}

Special Repair / Replacement Of U / S Solar Street Lights, Timer Box And Certain Misc Work At Various E / M Substation And Sr / Replacement Busbar Boxes And Certain Misc Work At E / M Installation At Makarpura At Af Stn Vadodara, baroda-Gujarat

Military Engineer Services-MES has published Special Repair / Replacement Of U / S Solar Street Lights, Timer Box And Certain Misc Work At Various E / M Substation And Sr / Replacement Busbar Boxes And Certain Misc Work At E / M Installation At Makarpura At Af Stn Vadodara. Submission Date for this Tender is 27-04-2024. Busbar Tenders in baroda Gujarat. Bidders can get complete Tender details and download the document.




Tender Notice

43078665
Corrigendum : Special Repair / Replacement Of U / S Solar Street Lights, Timer Box And Certain Misc Work At Various E / M Substation And Sr / Replacement Busbar Boxes And Certain Misc Work At E / M Installation At Makarpura At Af Stn Vadodara
Open Tender
Indian
Gujarat
baroda
27-04-2024

Tender Details

Special Repair / Replacement Of U / S Solar Street Lights, Timer Box And Certain Misc Work At Various E / M Substation And Sr / Replacement Busbar Boxes And Certain Misc Work At E / M Installation At Makarpura At Af Stn Vadodara

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 20-Apr-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 27-04-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 87500.0 /-
Tender Value
INR 43.67 Lakhs /-

BOQ Items

Name of Work : SR / REPLACEMENT BUSBAR BOXES AND CERTAIN MISC WORK AT E/M INSTALLATION AT MAKARPURA AND HARNI CAMP AND SR / REPLACEMENT OF U/S SOLAR STREET LIGHTS, TIMER BOX AND CERTAIN MISC WORK AT VARIOUS E/M INSTALLATION AT AF STN VADODARA
Sl. No. Item Description
1Supply, installation, tesing and commissioning of factory made (including CPRI approved manufacturer) LT panel box (KIOSK) out door type size not less then 1500 W x 1500Hx 500 D platform mounted suitable for 415 volt , 3 phases, 4 wire , 50 Hz ACsupply system all as specified and directed having busbar chamber with 4 Nos insulated AL bus bars 600 amps rating installed on percelain insulators, the panel shall be dust and vermin proof double door made of 3.15 mm CRCA MS sheet outer & inner and individual compartment for MCCB/ volt/Ampsmeter and 50 x 50 x 6 mm thick angle iron for base frame work having angle iron4 Nos each Suitablelong welded to frame/cubical and grouted in ground upto 0.5 Meter by using PCC1:2:4 B2of Suitable sizethe ground over the ground level upto 1 Mtr height . 2 Nos earth terminal to be welded with feeder piller.The complete feeder pillar box should be anti corrosive coating and finally epoxy polyester powder coating of flint grey shade (RAL-7032) including internal wiring with PVC insulated solid copper conductor FRLS cables appropriate size but not less than 2.5 Sqmm.
2Frontand back opening type for cable entry with double door shutter including locking arrangement as per manufacturers with 2 Keys reconnecting all existing UG cable with suitable lugs for incoming/outgoing feeders and comprising of all complete all as specified and directed:- Incomer:- (a) MCCB FP250 A 36 kA with Electronic microprocessor release with over load Zone of adjustment 0.4 to 1.0 In and Electronic release withShort circuit Zone ofadjustment 1.5 to 10.0 Ir. (Adjusted current) with time with Extended Rotary Handle vari-depth type and Spreader between phases and neutral. -02 no (b) 4 Nos Aluminium Bus bars of 500 Amp current rating capacity, of suitable size of length as actually required at site for 3 phase andneutral, mounted on epoxy/FRP bus bar insulator complete with nut bolt fixing arrangement complete- 01 set
3Outgoing:- (c) MCCB FP 100 A 16 kA with Adjustable Thermal release for over load 0.7 to 1.0 and Adjustable magnetic release (10.0 In) forShort circuitwith Extended Rotary Handle vari-depth type and Spreader between phases and neutral. -06 Nos Metering Compartment (f) Digital type Amp meter 0-250 Amp(size 96mmx96mm) with Selector switch and3 Nos CT of ratio 250 A/5A-1No (g) Digital Type volt meter 0-500 V with selector switch -1Nos (h) Digital Multifunction meter having for measuring KW, KVA KVRa, KWAH, KVAH , Pf, Hz etc-1Nos (i) RYB LED incating lamp -3 Nos Note :- (i) Cost of taking out old unserviceable panel is deemed to be included with unit rate of item. (ii) Earth work, PCC baseetc is deemed to be included with unit rate of item. (iii) All MCCB to be installed vertically therefor panel shall be designed accordingly.
4Supply, installation, testing and commissioning of factory made (including CPRI approved manufacturer) LT panel box (KIOSK) out door type size not less then 2000 W x 1500Hx 500 Dplatform mounted suitable for 415 volt , 3 phases, 4 wire , 50 Hz ACsupply system all as specified and directed having busbar chamber with 4 Nos insulated AL bus bars 600 amps rating installed on percelain insulators, the panel shall be dust and vermin proof double door made of 3.15 mm CRCA MS sheet outer & inner and individual compartment for MCCB/ volt/Ampsmeter and 50 x 50 x 6 mm thick angle iron for base frame work having angle iron4 Nos each Suitablelong welded to frame/cubical and grouted in ground upto 0.5 Meter by using PCC1:2:4 B2of Suitable sizethe ground over the ground level upto 1 Mtr height . 2 Nos earth terminal to be welded with feeder piller.The complete feeder pillar box should be anti corrosive coating and finally epoxy polyester powder coating of flint grey shade (RAL-7032) including internal wiring with PVC insulated solid copper conductor FRLS cables appropriate size but not less than 2.5 Sqmm.
5Frontand back opening type for cable entry with double door shutter including locking arrangement as per manufacturers with 2 Keys reconnecting all existing UG cable with suitable lugs for incoming/outgoing feeders and comprising of all complete all as specified and directed :- Incomer:- (a) MCCB FP400A 36 kA with Electronic/Microprocessor release with over load Zone of adjustment 0.4 to 1.0 In and Electronic release withShort circuit Zone ofadjustment 1.5 to 10.0 Ir. (Adjusted current) with time with Extended Rotary Handle vari-depth type and Spreader between phases and neutral. -01 no (b) On Load changeover switch 400 Amp 4 pole -1 (c) 4 Nos Aluminium Bus bars of Aluminium strips (50X12mm) having 600 Amp current rating capacity, of suitable size of length as actually required at site for 3 phase andneutral, mounted on epoxy/FRP bus bar insulator complete with nut bolt fixing arrangement complete- 01 set
6Outgoing:- (d) MCCB FP 200A 36 kA with Adjustable Thermal release for over load 0.64 to 1.0 and Adjustable magnetic release (3.5 to 10.0 In) forShort circuitwith Extended Rotary Handle vari-depth type and Spreader between phases and neutral. -04 Nos (e) MCCB FP 160 A 36 kA with Adjustable Thermal release for over load 0.64 to 1.0 and Adjustable magnetic release (3.5 to 10.0 In) forShort circuitwith Extended Rotary Handle vari-depth type and Spreader between phases and neutral. -02 Nos (f) MCB 4 pole 63 Amp -6 Nos Metering Compartment (g) Digital type Amp meter 0-400 Amp (size 96mmx96mm) with Selector switch and3 Nos CT of ratio 400A/5A-1No (h) Digital Type volt meter 0-500 V with selector switch -1Nos (j) Digital Multifunction meter having for measuring KW, KVA KVRa, KWAH, KVAH , Pf, Hz etc-1Nos (k) RYB LED incating lamp -3 Nos Note :- (i) Cost of taking out old unserviceable panel is deemed to be included with unit rate of item. (ii) Earth work, PCC baseetc is deemed to be included with unit rate of item. (iii) All MCCB to be installed vertically therefor panel shall be designed accordingly.
7M&L for providing earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6.0mm thick buried dirictlyin ground (Earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level,connected toand including galvanised earth strip 32 X 6mm mm size upto 7.5 meter long by means of bolts,nuts check nuts and washers of all galvanised iron or steel all as shown in electrical plate No.3 of SSR Part-1 and connected to test point including necessary excavation/ earth work in any type of soil/rock strata,funnel with wire mesh and watering pipe(GI,light grade) 20mm dia,PCC pit with 50mm thick PCC cover etc. including testing on completing but excluding GI protection pipe for earthing lead complete all as specified and directed
8Surface excavation not exceeding 30 cm deep and averaging 15cm deep and getting out complete all as specified and directed
9M & L forstones aggregateof gauge 40 mm graded including spreading at various location of sub station complete all as specified and directed
10Repair ofold rusted/worn outwire mesh chain link fencingof any type and description including necessary welding, clamping nut boltetc complete all as specified and directed.
11Fixing only chain link fencing (Approx area 66 Sqm) including line wires any mesh size and type of soil rails straining bolts etc.including provision of binding wire complete all as specified and directed
12Supply only chain link fencing made out of MS galvanized Minimum 4mm dia GIopening size 2.5" (approx) complete all as specified and directed
13S&F mild steelTMT bars 6 mm to 8 mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia or securing with clips complete all as specified and directed
14Excavating Post holes in any type soil (or similar holes)each n exc 0.5 cum,getting out, returning filling,and ramming earth or broken rubble mixed with earth around,in layers not exceeding 25cm,watering,and removing surplus soil to a distance n exc 50m and making good surface complete all as specified and directed
15S & F mild steel work such as in angle iron flat iron fillets hand rails half round or other steel section or core for wooden hand rail straight portion drilled and countersunk for baluster running bars for doors balusters running bars for doors baluster noising to steps including embeding in concreat an screwing etc,wind ties for roof including securing bolts post and struts in fencing including cutting tops to shape as directed drilling holes notching for wire including all necessary works and applying two coat of synthetic enamel paint over and including of one coat of red oxide primer complete all as specified and directed
16S & F screw bolt (machine made) with hexagonal or square heads at one end and screwed the other or screwed both ends each scerwed end to be fitted with washers and one hexagonal or square nut n exc 10cm ans n esc 15cm long complete all as specified and directed
17M&L for Plain cement concrete type D-2 1:4:8 (using 40mm graded crushed stone aggregate) as in 75mm thick flooring finished surfaces even and rough to receive the flooring etc without using extra cement complete all as specified and directed
18M&L for PCC 1:3:6 type C2 as in foundation, filling and mass concrete complete all as specified and directed
19M&L for Plain cement concrete type B-2 1:2:4 (using 40mm graded crushed stone aggregate) as in 75mm thick flooring finished surfaces even and fair without using extra cement complete all as specified and directed
20Providing and laying 60mm thick factory made chamfered edge cement concrete paver block of M-35 grade with approved colour, design & pattern as in footpath, parks, lawns, drive ways or light traffic parking etc., of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over and including 50mm thick compacted bed of fine sand, compacting and proper embedding/ laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand complete all as specified and directed
21Supply and fixing Rough dressed sand stone slabs 40 mm thick on drain complete all as specified and directed
22Sand filling under floors or in foundations including watering and consolidation complete all as specified and directed
23M & L for preparing old steel surfaces of any description and applying one coat of synthetic enamelled paint complete all as specified and directed
24Disconnecting/dismantling and removing unserviceable time switch board of any descriptionand S&F of automatic street light switch using Infrared Sensor based NATURE SWITCHfor automatic switching of street lights. Nature switch operation switch operation should be basedon Natural light Lux level. Required illuminancelevel for Switching ON is<= 30 lux andfor switching OFF>=10 lux. The sensor should also have part night operation facility of min 4 hours to max 12 hours. The sensor along with suitable Power contactors, incoming-outgoing MCB"s and Auto manual (Sensor By-pass) selection option should be enclosed in a pole/wall mountable Enclosure made of Rust Proof, Electric Shock Proof, termite proof and FR grade IP66 protection class 2 Enclosure made of thermoplastic polycarbonate and protected against weather influences. For three phase load of 5KW (Swadeep02 EC dual series-5kW3P) with: 3 Nos contactors, 3 nos incoming MCB"s & 3 nos outgoing MCB"s of 20-25 Amps each and 1 No time switch & circuit wiring (copper)of min 10 sqmm complete all as specified and directed Make:Nature switch:Kakatiya Energy system/Bajaj/Healer, Contactors:BCH/L&t/SSchneider, MCB"s: HAGER/Schneider/L&T(Exora/AU series)/C&S, Time switch : L&T, Schiender ABB
25Supply and fixing of solar street light driver /controller of capacity Power = 30W-50wttInput voltage: 12 voltAutomatic ON OFF complete all as specified and directed
26Supply and fixing of100AH Tubular lead acid battery, maintenance free suiatbel for solar street lightcomplete all as specified and directed
27Supply and fixing LED street light 40W, 12 V suiablle for solar street light complete all as specified and directed
28Supply and fixing LED 10W bollard garden light pressure die cast Powder coated PDC Aluminium body with Opal diffuser./ PC diffuser efficent high output with IP 65 protection complete all as specified and directed Make Crompton LBLA1-10 CDL /Polycab LED BOLLARD – 6/ Orient LLCBL -10-W-B
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail