Tata Memorial Centre has published Tender For Supply, Installation, Testing And Commissioning Of Fire Alarm System(Addressable)And Pa System At Dr.B.Borooah Cancer Institute. At Dr. B. Borooah Cancer Institute. Submission Date for this Tender is 29-05-2024. Alarm Systems Tenders in Kamrup Metro Assam. Bidders can get complete Tender details and download the document.
FileName | File Description | File Size |
ed2a5961-e7ed-4ba1-8b9d-857d53fbf665.html | Tender Notice | 0 KB |
ApproveMake.pdf | Tender Document | 0 KB |
BOQ_846897.xls | Tender Document | 0 KB |
detailtender.pdf | Tender Document | 0 KB |
Drawings.pdf | Tender Document | 0 KB |
techdocumentchecklist.xls | Tender Document | 0 KB |
Tendernotice_1.pdf | Tender Document | 0 KB |
Sl. No. | Item Description |
1 | NEW HOSPITAL BUILDING |
2 | Fire Alarm System |
3 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loopmodules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. |
4 | Ten Loop Panel. |
5 | Supplying, installation, testing & commissioning of central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required. |
6 | Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required. (Location-Reception and main gate) |
7 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
8 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. |
9 | Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required. |
10 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
11 | Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required. |
12 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. |
13 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
14 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. |
15 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.Preferrably Red colour cable |
16 | PUBLIC ADRESS SYSTEM |
17 | Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zonebutton paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required. |
18 | Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required. |
19 | Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V rms operating at 240 Volt AC Supply complete as required. |
20 | Supplying, installation, testing & commissioning of exit point directional sound speaker with voice and integral audio amplifier with selectable sound pulse patterns complete as required. |
21 | Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required. |
22 | Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size includingconnections and interconnections etc. as required. |
23 | speaker cable Single pair, 2-core, 1.5 sqmm.Preferrably blue colour |
24 | OLD HOSPITAL BUILDING |
25 | Supplying, installation, testing & commissioning of central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required. |
26 | Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required. (Location-Reception and main gate) |
27 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
28 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. |
29 | Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required. |
30 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
31 | Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required. |
32 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. |
33 | Supplying, installation, testing & commissioning of intelligent addressable duct detector including suitable Photo detector complete with base as required. |
34 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
35 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. |
36 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. |
37 | Public ADRESS SYSTEM |
38 | Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required. |
39 | Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V rms operating at 240 Volt AC Supply complete as required. |
40 | Supplying, installation, testing & commissioning of exit point directional sound speaker with voice and integral audio amplifier with selectable sound pulse patterns complete as required. |
41 | Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required. |
42 | Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size includingconnections and interconnections etc. as required. |
43 | speaker cable Single pair, 2-core, 1.5 sqmm |
44 | Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required. |
45 | RT Annexure Building |
46 | Supplying, installation, testing & commissioning of central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required. |
47 | Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required. (Location-Reception and main gate) |
48 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
49 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. |
50 | Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required. |
51 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
52 | Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required. |
53 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. |
54 | Supplying, installation, testing & commissioning of intelligent addressable duct detector including suitable Photo detector complete with base as required. |
55 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
56 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. |
57 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. |
58 | PUBLIC ADRESS SYSTEM |
59 | Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required. |
60 | Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V rms operating at 240 Volt AC Supply complete as required. |
61 | Supplying, installation, testing & commissioning of exit point directional sound speaker with voice and integral audio amplifier with selectable sound pulse patterns complete as required. |
62 | Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required. |
63 | Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size includingconnections and interconnections etc. as required. |
64 | speaker cable Single pair, 2-core, 1.5 sqmm |
65 | Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required. |
66 | OLD HOSPITAL BUILDING(Existing) |
67 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loopmodules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. |
68 | Ten Loop Panel. |
69 | Supplying, installation, testing & commissioning of central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required. |
70 | Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required. (Location-Reception and main gate) |
71 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
72 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. |
73 | Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required. |
74 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
75 | Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required. |
76 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. |
77 | Supplying, installation, testing & commissioning of addressable phone control module complete as required. |
78 | Supplying, installation, testing & commissioning of intelligent addressable duct detector including suitable Photo detector complete with base as required. |
79 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
80 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. |
81 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. |
82 | PUBLIC ADRESS SYSTEM |
83 | Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zonebutton paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required. |
84 | Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required. |
85 | Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V rms operating at 240 Volt AC Supply complete as required. |
86 | Supplying, installation, testing & commissioning of exit point directional sound speaker with voice and integral audio amplifier with selectable sound pulse patterns complete as required. |
87 | Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required. |
88 | Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size includingconnections and interconnections etc. as required. |
89 | speaker cable Single pair, 2-core, 1.5 sqmm |
90 | Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required. |
91 | Comprehensive Annual Maintenance Contract(CAMC) for above Fire Alarm System(Addressable)and PA System after Defect liability period of 01 year. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail