Provision Of 250 Kva Trolley Mounted Transformer At Tangdhar Under Ge 874 Ews Provn Of 250 Kva Trolley Mounted Transformer At Tangdhar Under Ge 874 Ews, Srinagar-Jammu And Kashmir

Military Engineer Services-MES has published Provision Of 250 Kva Trolley Mounted Transformer At Tangdhar Under Ge 874 Ews Provn Of 250 Kva Trolley Mounted Transformer At Tangdhar Under Ge 874 Ews. Submission Date for this Tender is 14-06-2024. Transformer Supply Tenders in Srinagar Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

43361569
Corrigendum : Provision Of 250 Kva Trolley Mounted Transformer At Tangdhar Under Ge 874 Ews Provn Of 250 Kva Trolley Mounted Transformer At Tangdhar Under Ge 874 Ews
Open Tender
Indian
Jammu And Kashmir
Srinagar
14-06-2024

Tender Details

Provision Of 250 Kva Trolley Mounted Transformer At Tangdhar Under Ge 874 Ews Provn Of 250 Kva Trolley Mounted Transformer At Tangdhar Under Ge 874 Ews

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 03-Jun-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 10-06-2024
2 07-Jun-2024 Other Other 14-06-2024
3 07-Jun-2024 Date Date 14-06-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 25720.0 /-
Tender Value
INR 12.86 Lakhs /-

BOQ Items

Name of Work: PROVN OF 250 KVA TROLLEY MOUNTED TRANSFORMER AT TANGDHAR UNDER GE 874 EWS
Sl. No. Item Description
1Supply, installation, commissioning & testing of highly energy efficient, outdoor type oil immersed naturally cooled (ONAN) step down transformer copper wound type of capacity 250 KVA , 11 KV/440 volts (at full load), AC 3 Phase 50 Hz as per latest IS code, conforming to IS-1180, Level-II with off load tap changer on primary side to vary secondary voltage within limit (+) 5% to (-) 7.5% in step to 2.5% including standard fittings and first filling to transformer oil as per IS-335 of 1980 with cooling system. The transformer shall be provided with cable termination box to terminate outdoor type termination of suitable size on HT side 11 KV & LT side 1100 volts.Transformer step down ratio 11000 volts/ 433 volts, 3 phase 4 wire, impedance as per oil type, ONAN cooled, suitable for outdoor installations and double wound core type with cold rolled grain oriented silicon shell insulated laminations and clamped to minimize vibration and noise. The winding shall be copper and shall be designed for full load current and with stand the thermal and electro magnetic stresses arising due to the through fault current vector group shall be Dyn-11 including supply of all standard fittings & fixtures and comprising of the followings :-
2(a) HT cable termination box. (b) LT cable termination box. (c) Rating and diagram plate. (d) Earthing terminals. (e) Lifting lugs. (f) Oil level indicator with minimum level marking. (g) Thermometer pocket. (h) Conventional conservator with oil filling hole with cap and drain cum sampling valve. (j) Air release plug. (k) Silica gel breather. (l) Off circuit tap changer with locking provision. (m) Bi-directional rollers. (n) Jacking Pads. (o) Radiators/ Fins and all (Epoxy painted). (p) Danger Notice Board.
3M & L for XLPE insulated , screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts, Earthed grade cross sectional area 95 Sq mm, 3 core, ISI marked complete all as specified and as directed by Engineer-in-Charge.
4Material and labour for cable jointing kit for 11KV(Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm 3 core complete all as specified and as directed by Engineer-in-Charge.
5Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 Sq mm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
6Supply, Installation & Testing of outdoor type LT Control Panel, CPRI approved, suitable for 440 volts (Three phase 4 wire system), made out of 3.15mm thick powder coated CRCA sheet, front & back side openable type and front side with double door, fixed with hinges and knob including locking arrangement, dust, weather & vermin proof, cubicle type of size not less than 0.80 x 0.60 x 0.40 mtr and fixed with angle iron leg of size 32x32x6mm thick and 0.40 mtr long/ high - 04 Nos and welded the same and fixed on the trolly including high tensile nut, bolts and washers or welding etc, dully painted with two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete with and including copper bus bar of four pole in colour code of capacity 800 Amps, fixed over epoxy insulator with and including one No 600 Amps ACB 4 Pole 36 KA of microprocessor based thermal / magnetic controller including necessary copper spreader for main controlling switchgear with incoming and outgoing connection, Voltmeter 0-500 V - 01 No, Ammeter 0 to 600 Amps - 01 No, indicating lamp RYB - 01 Set, complete all as specified and directed by Engineer-in-Charge.
7M&L for fabrication of towing type transformer trolley suitable for 250 KVA transformer step down, outdoor type 11 KV/433 V of capacity complete made out of MS "I" beam of size 250 mm x 125mm x 6.9mm (40 Kg/mtr) and MS sheet for platform 6mm thick, mounted on 4 wheels size of 7.50/OR 16 (including wheel drums, bearings) with rims mounted on 02 Nos front and rear axle wheel with leaf spring clamps cushioning arrangement, between platform and 02 Nos front and rear axels, complete with towing arrangement with tow hook to take full load of trolley and transformer, Jalli (XPM) around platform on angle iron frame of size 40x40x5mm opening arrangements from both sidewith locking arrangements for loading and unloading of transformer including welding, bending and drilling holes, spray painting with two coats of synthetic enamel paints over a coat of red oxide primer over all surface, complete all as specified and directed by Engr-in-charge.
8(a) Size of the transformer trolley platform shall be 4 Mtr x 2.5 Mtr and sufficient space all around after transformer installation for ventilattion/ maint purpose as recommended by OEM and accomodate HT/ LT connecting cables loops on the platform. (b) The trolley shall be provided with steel square net of suitable guage fixed on angle iron in all around the trolley body with opening arrangement as protection. (c) Necessary provision for PVC insulated heavy duty copper cable multistranded single core 95 sqmm with cable lugs to connect the earting as cut to required length - 50 mtrs. Notes :- (i)Any other works not mentioned in item above but required for smooth functioning of trolley shall be deemed to be included in the rates quoted by the contractor. (ii) The technical drawings and details of schedule "A" item Nos 1, 5 & 6 shall be submitted for approval by GE before procurement/ fabrication from OEM factory/ workshop.
9M&L for manual operated cable reeling drum made out of MS sheet, fixed on trolly, suitable for reeling minimum 50 RM LT side 240 Sqmm 3.5 Core cable, complete all as specified and directed.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail