Paschimanchal Vidyut Vitran Nigam Limited has published Tender For Business Plan Work In The Area Of Edsd Talhedi Under Edd Deoband, Tender For Due To Overloading Of 100 Kv Transformer Installed At Village Pahadpur Of 33/11 Kv Sub-Centre Amki, Work Of Increasing The Capacity And Installing 250 Kva Transf. Submission Date for this Tender is 08-05-2024. Transformer Supply Tenders in Saharanpur Uttar Pradesh. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 20-Apr-2024 | date extended | Date | 29-04-2024 |
2 | 29-Apr-2024 | date extend to 08/05/2024 | Date | 08-05-2024 |
FileName | File Description | File Size |
d64fb6a6-4756-40e6-a06c-1ef6c7707ed4.html | Tender Notice | 0 KB |
345.pdf | Tender Document | 0 KB |
BOQ_1592054.xls | Tender Document | 0 KB |
Tendernotice_1.pdf | Tender Document | 0 KB |
Sl. No. | Item Description |
1 | Detail of Work |
2 | Safely Carriage of 11 KV XLPE Cable size 3x300 sq.mm from ESC, SRE to Site of work including loading & unloading at both ends. |
3 | Damage cable pulled out by digging the job ground |
4 | Safely carriage of Damage XLPE cable from site to ESC SRE including loading and unloading at both ends |
5 | Providing of HDPE Pipe 160 mm |
6 | Making and fixing of 11 KV Cable Heat shrinkable terminationskits of size 3x300 sq.mm ofoutdoor/indoorside. |
7 | Driling of earth under road crossing 1.5 mtr deep and laying of 2 No parreral HDPE pipe 160 mm dia on 1 meter distance by drill machine. |
8 | Laying of11 KV XLPE cable 3X300sq mm in the 2 No parreral HDPE pipe 160 mm dia on 1 meter distance. And fixing of G.I. Pipe 150 mm dia and hanging of Cable on D/P after fixing of outdoor terminations kits work as per site condition with jumpering complete. |
9 | Removal of 100 KVA T/F from the existing D/P after opening HT & LT connection and with shifting the T/F from the site to ESC, SRE/JE store with loading & unloading at both ends. |
10 | Safe cartage of 250 KVA T/F from ESC,SRE, to the site of work including loading & unloading at both ends. (Dist. Upto 30 km.) |
11 | Constriction of plinth for installation of 250 kv T/F of size 1.5x1.5x1.5 mtr made of 9”inch thick wall in all four sides with 6”inch thick RCC top duly filled with sand and plastered 12mm thick in ratio 1:4 with cement and sand on outer surface of brick wall. |
12 | Safe installation of 250 KVA T/F on the Plinth with complete fittings including making connections and commissioning. |
13 | Wire mesh fencing of 250 KVA T/F size 2.5x2.5x2.5 mt. grouting making frame of MS angle 45x45x6 mm and fixing four no. MS strip size 25x6 mm at equal distance in between the frame and fixing squre mesh 50 mm square in each frame the fencing should cover all side of T/F with providing 1 No. door size 6"x3" with sitakni & Dandala. |
14 | Pipe/Water Level Earthing of 250 KVA T/F (1 No body & 1 No. neutral earthing) by boring of 60 Ft deep & fixing of 60 ft. G.I pipe 11/2" Dia (Jindal Class B) and connecting with G.I. Strip of size 40x5 mm and G.I wire at bottom of G.I pipe to the T/F providing of required charcoal & salt in the pipe |
15 | Providing of Aluminum bolted type lug 250 sq.mm |
16 | Laying of LT/XLPE cable 1*240 sq.mm/3.5*70 sq.mm as per respo specification. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy