Tender For Rectification Of Automatic Fire Detection And Fire Alarm System Including Replacement Of Fire Alarm Control Panel At Main Telephone Exchange , Jeypore Under Koraput Ba., koraput-Odisha

Bharat Sanchar Nigam Limited-BSNL has published Tender For Rectification Of Automatic Fire Detection And Fire Alarm System Including Replacement Of Fire Alarm Control Panel At Main Telephone Exchange , Jeypore Under Koraput Ba.. Submission Date for this Tender is 09-04-2024. Alarm Systems Tenders in koraput Odisha. Bidders can get complete Tender details and download the document.




Tender Notice

43077677
Tender For Rectification Of Automatic Fire Detection And Fire Alarm System Including Replacement Of Fire Alarm Control Panel At Main Telephone Exchange , Jeypore Under Koraput Ba.
Open Tender
Indian
Odisha
koraput
09-04-2024

Tender Details

Rectification Of Automatic Fire Detection And Fire Alarm System Including Replacement Of Fire Alarm Control Panel At Main Telephone Exchange , Jeypore Under Koraput Ba. Rectification Of Automatic Fire Detection And Fire Alarm System Including Replacement Of Fire Alarm Control Panel At Main Telephone Exchange , Jeypore.

Key Value

Document Fees
INR 590 /-
EMD
INR 3395.0 /-
Tender Value
INR 1.69 Lakhs /-

BOQ Items

Name of Work: Rectification of Automatic Fire Detection and Fire Alarm System including Replacement of Fire Alarm Control Panel at Main Telephone Exchange , Jeypore under Koraput BA.
Sl. No. Item Description
1Testing, checking &fault finding of Automatic Fire Detection, Fire Alarmsystem comprising ofFire control panels , Fire Detectors , Manualcall points, Electronic Hooters etc.assessing the faults and material required for repairing and rectification of faults i/c rectification of minor faults, testing for proper functioning etc. complete as required.
2Ground Floor with Main Fire Alarm Control panel (FACP) & 1st/ 2nd Floor with Local FACP
3Supply, installation testing and commissioning of following ZonesUL listed Microprocessor based Fire Alarm Control Panel Made of16/18 SWG CRCA sheet powder coated, finish suitable for operation with 220V 50HZ AC mains power supply with standby battery backup 24Volt DC power supply and built in charger (without batteries) , normal operating voltage 24 v DC, compatible with all types of conventional detectors, manual call points and normally opened dry contact devices, 16X2 Dot matrix display, fully compatible with UL-864 and NFPA-72 etc. complete as required as per details specifications. (make- Agni Instruments / Agni Devices/GST / Honeywell / system sensor / Ravel)
48 Zone Main Control panel without PA system
510 Zone Main/Local Control panel without PA system
6SITC of 2nos 12V(2x12V)sealed maintenance free battery of not less than 7AH capacity with all accessoriesetc as reqd.(Exide /Amco/Superior)
7Supply, installation, testing and commissioning of UL listed, CE certified 2 wire conventional Photo electric/ Ionization typeSmoke detector withbase (Blinking LED type) made of ABS plastic with all accessories, suitable for operation on 24v DC, internal protection class: IP23,dual pulsing LED with 3600 visibility, relative humidity:=95%;non-condensing and EN54 compliance of approved make etc. as required. (Make- Apollo / GST/ Honeywell / System sensor)
8Supply, installation, testing and commissioning of UL listed, CE certified 2 wire conventional Multidetector(fixed cum rate of rise heat Detector using a thermistor, raises an alarm when the detector reaches 590C (Fixed) or when the change in temperature exceeds the rate of rise of 110C/min) withbase (Blinking LED type)made of ABS plasticand all accessories, suitable for operation on 24 v DC, internal protection class: IP23, dual pulsing LED with 3600 visibility, relative humidity:=95%;non-condensing and EN54 compliance of approved make etc. as required.(Make- Apollo / GST / Honeywell / System sensor)
9Supply, installation, testing and commissioning of electronic hooter cum speaker made of 16/18SWG CRCA sheet duly powder coated with PO red colour, output not less than 80db @25mtr, LMT with adjustable sound output of 2.5 watt,5 watt, suitable knock out for cable entry from top suitable for operation on 100/70 volt RMS AC supply etc. as required. (Make- Apollo / Honeywell / GST/ system sensor/ Ravel /Agni)
10SITC of manual push button station(pill box) Manual Call Point in MS Housingfor Conventional Fire Alarm System with glass for breaking up in case of fire and hammer with chain etc. (Make- Apollo / Honeywell / GST/ system sensor/ Ravel /Agni)
11SITC of twin LED type response Indicatrors with suitable 16 guage M.S./Alumunium bos, Acrylic sheet cover of min 2mm thick LED etc. as required.. (Make- Apollo / Honeywell / GST/ system sensor/ Ravel /Agni)
12Supply and laying of 2 core 1.5sqmm FRLS PVC insulated and PVC sheathed copper conductor armoured cable on surface/recess for looping the fire alarm devices & providing power supply to sounder cum strobes etc. as required. (ISI)
13Supplying and making indoor end termination with brass compression gland and aluminium lugs for following size of PVC insulated and sheathed/XLPE aluminium conductor cable of 1.1 KV grade as required. a)2 core, 6 Sq. mm (19mm)
14S/F ABS roundbox / MS Boxon ceiling for fixing the detectors etc as reqd.
15Supplying & Fixing ofwall mounted Autoglow Signage Fire Exit Sign Board 3mm PVC Sheet with high Glow intensity in total Darkness. (Red and Green colour with exit symbols as per requirements)
16Checkingof all old existing detector , RI, Hooter, Sign board after dismantling from the exiosting position i/c cleaning of the old working detector, hootet, RI & Sign board and re-fixing of the working one i/c rectification of minor faults, testing for proper functioning etc. complete as required.
17Testing, checking of Automatic Fire Detection, Fire Alarmsystem comprising ofFire control panels , Fire Detectors , Manualcall points, Electronic Hooters etc.after rectification of fault byfixing of new items and required repairing workof AFD system i/c arranging of FIRE DRILL in the presence of Building Incharge/ Site incharge , testing for proper functioning etc. complete as required.