 2.37.2) 47 (B) 25mm nominal outer dia pipes (S 2.37.3) 48 2.39.2/SProviding and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings, this included jointing of pipes & fittings with one step CPVC solvent cement , trenching refilling & testing of joints complete as per direction of Engineer in Charge.(External work).(A) 20mm nominal outer dia pipes 49 (B) 25mm nominal outer dia pipes (S 2.39.3) 50 3.3.1/SProviding & Laying C.C. 1:5:10 (Stone aggregate 40mm nominal size) upto haunches of S.W. pipes including 150 mm thick bed concrete (Width W= Dia of pipe in Cm+ 30Cm.) concrete width to be reduced from width W at center of pipe to `0` at top of pipe.(Excluding cost of pipe) 100mm dia S.W. pipe 51 S 3.22.3Construction of soakage well in all type of soil with 300 mm thick dry masonry, top and bottom 300 mm course in CM 1:6, 80mm thick stone slab, jointing of slab in CM 1 : 3, Ralthal, Kharanja, 40 mm thick M-15 grade C.C flooring , earthwork complete as per approved drawing including disposal of earth within a lead of 50 mtr.:Size 240 Cm. dia outside & 240 Cm. depth. 52 3.19.1/s-3Construction of manhole in all type of soil inner size 90 X 60 Cm. 300 mm thick masonry in CM 1:6, 10 Cm. thick cement concrete 1:5:10 in foundation, 20 mm thick inside plaster in CM 1:6, finished with floating neat cement, 50mm thick M-15 grade C.C. flooring, making channels, 80mm thick stone slab covering with 40mm thick M-15 grade C.C. flooring, Cement cover with frame of 450mm dia, earthwork etc. complete as per design including disposal of surplus earth within 50 mtr. lead.Depth up to 0.5 M 53 P & F Grating of approved quality/ make Stainless steel sheet size 125 mm dia. (S 1.48.1) 54 3.16.2 /S-3P & F rigid PVC pipe ( IS: 4985 make) class II/(4 Kg./Cm2). Approved quality /make including jointing the pipe with solvent cement rubber ring and lubricant.(A)110mm dia. (3.16.3) 55 3.17.9/S-3P & F rigid PVC pipe fitting ( IS: 4985 make) of approved quality /make including jointing the pipe with solvent cement rubber ring and lubricant.(A) Bend 87.5 110mm dia 56 E 1.1.1Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694)inrecessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & itsISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thickHot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws,making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheets & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure A attached with this BSR(A) Short point (up to 3 mtr.) 57 (B) Medium point (up to 6mtr). (E1.1.2) 58 (C) Long point (up to 10mtr).(E1.1.3) 59 E 1.3.1Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal sizeFR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) inrecessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & its ISI marked (IS:3419-1988)accessories, Hot Dipped GalvanizedModular box of 1.2 mm thick with earth terminal, 10 A modularswitch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheets & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure A attached with this BSRon board. 60 Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,in existingsurface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure A attached with this BSR(A) 2 x 2.5 sq. mm. + 1x1.5sqmm (E 4.1.7) 61 (B) 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. (E 4.1.14) 62 E 7.36Providing and fixing of power plug point with non modular accessories as per PWD specification for electrical Works withGalvanized box of 1.2 mm thickwith earth terminal with suitable size phenolic laminated sheet (IS : 2036 -1995) cover including cost of 16 amp. Switch (IS :3854) and 3/6 pin 16 amp. socket outletmaking connection , testing , etc. as required. . For specification ofWiring accessories refer ChapterE - 07 related item &For additional technical parameters of product / work refer Annexure A attached with this BSR 63 E 6.1.1.2Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load andsite requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted inexisting distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above ratingincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure A attached with this BSR 6A to 32 A rating.single pole mcb 64 E 6.2.1.2Providing & Fixing of 240/415 V isolatorISI marked IS:13947-III/conforming to IEC 60947-3, suitable for AC22A utilization category, 4KV impulse withstand voltage,true contact indication,Red colour dolly / lever shall have single mould covering over all poles for operation , two position din rail mounting,minimum phase termination capacity of 35sq.mm.IP 20 contact protection and fitted in existing distribution board / sheetincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure A attached with this BSR Double pole isolator 63 A rating 65 Providing & Fixing of Recessed/surface mounting heavy duty Enclosure made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. powder painted complete with din rail making internal DB terminations with copper lugs, detachable gland plate, including making connections, testing etc. as required.For additional technical parameters of product / work refer Annexure A attached with this BSR Suitable for Six / Eight module for MCB/ RCCB. (E 6.9.2) 66 Providing & Fixing of ISI marked (IS:1258) batten/angle lampholder with CM/L no. printed and made out from industrial grade Polycarbonate or fire resistant ABS material, brass terminal & captive screwsincluding making connection testing etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR .(E 7.13) 67 Providing & Fixing of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminiumhousing with in built driver, System lumen efficacy ≥ 110 lm/Watt output, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , Maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR . 1170mm(+/-10%) LED batten with min. lumen output 2200 lm (E 17.1.1) 68 P & F 1.2mm thickM.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm,12 mm dia rod fan hook with 100 mmlength extended on each side . All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure A attached with this BSR. (E 5.9) 69 Providing & Fixing of IS 11037:1984marked non modular socket size flush type 120 watt rotary minimum 5 step fan regulator with CM/L no. printed and made out from industrial grade Polycarbonate or fire resistant ABS material including making connection testing etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR .(E 7.20) 70 Providing & Fixing ofBEEStar rated copper wounded double ball bearing capacitor start, aluminium body & Metallicblade ceilingfanConforming to all the performance requirements laid down in IS 374:2019 including all amendments, as applicable ; & Carry BIS licensing (i.e. ISI marking) with down rod up to 80 cm with secondary support safety cable ( steel rope) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR .1200 mm Sweep BEE 1 Star rated (service value >=4.0 to < 4.5 ) (E 15.7.1) 71 Supply and erection of P.C.C. pole as per REC manual no 15/1979 (ammended upto date) and as per latest Discom specifications with factor of safety 2.5including excavation of pit upto pole planting depth 1/6th of pole length. and back filling with stone aggregate/boulders and soil by ramming and watering etc complete as required. All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure A attached with this BSR.8.0 Mtr long PCC pole of 200 Kg Working Load. (E 19.1.1) 72 Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have its own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure A attached with this BSR(A) 6.0 Sq. mm 2 core. (E 11.2.2.1) 73 (B) 4.0 Sq. mm 2 core. (E 11.2.1.1) 74 Providing & Fixing of Street light bracket made out from following size of B class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure A attached with this BSR .20 mm Dia. (E18.18.1)