Tender For Integration Of New01 Nos. 33Cap. Bay, Providing And Installation Of New Gateway And Rectification Of Sas Installed At 132Kv Substation Auraiya Under Etd-Etawah., 1 Inspection And Rectification Ofalstom Make Substation Automation System Instal, Auraiya-Uttar Pradesh
TDR : 45465009
Tender Notice
BOQ
Expired
Auraiya
Uttar Pradesh
Tender For Integration Of New01 Nos. 33Cap. Bay, Providing And Installation Of New Gateway And Rectification Of Sas Installed At 132Kv Substation Auraiya Under Etd-Etawah., 1 Inspection And Rectification Ofalstom Make Substation Automation System Instal
Name of Work: FOR INTEGRATION OF NEW 01 NO., 33KV CAP. BAY, PROVIDING AND INSTALLATION OF NEW GATEWAY AND RECTIFICATION OF SAS INSTALLED AT 132KV SUBSTATION AURAIYA UNDER ETD, ETAWAH.
Sl. No.
Item Description
1
Inspection and rectification ofALSTOM make Substation Automation System installed at 132kv s/s Auraiya. The following works are including for healthy SCADA communication.(a) Replacing the defective armourd optical fiber cable and splicing it if required any anywhere in the Ring. (b) Replacing the defective FO multimod ST-ST port patch cords. (c) Checking & Rectifying the healthiness of LIUs and its communicating ports. (d) Checkingthe healthiness of IEC 61850-7 Ethernet switches. (e) Replacing the defective CAT-5/LAN cables and checking its healthiness. (f) Rectifyingcommunication healthiness of MOD Bus RTU for various MFM meters. . (h) Re-installation of old backupto SCADA. (I) Checking the healthiness of all protection relay\"s communication to SCADA. (j) Checking of all required events, alarms, numericals datas, status and signals to SCADA from various bays & feeders. (k) Checkingthe SLD of S/S to SCADA screen . (l) checking the all required operations of equipments from SCADA. (m) configuration of ethernet switches/modems/ RTU etc. if required. (n) installation of new window and DS AGILE software in standby PC, and reinstalling the old backup in HMI-2, making both HMI-1 & HMI-2 in all respect. at the time of rectification all required materials and computer parts will be arranged by department without extra charges, except the following given material will be provided by contractor.scada license key, activation key, old sas backup, and software CD will be provided by department.
2
Integration of33kv Capacitor bank bayIEC-61850 compliant IED with existing Substation Automation System.
3
work of Gateway remote data configuration to SLDC (Sending Data to remote station on protocol at IEC-101/104).
4
Providing & installation of New Gateway at 132kv s/s Auraiya with following specification as follows:- (1).Multiple-master communication capability(2). Support IEC60870-5-101/103/104, DNP3 serial/TCP MODBUS RTU/ASCII/TCP, IEC62056-DLMS, IEC61850, SNMP, SNTP, MQTT(3). Datapoint support :- 5000 (4.) PortConnectors :- 4 serial (RS232/485) and 2 Ethernet (5). Power supply (AC-DC) 85-265VAC 50-60HZ, 100-370VDC (6). Realiability :- IEC61850-3Complitant hardware, DNV certified IEC61850 server, HOT standby redundancy(7). Time sync basedon NTP/SNTP/NEMA/protocol specific synchronization (IEC104/DNP3.0etc)Suitable forexisting Alstom SCADAmake system as installed at 132kv s/s Auraiya.Work included as installation & all software configuration and its testing if requiredas per site condition and all other associated work to complete the job satisfactory
5
Supply of Fibre Optical Multimode patch cards for ST-ST, LC-LC, LC-ST, ports (each 5 meters).
6
Supply of Fibre Optical Multimode patch cards for ST-ST, LC-LC, LC-ST ports (each 10 meters).
7
Hot line stringing between the towers (NBDD+18and 220 KV Special Mono Pole Tower (30-60) (34 mtrs. Bottom Cross arms)) crossing of theNational highway(NH-86/NH-34) includes laying, tensioning, stringing, clamping, jointing etc. complete with ACSR Zebra of all Phases of both circuits including hoisting of insulator fittings of all neccessory hardware and accessories etc.(Note: No traffic block of NH will be arranged to complete the work)