Name of Work :SPECIAL REPAIR OF FIRE FIGHTING SYSTEM AT AF STATION PANAGARH UNDER GE (AF) PANAGARH
Sl. No.
Item Description
1
Note :Prior to commencement of the subject works, the contractor needs to submit valid Electrical License in the name of himself/them self or Agreement with agency having valid Electrical License alongwith Agency\"s Electrical License to the Accepting Officer for his approval through GE. In absence of such documents, no work will be executed at site and to be treated as defaulter on the Contractor\"s part . In addition, Supervisor for execution of electrical works employed by the Contractor shall posses Supervisory Certificate of competency issued by concerned State Govt/Union Territory and the Worker/Tradesman for execution of Electrical Works must hold necessary permit issued by concerned State Govt/Union Territory.
2
Supply and fix smoke cum heat detector system designed for direct surface or electrical box mounting, sealed against back pressure, work in relative humidity range 10%-93%, voltage range15-32 volts DC peak ISO 9001 certified with detector base voltage range 15-32 volts, base dia 4 inches base height 18.8mm fixed to any type of ceiling and making good to surface complete as per existing make all as directed by Engineer-in-Charge.
3
Supply and fix manual call point ISO 9001 certified RH-10% to 93%, normal operating voltage 24 VDC temperature range 32F to 120F, shell door and handle are molded of durable polycarbonate as per existing make all as directed by Engineer-in-Charge.
4
Supply and fix CPU with power supply and data programming as per site requirement suitable to existing panels as per existing make all as directed by Engineer-in-Charge.
5
Supply and fix 2Cx1.5 sqmm FRLS Armoured Cable to connect all smoke cum detector, manual call point and existing control panels in a circuit in complete as per existing make all as directed by Engineer-in-Charge.
6
Supply and fix fire relay module for AHU tripping as per existing make all as directed by Engineer-in-Charge.
7
Supply and fix fault isolator module relative humidity range 10%-93%, voltage range 15-32 volts DC peak temperature range 32F to 120F as per existing make all as directed by Engineer-in-Charge.
8
Commissioning of Fire fighting system all as specified and as directed.
9
Supply and fixing standard short size gun metal branch pipe with gun metal nozzle 16 mm dia outlet with standard male instantaneous spring lock type 63 mm dia coupling. Branch pipe and nozzle shall confirm to IS : 903-1985 as per existing make all as directed by Engineer-in-Charge.
10
Supply and fixing 63 mm dia 15m long Reinforced Rupper Lined (RRL) woven jacketed hose tested to bursting pressure 32 Kg/sqcm as per existing make all as directed by Engineer in Charge.