Tender For Provision Of New Transformer And Connecting Network At Udhampur For Ct Scanner Under Ge (P) Ch Udhampur, udhampur-Jammu And Kashmir

Military Engineer Services-MES has published Tender For Provision Of New Transformer And Connecting Network At Udhampur For Ct Scanner Under Ge (P) Ch Udhampur. Submission Date for this Tender is 11-05-2024. Transformer Supply Tenders in udhampur Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

43210459
Corrigendum : Tender For Provision Of New Transformer And Connecting Network At Udhampur For Ct Scanner Under Ge (P) Ch Udhampur
Open Tender
Indian
Jammu And Kashmir
udhampur
11-05-2024

Tender Documents

Additional Details Available on Click
✓ Tendering Authority
✓ Publication Document
(Tender Document / Tender Notice )

Tender Details

Tender For Provision Of New Transformer And Connecting Network At Udhampur For Ct Scanner Under Ge (P) Ch Udhampur

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 25-Apr-2024 Revised BOQ Amedment BOQ 11-05-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 76400.0 /-
Tender Value
INR 38.19 Lakhs /-

Attachment

FileName File Description File Size
554064b9-e9f8-4279-b724-c149cf0e3bf3.html Tender Notice 0 KB
BOQ_728264.xls Tender Document 0 KB
Tender8282.pdf Tender Document 0 KB
Tendernotice_1.pdf Tender Document 0 KB

BOQ Items

Name of Work : PROVN OF NEW TRANSFORMER AND CONNECTING NETWORK AT UDHAMPUR FOR CT SCANNER UNDER GE (P) CH UDHAMPUR
Sl. No. Item Description
1Excavation in trenches n.exc 1.5m wide and not exc 1.5m in depth and getting out in any type of soil complete all as specified.
2Exacavation in trenches in any type of soil n.exc 1.5m wide and depth exceeding 1.5m but n.exc 3.00m in depth and getting out complete all as specified.
3Returning, filing in, including spreading, leveling, watering and well ramming in layers 25 cm in thickness in any type of soil.
4Removing of excavated material (SOIL) to a distance not exc 50m and depositing where directed at a level n.exc 1.5 m above starting point complete.
5Supply, laying & testing cable XLPE insulated , screened, PVC bedded, galvanised steel strip or wire armoured electric power cables ( heavy duty) with stranded aluminium conductor 11000 volts earthed grade of size 3 core 120 sqmm including HT Cable route indicator at 30 mtrs distance all as specified and directed.
6Supply and lay cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric , power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 630 sqmm 3.5 core.
7Supply and lay cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric, power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 240 sqmm 3.5 core.
8Material and labour for sand cushioning to under ground cable, provided with 8 cms thick layer before laying the cable and 15 cms thick after laying and stretching the cable complete all as specified.
9Supply and laying factory made reinforced precast concrete cable cover, class HV Type-I, Flat size 300mm x 180mm x 40mm all as specified and directed.
10Supply and laying factory made reinforced precast concrete cable cover, class LV Type-I, Flat size 250mm x 150mm x 40mm all as specified and directed.
11Material and labour for PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) in foundation, filling and mass concrete.
12Plain cement concrete 1:2:4 type-B-1(using 20mm graded crushed stone aggregate) for coping of HT poles all as specified.
13Supply, installation, testing and commissioning of step down transformer 11 KV/ 433 Volts (at no load) 3 Phase 50 Hz, 400 KVA, copper wound, outdoor type, with off load tap changing arrangement of HT side to vary secondary voltage upto ± 7.5 % in step of ± 2.5% including suitable cable entry boxes both on HT and LT to receive 95 sqmm 3 core XLPE cable on HT side complete in all respect with std. accessories and fitment confirming to IS-1180 Part-I of 2014/IS 2026 and IS-1180 latest ammendments Dyn -11 connection complete all as specified and directed. The salient features of Transformer shall be as follows :- (a)Transformer shall be oil immerse, naturally self cooled double wound copper, winding core type, MS radiater cooled tank complete with first fill of transformer oil plus 5% spare oil as per IS 335 of 1980 with test certificates with own cooling system. (b)Rating and diagram plates. (c)Earthing terminals = 02 Nos. (d) Lifting lugs. (e) Thermometer pocket. (f) Air release hole with plug (g) Winding/Oil temperature indicator (h) Conservation with oil level indicator (j) Castors with locking provision (k) Silica Gel breather complete Note : Transformer must be as per Energy efficiency Level-2 of IS: 1180:2014 with amendment No. 4. Transformer must be BIS Marked and BEE labelled and manufacturer should have NABL aproved testing lab.
14Supply and fix HT 11 KV, out door type gang operated air break switch suitable for horizontal or vertical mounting fixed type complete with 12 insulators of rating upto 200 Amps.
15Steel tubular swaged poles complete with MS base plate 6mm thick of size 300mm x 300mm, finial taper plug, bolts, nuts, washers and screws (11 metres long) type 410 SP-55 (11.0 Mtr long) including drilling of holes or required size and nuts for fixing of cross arms, painting with a coat of red oxide zinc chrome primer and two coats of aluminium paint on exposed surfaces and two coats of back bituminous paint for portion embedded in concrete, painting five black/white bands at lower portion of pole each of 300 mm height at 300mm spacing, complete all as specified.
16Cable jointing kit for 11 KV gradeEarthed XLPE cable for outdoor termination heatshrinkable joints complete with jointing material of cable size 120 Sqmm 3 Core.
17Cable jointing kit for 11 KV gradeEarthed XLPE cable for indoor termination heatshrinkable joints complete with jointing material of cable size 120 Sqmm 3 Core.
18Supply and fix lightning arrestor HT 11 KV 10 KA station class.
19Material and labour for Anti climbing devices; comprising 2.24mm dia galvanised steel 2-strand barbed wire with 2.00mm dia barbs wrapped spirally round poles, to a length of 0.5 to 1.0 metre clamped andproperly secured or as ordered.
20Material and labour for Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed withM.S. clamps, bolts and nuts of approved size, for LT, 20 x 15cm complete all as specified.
21Material and labour for Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed withM.S. clamps, bolts and nuts of approved size, for HT, 25 x 20cm complete all as specified.
22Material and labour for Cross arms, bracings supports, clamps, and back plates fabricated out ofstructural steel sections including, nuts, bolts, washers,welding ,bending cold or hot, drilling holes for bolts ,in any shape or size as indicated or direected and inclusive of one primer coat of red oxide zinc chrome,one undercoat and one finishing coat of aluminium paint complete all as specified and directed by Engr-in-Charge.
23Supply and laying MS Tubes of 100 mm bore, "light grade" galvanised, with all fitting and fixed complete to walls and ceilings or laid in trenches for cable protection complete all as specified and directed by Engr-In-Charge.
24Earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6mm thick buried directed in ground (earth plate not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5m below normal ground level) connected to and including galvanised iron earth lead wire 4mm dia by means of bolts, nuts, check nuts and washers of galvanised iron including PCC 1:2:4 in pit, angle iron 25x25x3mm frame work with precast RCC 1:2:4 cover reinforced with 8mm dia TMT bars @ 150mm C/C both ways and 12 mm dia MS fabricated handle, mediumgrade GI watering pipe 20mm bore with funnel, wire mesh and light grade GI protection pipe 15mm bore upto 5m length for drawing in earth lead wire, salt, charcoal, etc. Including excavation and earth work in any type of soil, removal of surplus soil to a distance not exc. 50m complete all as shown in electrical plate No 3 of MES schedule 2009 (Pt-I) and connected to main control board all as specified or indicated including testing on completion.
25Earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6mm thick buried directed in ground (earth plate not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5m below normal ground level) connected to and including galvanised iron strip 32 x 6mm by means of bolts, nuts, check nuts and washers of galvanised iron including PCC 1:2:4 in pit, angle iron 25x25x3mm frame work with precast RCC 1:2:4 cover reinforced with 8mm dia TMT bars @ 150mm C/C both ways and 12 mm dia MS fabricated handle, mediumgrade GI watering pipe 20mm bore with funnel, wire mesh and light grade GI protection pipe 40mm bore upto 5m length for drawing in earth lead wire, salt, charcoal, etc. Including excavation and earth work in any type of soil, removal of surplus soil to a distance not exc. 50m complete all as shown in electrical plate No 3 of MES schedule 2009 (Pt-I) and connected to main control board all as specified or indicated including testing on completion.
26Supply, installation, testing and commisining of LT electric panel board floor mounted type totally enclosed (Factory Fabricated), outdoor type double door type front and rear opening type,powder coated inside & outside made out of CRCA sheet not less than 3.15 mm thickhaving locking arrangement spray painting internally/externally, IP-65 including internal wiring with suitable size of Copper conductor strip, bus bar chamber 3 phase andfour wire type system 415 volts, 50 Hz consisting of copper bus bar of capacity 800 Ampsand consisting of the following:- Main LT Cum DG Synchronising Panel (a) MCCB 4 pole 630 Amp 50 KA - 01 No. (b) Extended Rotary Handle- 01 No (c) Spreader Link - 01 No (d) 600 Amps 4 Pole Contactor - 01 No (e) Digital Volt Meter- 01 No. (f) Digital Amp Meter- 01 No (g) CT-600/5A CL 1.0 15 VA- 04 No (h) LED Indicator lamp with holder 3 Nos - 01 Set. (j) On/Off/Trip Indication Lamp- 03 Nos (k) 6 A SP MCB, 10 KA-03 Nos (l) Termainal Block- 04 Nos BUS Coupler (a) MCCB 4 pole 320 Amp 36 KA - 01 No. (b) Extended Rotary Handle- 01 No (c) Spreader Link - 01 No (d) 300 Amps 4 Pole Contactor - 01 No (e) On/Off/Trip Indication Lamp- 03 Nos (f) 6 A SP MCB, 10 KA-03 Nos (g) Termainal Block- 04 Nos PLC Based Synchronising & Auto Load Sharing (a) PLC based Synchronising & Auto Load Sharing - 02 Nos (b) 8 Channel Relay Card 230 V AC- 06 Nos (c ) 8 Channel Relay Card 24 V DC- 06 Nos (d) VMR- 01 Nos (e) Auxilary relays- 05 Nos (f) Aux Contactors 2 No 2 NC-05 Nos (g) Add on block No 2 NC- 05 Nos (h) Push button- 06 Nos (j) 6 A SP MCB, 10 KA- 04 Nos (k) 16 A DP MCB- 02 Nos (l) Battery Charger 12/24 V DC- 02 Nos (m) Terminal block- 50 Nos Out Going (a) 250 Amp 4 Pole MCCB, 36 KA- 02 Nos (b) Extended Rotary Handle- 02 Nos (c) Spreader Link- 02 Nos GENERAL ITEMS (a) Steel fabricated body made out of 3.15 mm thick CRCA Sheet steel duly Powder coated -01 No (b) Copper bus bar 800 Amps with suport duly heat shrinkable PVC Sleeved- 1 Set (c) Hardware & Accessories- 01 Set (d) PVC Wiring- 01 Set (e) Programming- 01 Nos (f) Including cable gland for all the incoming and outgoing cables as per cable sizes
27Cable route marker with route indication at every 30 Mtr length on cast iron disc of 100mm dia and 5mm thick, marked/written for "HT cable 11000 VOLTS" embosed including indication direction fixed/bolted to 40mm x 40mm x 6mmthick MS angle iron support of 0.50 m long embedded upto 200mmdepth in concrete block of size 200mm x 200mm x 500mmcasted in PCC 1:3:6 type C-1 including painting with two coats of synthetic enamel paint over a coat of red oxide primer to exposed steel surface, complete all as specified and as directed.
28Material and labour for construction of plateform suitable for 400 KVA transformer of size 4m x4m with 1.20 mtrs (clear heights with additional 150mm thick PCC 1:3:6 Type C-2 using 40 mm graded crushed stone aggregates as in foundation below ground level). 23 cm wide brick masonry in CM 1:6 belwo & above ground level, hollow space to be filled hard core of size not exceeding 63 mm, deposited spread and levelled in layers not exceeding 15cm thickness, watered and well rammed with 100mmthick cement concreate 1:2:4 type B-2 as in Fllor/Top of platform, brick surfaces plastered in CM 1:4 including protection with XPM, gate and chain link fencing rail around the platform with angel iron of 40 x 40 x 6mm frame upto 120m clear height supports grouted in PCC 1:2 type B-1 using 20mmgraded crushed stoene aggregate as in foundation of angel iron including excavation in any type of soil to a distance 50m, complete all as specified and directed.
29Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150mm dia suitable for 0.4 mpa working pressure.