| 1 | Supply, installation, testing & commissioning of 11 KV HT panel, 400 A,3 pole, 50 HZ , 13.1 KA for 3 sec rupturing capacity, floor mounted, compartmentalised, outdoor type,free standing [grouted in PCC 1:2:4 type B1(Using 20 mm graded crushed stone aggregate)],duly labelled with vinyl stickers, modular construction, 4 wayHT Panel fabricated in minimum 3mm thick CRCA sheet , supported with suitable sizebase channel not less than 75x75x5 mm,painted in Siemens Grey shade RAL 703, compartmentalised, dust and vermin proof, IP 54 protection with bus /PT/relay compartment having IP 54 , doors and covers with non-ageinggasket, doors with concealed hinges with handle and locking facility, electrolytic grade copper bus bar of rectangular cross section of adequate size of OEM recommedation for 600 A , cable glands, cable bottom entry for incoming and outgoing cable, danger plate,thermostatically controlled strip heater with provision of double earthing terminals, lifting studs, louvers for proper ventilation covered with fine GI screen comprising of following : - |
| 2 | (a) 11 KV, 3 pole, 50 HZ 400 A draw out type VCB -06 Nos ( 01 No for incoming, 05 Nos for outgoing) confirming to IEC 62271-100 and 62271-200 ,E2 class,rupturing capacity 13.1 KA for 03 sec, manual and motorised spring charging mechanism suitable to operate by 240 volts, 1 P/110 V DC supply 24 volt DC universal motor 200 wattsand having charging time less than 10 seconds or as all per OEM design,with overload, earth fault and short-circuit protection, interrupter life minimum 30000 times at rated current and minimum 100 times at short circuit current and all outgoings should be connected through copper busbar of adequate size as per OEM recommendations.(b) Dual core dual ratio Current Transformer (CT) chamber, class E insulation, comprising of 3 Nos, single phase resin cast / ring core CTs of 200-100 / 5+5, burden not less than 15 VA and accuracy class 0.5, for metering, having class SP10 for protection as per IS:2705 for each circuit breaker - 06 Sets for 06 VCBs. |
| 3 | (c)1 No. Potential Transformer (PT), 3 phase, dry type (resin cast) fixed type 11 KV / 110 Volts, class \"E\" insulation, Burden 100 VA, Accuracy class 0.5 with HT HRC fuses & TPN MCBfor primary and secondary respectivelycomplete all as specified and as directed as per IS: 3156 - 01 Set (For Incoming) (d) SCADA compatibleself-powered , programmable type IDMT numerical relays having overload, earth fault and short circuit tripping facility, facility to record fault event with fault current and nature of fault , adjustableover current & earth fault and fault time setting (separate for earth fault and overcurrent), suitable DC auxiliary supply, housed on horizontal draw out type case, flush pattern with accessories duly connected with trip and alarm system -06 Nos total for complete protection of HT ,11 KV,3 Phase feederMODBUS communication on RS 485 communication port - 06 Nos including 1 No voltage monitoring relay for under voltage / over voltage protection -06 Nos (e) One set of mechanical indicator for ON / OFF indication for all VCB. |
| 4 | (f) LED type indication lamps for CB ON, CB Close, CB trip, spring charged , Trip circuit healthy with push button and oneset of capacitive voltage indication for R-Y-B -01 set for each VCB (g) One set of battery and battery charger to provide suitable back up as per OEM\"s instruction (h) Digital PT operated Voltmeter with inbuilt selector switch suitable for 11KV , 3 phase, 50 HZ CBs with accuracy class 0.5 - 5 set(j) Digital CT operated Ammeter with inbuilt selector switch suitable for 11KV , 3 phase, 50 HZ,200-100 / 5+5 CTs with accuracy class 0.5 - 6 set (k) Power pack suitable capacity with maintenance free battery and charger to provide required aux supply to VCBs as per OEM recommendation (l) Any other standard fittings / accessories required for smooth functioning of HT panel Note : -1. HT panel will be installed and commissioned by OEM at site including relay calibration as directed by Engineer-in-Charge. 2. The job includes all control wiring with suitable size of copper conductor (minimum 2.5 Sqmm), necessary electrical connection and civil work. |
| 5 | S&F steel tubular swaged poles complete with cast iron base plate of size 300 mm x 300mm x 6 mm thick ,finial taper plug,bolts,nuts and screws as specifiedtype 410 SP-55 (11 meters long) Including all necessary excavation & earth work in any type of soil for foundation of poles,PCC 1:4:8 type (D-2) (using 40 mm graded stone aggregate ) in padding concrete ofsize 1.20 m X 0.60 m X 0.15 m belowGL,PCC 1:3:6 type (C-2) (using 40 mm graded stone aggregate ) in foundations of size 1.20 m X 0.60 m X 1.50 m belowGL, PCC 1:2:4 type (B- 1 )(using 20 mm graded stone aggregate) in plinth block(coping) of size 600 X 600 X 300 mm above GLcomplete all as specified and directed. |
| 6 | Supply, stringing and fixing ofAluminium conductor steel reinforced (ACSR) OH conductor of any type including binding wire complete all as specified and as directed. |
| 7 | M &L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed. |
| 8 | Supply and fix gang operated air break switches, triple pole, manually operated, mounted on insulators and steel frame, with operating mechanism worked from ground level Vertical type for rating upto 200 Amps, 11000 volts complete with GI operating pipe of heavy duty all as directed. |
| 9 | Supply and fix lightning arrester expulsion type complete with all fttings, transmission class, discharge capacity 65 kilo amp ,11000 volts capacity pole mountedcomplete all as specified and as directed. |
| 10 | M & L for Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150mm, height, 150mm dia for 11000 volts grade all as specified and as directed. |
| 11 | S/FDisc type insulator, porcelain, vitreous 145mm high and 255 mm dia ball and socket type,brown coloured Single disc assembly for 11000volts grade complete all as specified and as directed. |
| 12 | Supply and Fix horn gap type fuse unit upto 25 Amps capacity, mounted on insulators and steel frame operated mechanism worked from ground level single pole 11 kV dropout lift off (DOLO) complete all as specifed and directed. |
| 13 | M&L for Danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and fixed with MS clamps, bolts and nuts of approved size, for HT, 25X15 cm size complete all as specified and directed |
| 14 | Supply of servo controlled voltage stabilizer (Confirming to as per BIS 9815 : Part I : 1994), Three phase AC system, 50 Hz of capacity 10 KVA , Naturally oil cooled, indoor, unbalance type load, copper wound, with microprocessor based control card, digital type, relay free smooth and silent operation with 1st filling of new insulating oil as per BIS standard packed in sealed containers, including necessary incoming and outgoing connection, complete all as specified andhaving following specifications : (a) Input voltage 360 V to 480V ( or as customer requirements)(b) Output voltage stabilized at any designed/desired voltage 415V +2.5% (c) Rated frequency 50Hz (d) No distortion in wave form (e) Response time not to exceed 10 milli seconds (f) Sensitivity (+) 1% (g) Rate of correction 8 volt /second(h) Efficiency more than 98% (i) Type of load : Three phase, unbalanced type (j) Multifunction meter 3 phase 415 volts showing Voltage, Amps & Hz. (k) Oil quantity as recommended by manufacturer complete with oil level indicator showing minimum and maximum level of oil and temperature gauge. |
| 15 | (l) Charging motor of suitable capacity.(m) Termination : Input & output termination as per IS : 3347.(n) Operation : Auto or Manual. (o) Metering : Digital AC voltmeter with selector switch for input & Output voltage. PROTECTION (i) Overload Cut-Off and short circuit Protection (ii) High/Low voltage cut off (iii) Bypass arrangement in case of emergency (iv) Single phase Prevention. (v) Spike and surge protection (vi) Earth Fault protection.INDICATOR DIGITAL:-(i) Power indicator(ii) Voltage indicator(iii) Frequency Meter(iv) Power Factor indicator(v) Ammeter, Temperature Meter, Digital Ammeter& Digital voltmeter.(vi) Phase sequence indicatior.(vii)Oil level indicator |
| 16 | Supply of servo controlled voltage stabilizer (Confirming to as per BIS 9815 : Part I : 1994), Three phase AC system, 50 Hz of capacity 100 KVANaturally oil cooled, indoor, unbalance type load, copper wound, with microprocessor based control card, digital type, relay free smooth and silent operation with 1st filling of new insulating oil as per BIS standard packed in sealed containers, including necessary incoming and outgoing connection, complete all as specified andhaving following specifications : (a) Input voltage 360 V to 480V ( or as customer requirements)(b) Output voltage stabilized at any designed/desired voltage 415V +2.5% (c) Rated frequency 50Hz (d) No distortion in wave form(e) Response time not to exceed 10 milli seconds (f) Sensitivity (+) 1%(g) Rate of correction 8 volt /second (h) Efficiency more than 98% (i) Type of load : Three phase, unbalanced type (j) Multifunction meter 3 phase 415 volts showing Voltage, Amps & Hz. (k) Oil quantity as recommended by manufacturer complete with oil level indicator showingminimum and maximum level of oil and temperature gauge. |
| 17 | (l) Charging motor of suitable capacity.(m) Termination : Input & output termination as per IS : 3347.(n) Operation : Auto or Manual.(o) Metering : Digital AC voltmeter with selector switch for input & Output voltage. PROTECTION (i) Overload Cut-Off and short circuit Protection (ii) High/Low voltage cut off (iii) Bypass arrangement in case of emergency (iv) Single phase Prevention. (v) Spike and surge protection (vi) Earth Fault protection.INDICATOR DIGITAL:-(i) Power indicator(ii) Voltage indicator(iii) Frequency Meter(iv) Power Factor indicator(v) Ammeter, Temperature Meter, Digital Ammeter& Digital voltmeter.(vi) Phase sequence indicatior.(vii)Oil level indicator |
| 18 | Supply install testing and commissioning ISOLATION TRANSFORMER Indoor type- suitable for IP 23 enclosure, 415 volts at no loadAC 3 phase 50 Hz capacity 10 KVA, ratio 1:1,with suitable MCCB, core type double copper wound ONAN cooled Oil immersed delta connected on primary side and star connected on secondary side in accordance with vector symbol DYN-II (vector group) with first filling of transformer oilof requisite dielectric strength up to level, with neutral brought out on secondary side (LV side) and having tapping at +5% in steps of2.5% by means of off circuit tap link board.The maximum temperature rise 115 degree calsius by winding resistance method after continuous full load on an ambient temp of 50 degree Celsius.The transformer shall be confirming to IS: 1180: 2014 and shall comprise of the following:- (a) Rating and diagram plate. (b) Two earthing terminals in two side. (c) Lifting lugs .(d) Off circuit link board. (e) Base channel with Bi- directional Rollers. (f) Danger board (g) 100 mm dial type thermometer. (h) Cable entry boxes etc complete as reqd. |
| 19 | Supply install testing and commissioning ISOLATION TRANSFORMER Indoor type- suitable for IP 23 enclosure, 415 volts at no loadAC 3 phase 50 Hz capacity 100 KVA,ratio 1:1, with suitable MCCB,core type double copper wound ONAN cooled Oil immersed delta connected on primary side and star connected on secondary side in accordance with vector symbol DYN-II (vector group), with first filling of transformer oilof requisite dielectric strength up to level,with neutral brought out on secondary side (LV side) and having tapping at +5% in steps of2.5% by means of off circuit tap link board.The maximum temperature rise 115 degree calsius by winding resistance method after continuous full load on an ambient temp of 50 degree Celsius.The transformer shall be confirming to IS: 1180: 2014 and shall comprise of the following:- (a) Rating and diagram plate. (b) Two earthing terminals in two side. (c) Lifting lugs .(d) Off circuit link board. (e) Base channel with Bi- directional Rollers. (f) Danger board (g) 100 mm dial type thermometer. (h) Cable entry boxes etccomplete as reqd. |
| 20 | Supply and fixingof GI tubing, medium grade, 40 mm bore with all fitting laid in trenches / pole / wall for protection of cables in repairs complete. |
| 21 | M&L for cutting /Drilling existing steel tubing for alteration or addition all as specified and as directed for the following size 40-50 mm |
| 22 | Supply,installation,testing&commissioningof Indoor type HT 11 KV, 3 phase, 50 Hz totally enclosed metal clad switchgear complete with Vacuum circuit breaker having rupturing capacity 250 MVA, 13.1KA , freestanding groutedinPCC1:2:4typeB1(Using20mmgradedcrushedstoneaggregate)], duly labelled withvinylstickers overload and earth fault protection, (a)LEDtypeindicationlampsforCBON,CBClose,CBtrip,springcharged,Tripcircuit healthywithpushbuttonandone setofcapacitivevoltageindicationforR-Y-B- 01set voltmeterOnesetofbatteryandbatterychargertoprovidesuitablebackupasper OEM\"sinstruction(b)DigitalPToperatedVoltmeterwithinbuiltselectorswitchsuitablefor 11 KV, 3 phase, 50 HZ CBs with accuracy class 0.5 and of rating upto 400 Amp- 01 set (c)Digital CToperated Ammeterwith inbuiltselector switchsuitablefor11 KV, 3phase, 50 HZ, 100-50 /5+5 CTs with accuracy class 0.5 -1 set(k) Powerpack suitablecapacity with maintenancefreebatteryandchargertoproviderequiredauxsupplytoVCBsasperOEM recommendation-01 set(l)Anyotherstandardfittings/accessoriesrequiredforsmooth functioning of VCB panel complete all as specified and directed. |
| 23 | (a) All VCB\"s shall be motorized with 110 V DC control voltage to operate two position double spring mechanism. Each VCB shall have green (on)/ Red (off) push buttons to operate & Live cable LED indicators through voltage dividers mounted on the bushing.(b) Theearthing shall be provided in each cable compartment to provide solid earthing for the cable shield . Each VCB(except bus Coupler) incoming and outgoing shall be equipped with digital MFMto measure Amps , Volts , Frequency, PF, KWH , KVAR etc & 3 O/C +1 E/F self powered numerical protection relay with low and high set for over current and Earth Fault . Relay should have facility to display the maximum loaded phase current also. Relay shall record minimum 5 faults records with time stamping or as per manufacturer design. |
| 24 | (c) incomer 400 Amp VCB along with off load isolator and fault making type earthing switch. Resin cast ring dual core dual ratiotype CT\"s 100-50/1 or 5 Protection Class 5P10- set and PT 11 KV/110 volt AC on incoming.(d) outgoing 400 Amp VCB along with off load isolator and fault making type earthing switch. Resin cast ring dual core dual ratiotype CT\"s 100-50/1 or 5 Protection Class 5P10- & Metering 100-50/1 or 5, CI 0.5-1 sets on outgoing |
| 25 | Note:(i) Configuration and Schematics arrangement of VCB Shall be got approved from Garrison Engineer before fabrication. (ii) Any other parts/items not specified above but have been required essential for smooth and safe functioning of the VCB shall be quoted rate (iii) The VCB will be tested as site as primary injector system and relay will be set as per load requirement (iv) VCB should have heating element with thermostat to avoid moisture condensation in the panel. (v) VCB willbe installedandcommissionedbyOEM at site includingrelay calibrationasdirectedbyEngineer-in-Charge.2.Thejobincludesallcontrolwiringwith suitablesizeofcopperconductor(minimum2.5 Sqmm),necessary electricalconnection and civil work. |
| 26 | Supply, Laying , commissioning & Testing of HT XLPE cable on pole/STR with suitable size of GI clamps made out of GI strip 32mm X 6mm, XLPE insulated screened, earthed, PVC bedded, galvanised steel strip, electric power cable (heavy duty) with aluminium conductor 11000 Volt grade (Earthed) IS: 7098 (Part II) 6.35 KV /11 KV (E) cross section area 95 Sq.mm 3 core alongwith S & F HT cable route indicator at every 100 mtr with suitable foundation complete all as specified and directed.Note :- (i) excavation, earth work, cable cover, sand cushioningand GI pipe etc shall be measured & paid separately in respective items. (ii) high voltage test to be conducted at site with suitable voltage before and after laying of HT cable and reading shall be recorded jointly and test report to be submitted in triplicate to the EIC. The cost of the same shall be deemed to be included in the quoted unit rate. |
| 27 | Supply, Laying , commissioning & Testing of cable in pipes/ ducts/ poles/ trenches/ under floor/ under road XLPE insulated cable screened PVC bedded galvanised steel strip armoured,electric power cable heavy duty with aluminium conductor 11000 Volt grade (Earthed) IS: 7098 (Part II) 6.35 KV /11 KV (E) cross section area 95 Sq.mm 3 core complete all as specified and directed..Note :-excavation, earth work, cable cover, sand cushioningand GI pipe etc shall be measured & paid for separately |
| 28 | Supply Jointing and testing of Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and as directed. |
| 29 | Supply Jointing and testing of Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and as directed. |
| 30 | Supply Jointing and testing of Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and as directed. |
| 31 | Supply laying jointing and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of following sizes. |
| 32 | cross sectional area 35 Sqmm x 3.5 core |
| 33 | cross sectional area 50 Sqmm x 3.5 core |
| 34 | cross sectional area95 Sqmm x 3.5 core |
| 35 | Supply, jointing and testing of cable jointing kit for 1100 V grade cable for indoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 16 to 50 sqmm, complete all as specified and directed |
| 36 | Supply, jointing and testing of cable jointing kit for 1100 V grade cable for indoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 to 95 sqmm, complete all as specified and directed |
| 37 | M & L Earthing complete with galvanised steel earth plate electrode 600mm X 600 mm X 6.30mm thick burried directly in ground (earth plate not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to and including GI earth lead of GI strip 32X6mm size by means of steel bolts,nuts, check nuts and washers test points made of GI strip 40X8mm, 10 cm long , PCC 1:2:4 type B-1 in pit, angle iron 25X25X3mm frame work with precast RCC 1:2:4 type B-1 cover reinforced with 8mm dia TMT bars @ 150mm C/C both ways abd 12mm dia MS fabricated handle, medium grade GI watering pipe 20mm bore with funnel, wire mess and light grade GI protection pipe 40mm bore upto 5m lenght for drawing in earth lead ,salt,charcol etc. including excavation and earth work in any type of soil , removal of surplus soil to a distance not exceeding 50m complete all as shown in electrical plate No. 5 of MES schedule 2009 part-I and connected complete all as specified including testing on completion.Note : Main earth strip beyond 7.5 meter shall measured and paid separately. |
| 38 | Supply and fixing earth continuity conductor of main earthing lead 32X6 mm galvanised steel strip/earth lead laid in pipe/fixed on walls or any other position including jointing by tinned copper/brass nuts bolts and washers in addition to brazing at every joint complete all as specified and directed. |
| 39 | M&L for boring of horizontally holes under the road below 1.0 mtr from the road/hard surface by trenchless techonology using ultra sound technique and inclduing necessary machine without damaging the existing road and getting out in any type of soil and disposal of soil to a distance not exceeding 50m from the site of work including supply & laying HDPE pipe up to 150 mm dia suitable for 0.6 MPA work pressure . |
| 40 | Supply and laying of insulating mats 2.5mm thick made of elastometer ( a generic term that includes rubbers, latex and elastomeric compounds that may be natural or synthetic or a mixture or a combination of both) for use as floor covering for the protection of workers on AC and DC installation with the system voltags up to 11 KV AC and 240V DC and as per CI 5 of IS15652 latest class B cat II of size 1m X 2m complete with relevant test report and fixing on floor with suitable adhesive complete all as specified and as directed. Note : The mat should be permanently pasted with the help of suitable adhesive / resin. All joints and comers shall be filled / covered with insulating material of matching colour. Matching colour and matching designed tapes should be used to maintain an aesthetic look at the installation. |
| 41 | Supply of electric rubber hand gloves 11 KV as per ISI marked completeall as specified and as directed. |
| 42 | Excavation in trenches not exc1.5 min depthandnot exc 1.5 mtr wideincludinggetting out in soft/loose soil complete all as specified and as directed. |
| 43 | Excavation in trenches not exc1.5 min depthandnot exc 1.5 mtr wideincludinggetting out in hard/dense soil complete all as specified and as directed. |
| 44 | Returning filling in including leveling spreadingwatering and well ramming in layers not exceeding 25 cmthick in soft/loose soilcomplete all asspecified and directed . |
| 45 | Removing of surplus soil to a distance not exceeding 50 mtrand depositingwhere directed at a level not exceeding1.5 mtr above the starting point complete all as specified and as directed. |
| 46 | Supply & laying sand cushioning for cable protection in trenches 8 cm thick before laying cable and 15 cm thick over the cable as loose sand thickness complete all as specified and ditected.Note: Sand cushioning thickness (8 cm+15 cm=23 cm) are punned thickness and only Punned thickness will be measured and paid. |
| 47 | Supply and laying un-reinforced precast concrete cable covers,factory made, class-HV, Type-I, flat, as per IS 5820, ofsize 300mmx180mmx40mm laid dry complete all as specified and as directed. |
| 48 | M&L for laying of bricks subclass ‘B’ old size laid flat perpendicular to the direction of cable for protection of cable complete all as specified. |