| 1 | Disconnection & discharging (R.C./D.C. charge) of 33/0.433 KV transformer sub station from MPPKVVCL site for maintenance. |
| 2 | Cleaning and greesing all the conductive part of D.O. fuse, cable, AB switch & operating pipe of 33 KV sub station. |
| 3 | Providing & fixing of 33 KV lightning arrestor. |
| 4 | Providing & fixing of 33 KV A.B. post insulator. |
| 5 | Providing & fixing of 33 KV A.B. metal part |
| 6 | Providing of as per required hardware material (nut bolts, washer etc.) |
| 7 | Testing checking earth resistance checking of all the earth pits and providing report. |
| 8 | Testing checking insulation resistance checking of transformer and providing report. |
| 9 | Providing & sperading B.T. metal 40 mm |
| 10 | Providing & fitting 33 KV. D.O. fuse barrel. |
| 11 | Providing & fitting 33 KV. D.O. fuse. |
| 12 | Providing & fitting 33 KV. D.O. fuse assembly with brass parts. |
| 13 | Providing & fixing of 33 KV A.B. switch complete assembly. |
| 14 | Providing & fitting jumper of 075ACSR conductor for each point |
| 15 | Opening & fitting of top cover for 500 & 630 K.V.A. 33/0.44 KV transformer for complete over hauling work at site. |
| 16 | Providing & replacement of all the gaskets & packing of transformer 33 KV from top cover HV & LV side of 500/630 KVA 33/0.433 KV. |
| 17 | Providing & fixing of breather with silica gel for 500/630 KVA transformer. |
| 18 | Providing for E.H.V. GR-II transformer oil filtration. |
| 19 | Providing cost of E.H.V. GR-II transformer oil shortage quantity due to filtration. |
| 20 | Providing & painting of complete 33 KV outdor sub station structure & wire fencing boundry using aluminium paint & transformer using enameld paint as required. |
| 21 | Providing & fixing of copper earthing arrangement of 33 KV electric sub station lighting arreaster for earthing arrangement copper plate of 600×600×3 mm. size which includes following work digging of pit i/c packing of charcoal powder & salt as per specification watering pipe of 19 mm dia GI with funnel top etc making brick mesonary chamber with CI frame & cover complete as per IS specification. |
| 22 | Providing & fixing of 25×5 size copper strip to connect lighting arrester to copper earthing electrod. |
| 23 | Providing & fixing of danger board enameld type for 33 KV sub station yard. |