Tender For Internal Electrical External Electrical Lan And Cctv Fire Fighting And Lift Work In Construction Of Family Court Building In Animal Husbandry Department Premises At Gandhi Nagar Jaipur, jaipur-Rajasthan

Rajasthan State Road Development And Construction Corporation Limited has published Tender For Internal Electrical External Electrical Lan And Cctv Fire Fighting And Lift Work In Construction Of Family Court Building In Animal Husbandry Department Premises At Gandhi Nagar Jaipur. Submission Date for this Tender is 22-03-2024. CCTV System Tenders in jaipur Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

42886472
Tender For Internal Electrical External Electrical Lan And Cctv Fire Fighting And Lift Work In Construction Of Family Court Building In Animal Husbandry Department Premises At Gandhi Nagar Jaipur
Open Tender
Indian
Rajasthan
jaipur
22-03-2024

Tender Details

Tender For Internal Electrical External Electrical Lan And Cctv Fire Fighting And Lift Work In Construction Of Family Court Building In Animal Husbandry Department Premises At Gandhi Nagar Jaipur

Key Value

Document Fees
INR 2360 /-
EMD
INR 805800.0 /-
Tender Value
INR 4.02 Crore /-

BOQ Items

Name of Work : -Internal Electrical , External Electrical , Lan & CCTV , Fire Fighting and Lift work in construction of Family Court Building in Animal Husbandry Department Premises at Gandhi NagarJaipur.
Sl. No. Item Description
1Internal Electrification
2Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694)inrecessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it"sISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thickHot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws,making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheet"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure "A" attached with this BSR
3Short point (up to 3 mtr.)
4Medium point (up to 6 mtr.)
5Long point(up to 10 mtr.)
6Wiring of twin control light point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694)in recessed ISI markedMMS ( IS:9537 P - III ) PVC conduit & it"s ISI marked (IS:3419-1988) accessories, round tiles, 2 Nos Hot Dipped Galvanized M.S Modularbox of 1.2 mm thickwith earth terminal,2 Nos10 A two way Modular switch, 3 pin ceiling rose / holder / 3 way connector ,Modular face plate with grid plate,screws,making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheet"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure "A" attached with this BSR
7Long point(up to 10 mtr.)
8Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal sizeFR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) inrecessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it"s ISI marked (IS:3419-1988)accessories, Hot Dipped GalvanizedModular box of 1.2 mm thick with earth terminal, 10 A modularswitch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheet"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure "A" attached with this BSR
9On board
10S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along withISI marked (IS:3419-1988) accessories as requiredinrecessincludingcutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
1120 mm
1225 mm
1332 mm
1440 mm
1550 mm
16Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,in existingsurface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
172 x 1.5 sq.mm
183x 1.5 sq.mm
192 x 2.5 sq. mm. + 1x1.5sqmm
202 x 4.0 sq. mm. + 1 x 2.5 sq. mm.
212 x 6.0 sq. mm. + 1 x 4.0 sq. mm.
222 x 6.0 sq.mm
232 x 4.0 sq.mm
244 x 10.0 sq.mm
254 x 6.0 sq.mm
26Supplying and drawing coaxial cable 75 ohm impedance with foam PE insulated solid bare copper inner conductor, and Ist outer conductor of bonded alum. tape and second outer conductor ofalum. alloy braidin existingsurface or recessed conduit/casing capping including making connections as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
27RG - 6
28P & F 1.2mm thickM.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm,12 mm dia rod fan hook with 100 mmlength extended on each side . All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
29P & F of Gravity Louver shutter of superior quality made out of frame of18 swg M.S. sheet & Louvers made from 24 swg MS Sheetwith enamel paint including cost of nuts, bolts, etc as reqd.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
30Up to 380 mm size
31Providing & Fixing ofextra down rod of 15 mm dia . ERW (Electrical resistance welded ) of 1.6mm nominal thick medium duty steelpipe including cutting, threading, drilling, fixing quarter pin etc as reqd.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
32Providing & Fixing of single / multi tone electronic call bell as per PWD specification for electrical Works, including making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
33Providing & Fixing of modular type switch/ bell push duly ISI marked (IS :3854) with CM/L no. printed and made out of unbreakable and fire retardant vergin UV Stabilized Polycarbonatewith brass terminals and captive screws & silver alloy contact tipwith IP-20 rating ,minimum width ofswitch toggle( PUSH PART ) should not less then 20mm,includingall as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
3410 A one way switch
3510 A bell push
36Providing & Fixing of modular type lockable feature socket dulymade out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating , includingall as per pre approved by Engineer in charge,making connections, testing etc. as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
376 A3/5 pin shuttered socket
3825 Amp. 2 Module Socket
39Providing & Fixing of modular type 120 W Step Fan regulator duly ISI marked (IS 11037:1984 ) with CM/L no. printedmade out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating ,includingall as per pre approved by Engineer in charge,making connections, testing etc. as required.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
405 step fan regulator 2 Module 360 dgree rotating
41Providing & Fixing of following modular accessories as per PWD specification for electrical Works,made out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating , includingall as per pre approved by Engineer in charge,making connections, testing etc. as required.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
42T.V. coaxial socket
43RJ-11 telephone jack Double line
44Blanking plate
45Modular MCB 6 A to 32 ADP
46Providing & Fixing offollowing size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
471/2 Module
488 Module
49Providing & Fixing ofWiring Accessories OEM fabricated following size GI box of 1.2 mm thick with earthing terminal and adjustable floating clamp in recess/ surface suitable for modular accessories as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
501-2 Module
516 / 8 module
52Providing & Fixing of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminiumhousing with in built driver, System lumen efficacy = 110 lm/Watt output, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.=0.95, CRI >80 , life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , Maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
53570mm (+/-10%) batten with min. lumen output 1000 lm
541170mm(+/-10%) LED batten with min. lumen output 2200 lm
55Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / SqaureSMD Mid Power LED Downlight with power coated die-cast aluminum housingwith UV Stabilized non yellowish Diffuser withBIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% . System Lumen efficacy of = 110 lm / watt, THD < 10 % , Pf.=0.95, CRI >80,life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing.
56OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
57Surface Mounting (with extruded alumn. Housing )
58Minimum lumen output 1300 lm
59Minimum lumen output 1950 lm
60Providing & Fixing of IP20, 2"x2" LED Surface/ Recessedmounting Mid power SMD type LED Light fixture not less than 50mm housing depth made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non -yellowish diffuser for uniform light distribution. High efficiency with 4 KV internal/external surge protection BIS certified isolated driver having efficiency > 85% , with Short & Open circuit protection(Integral with light fixture). System lumen efficacy of = 120 lm/Watt ,THD < 10 % , p.f.=0.95,CRI >80 ,life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing.
61OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
62Surface Moutning
63Minimum lumen output 4200 lm
64Providing & Fixing of IP65 IK08 rated Integrated SMD Mid power LED bulk head type light fixture made from Pressure Die Cast AL housing suitable with integral driver, system lumen efficacy =100 lm/Watt output , THD < 10% ,p.f.=0.95,CRI >80 , life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. surge protection 4 KV. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
65Minimum lumen output 1000 lm
66Providing & Fixing of 400 mm SweepBLDC technology Oscillating type Wall mounting / Pedestal typefans with Three speed, ON andOFF position, Double Wall bearing withfront and back 120 or moreribs guard; Three no.blades, noise level should be <= 75 dB,including fixing with anchor bolts, making connection testing etc. as required. ( With Remote ) All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
67Wall mounting type with Service value 2.0 CMM /W, Min. Air Delivery 71 CMM
68Providing & Fixing ofBEEStar rated copper wounded double ball bearing capacitor start, aluminium body & Metallicblade ceilingfanConforming to all the performance requirements laid down in IS 374:2019 including all amendments, as applicable ; & Carry BIS licensing (i.e. ISI marking) with down rod up to 80 cm with secondary support safety cable ( steel rope) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
691200 mm Sweep BEE 1 Star rated (service value >=4.0 to < 4.5 )
70Providing & Fixing of Heavy duty capacitor start, copper woundDouble ball bearing900/1400 RPM single phaseExhaustfan conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
71300 mm sweep(900/1400 RPM)
72380 mm sweep(900/1400 RPM)
73Providing & Fixing ofof ventilating fans Capacitor start, copper wounded, single phase with PVC impeller, ABS body, automatic openable louver shutter in existing opening including making connection, testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
74250 mm sweep
75Providing & Fixing ofof Double ball bearing, copper wounded capacitor startsingle phase metallicblade fresh air fan, in existing opening including cost of hardware , flexible 3 core copper conductor ,making connections, testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
76300 mm sweep
77Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminummaterial with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass coverand secondary lens on each LED & should be SMD type of 3 to 5 watt each . The System efficacy >=125 lm/ wt and potted driver& has a unique BIS R number withInput Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety , Power Factor >0.95 driverEfficiency >85%,THD(I) <10%Humidity 10% to 90% RH Working Temp -5C to 45C .driver current <750mA. The luminaireshall be BIS certified and Trade mark certified. Life ExpectancyEqual or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min = 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs.Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
78LED Street Light fixture with Minimum lumen output 11225 lm
79Supply and erection ofGalvanized Iron pole with galvanizing done in single dipping (Average coating thickness Minimum 65 Microns) continuously tapered poles having Octagonal / Circular cross-sections designed to withstand the maximum wind speed as per IS 875, The pole shaft shall be made from sheet steel (HT Steel Conforming to grade S355JO) and confirming to BSEN 10025 and shall be continuously tapered with single longitudinal welding. There shall not be any circumferential welding. The welding of pole shaft shall be done by Submerged Arc Welding (SAW) process. pole shafts shall be provided with the rigid flange plate of suitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4 no. foundation bolts, This base plate shall be fillet welded to the pole shaft at two locations i.e. from inside and outside.The octagonal Poles shall have lockable door of approximate 500 mm length at the elevation of 500 mm from the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) inside the pole at door opening for cable connection of following length and dimension as per table P-01 with base plate and foundation bolt on the Existing cement concrete foundation.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
80Poles with Octagonal Cross Section
817 Mtr.
82Supply and Fixing of Pole OEM fabricated hot dipped galvanised M.S. Overhang (48.3 X 3.25 mm) with cap (400 x 88.9 / 114.3 x 3.25 mm) over the existing poles. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
83Single arm overhang
84Providing and Laying RCC Foundation for Octagonal/ Conical Street Light poles, High mast Poles as per Drawing attach at TableP-4with Following Procedure& All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
85A) Excavation of Pit for Foundation Size upto required depth from Ground level
86B) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surface complete.
87C) Providing and laying in position cement concrete of M-10 grade of 75 mm thickness
88D) Reinforcement for R.C.C. work with TMT bars including straightening, cutting, bending, placing in position and binding all complete.
89E) Centring and shuttering including strutting , propping etc. and removal of form work for Footing and Pedestal
90F) Providing & Fixing of 2 no. Required SizePLB HDPE Pipe& Foundation Bolt with template as per OEM Recommendations.
91G) Providing and LayingReinforce cement Concrete of M-25 grade in Footing and Pedestal including Curing the foundation for 7 days.
92H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2 no. 100 mm long, 10 mm dia. Lugs on each face.
93Pole Foundation for Octagonal pole from 7 Mtr. To 9 Mtr.
94Providing & Fixing of IK08IP65 protected Top/Bottom mounted LED Post top Luminarie made of single piece constructionpowder coated die cast alluminium housing with UV stabalized Clear / frosted Polycarbonate diffuser andAluminium anodised with sand blast reflector. The System level Luminous efficacy =100 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N)and efficiency > 85%, PF>0.9, THD<10% and input Voltage range of 140-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained . Driver current <750mA.Fixture must be in compliance with BIS Standards and Trade mark Certificate complete in all respect.OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
95Minimum lumen output 4000 lm Post top Luminarie
96Providing & Fixing of Street light bracket made out from following size of " B " class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
9740 mm Dia.
98Providing and laying Non Pressure NP-3 classR.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) etc. as required. (Excavation of Earth& Back filling with compaction is to be Paid Extra). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
99200 mm Dia.
100labour charges for Excavating trenches of required width for pipes dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr.:
101All kind of Soils
102Supply & Laying following size" B " class ,G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc.for laying earth conductor/ strip / cable in ground/ surface/ recess as required.All as per pre approved by Engineer in charge.(Earth Excavation will be Paid Extra)All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annex ure "A" attached with this BSR .
10340 mm dia.
10450 mm dia.
105Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load andsite requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted inexisting distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above ratingincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
106Single pole MCB (With B/C curve tripping Characteristics)
1076 A to 32 A rating
108Double pole MCB(With B/C curve tripping Characteristics)
10950/63 A rating
110Triple pole MCB(With B/C curve trippingCharacteristics)
1116 A to 32 A rating
11250/63 A rating
113Four pole MCB (With B/C curve tripping Characteristics)
11450/63 A rating
11540 A rating
116Providing & Fixing of 240/415 V Residual current circuit breaker (RCCB) conforming to (IS:12640-1)/ IEC 61008 -1 , rated 4 KV impulse withstand voltage truly current operated and shall operate on CBCT mechanisum, provision for pad lock,min. operation 10,000 upto 63 A rating and5000 for 100 Aratingand minimum phase termination capacity of 35 sq.mm. rigid wire, IP 20 contact protection with existing distribution board / sheetincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
117Two pole 100/300mA sensitivity
11840 A rating
11963 A rating
120Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick  conforming to IS-8623-1 & 3 /  IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp.  insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set  of suitable rating and din bar,masking sheet,  making internal DB  terminations with copper lugs, Ferrules,  detachable gland plate, including making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
121Metal door (single phase) IK-09 and IP-43 with Metal end box
12212 Way (12+2)
123Metal door (Three phase) Per phase isolation, Horizontal IK-09 and IP-43 with Metal end box
12412 Way(Incomer 8,Sub Incomer2+2+2)
125Providing & Fixing of Recessed/surface mounting heavy duty Vertical TPN Distribution board with Metal end box with provision of incomer suitable for 3/4 pole MCCB and SP / TP MCB as outgoing ,made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick  conforming to IS-8623-1 & 3 /  IEC 61439- 1 & 3. powder painted with reversible door (for double door DB only ) complete with insulated 160 (upto 160 A Incomer) / 250 Amp.  copper bus bar, neutral bars with shrouds,  earth bar , color coded interconnecting wire set  of suitable rating and din bar,masking sheet,  making internal DB  terminations with copper lugs, ferrules,  detachable gland plate, including making connections, testing etc. as required.  OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
126Double door IP-43 & IK-09 with Provision of Incomer MCCB 160 A Rating with Metal end box
1276 Way
128Double door IP-43 & IK-09 with Provision of Incomer MCCB 250 A Rating with Metal end box
1296 Way
130Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
1316.0 Sq. mm
1324 core
13316.0 Sq. mm
1344 core
13550.0 Sq. mm
1363.5 core
13795.0 Sq. mm
1383.5 core
139120.0 Sq. mm
1403.5 core
141240.0 Sq. mm
1423.5 core
143300.0 Sq. mm
1443.5 core
145Add extrain item no. 11.1 to 11.4 for Laying Charges for cable through Manual Boggi by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required.
146Add Extra for Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV gradedirect in ground including excavation of trench of size 75 cm (Depth) x 35 cm(Width) ,with procedure as per followingpoints:- (a) Make a river sand bed of height 125 mm along the trench,(b) Lay the cable in the middle of the trench,(c) Provide river sand bed of height 125 mm on top of the cable, (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thicknessand 225 mm widejust above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth
147Add Extra for Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV gradedirect in ground in the same trench in one tier horizontal formation including excavation of trench of size additional 20 cm in width,with procedure as per following points :- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay another cable in middle of trench in such manner that spacing between another cable is 20 cm., (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 /Sand stone slabs of 50 mm thicknessand 225 mm widejust above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth
148Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring,Compression Nut,heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as perIS 8337-1976offollowing size ofPVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1493.5 x 240.0 sq.mm
1503.5 x 35.0 sq.mm
1513.5 x 95.0 sq.mm
1524 x 6.0 sq.mm
1534 x 16.0 sq.mm
1543.5 x 120.0 sq.mm
1553.5 x 300.0 sq.mm
156Supplying and makingend termination with heavy aluminiumlugs ( Pin / ring type )confirming to IS 8309 -1993 & IS 8337-1976 duly crimped with crimping tool, PVC tape etc of following size.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
157300.0 Sq.mm
158Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
159150mm x 50mm x 1.6mm
160300mm x 50mm x 1.6mm
161Supplying and fixing of power plug point with Modular accessories as per PWD specification for electrical Works, on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost ofISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required. For specification ofWiring accessories refer ChapterE - 07related item & For additional technical parameters of product / work refer Annexure "A" attached with this BSR
162P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class750 N,Externally corrugated and having smooth surface insidewith HDPE Coupler, Elbow, Teeat required Depth below the ground for laying cable of followingNominal Outer dia.MFR Test reportfrom NABL accrediated is to be submitted.(Excavation of Earth& Back filling with compaction is to be Paid Extra)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
16350 mm
164110 mm
165External electrical work
166Providing & Laying XLPE insulated three core ArmouredAluminiumcable for working voltage 11 K.V.(E) confirming IS :7098 P - 2withH4- Grade electrolyticaluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810 All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1673 core 185.0 Sq.mm
168Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kitsuitable for11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streightthrough joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Crosslinking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. includingtesting etc. as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
16911 KV End Termination Kit Indoor type
1703 core 120/150/185 Sq.mm
17111 KV End Termination Kit Outdoor type
1723 core 120/150/185 Sq.mm
173Supplyandinstallationofhigh tensile low carbon steel rod molecularly bonded with 99.9 % Copperthickness (250 microns) andconfirming toUL 467, IS/IEC 62561-2of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :-
174(a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole
175(b)filled with anti corrosiveconductivecompounds with the permanent sealings at both the ends, CPRI/ ERDAtested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated labfor lowresistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major contentas per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts
176© Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt
177(d) Place Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm.
178(d)Testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book.
179(e) Test certificatesfor confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
18025 mm thick and 3 Mtr. Long
181Plate Earthing as per IS:3043 withcopper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying3 mtr. below the ground level with 20mm dia. G.I. "B" class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm. and embodying the pipecomplete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
182Supply & Laying following size earth stripin horizontal or vertical run in surface by means of Earth strip DMC Insulatorincluding riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
18325mm x 6mm G.I. ( Hot Dipped) Strip
18450mm x 6mm copper strip
185Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles,making connection with GI/Cu purity purity >95%thimble etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1868 SWG tinned copper Wire
1878 SWG G.I. ( Hot Dipped) Wire
188Providing & Fixing of ISO certified company made on load change over switch, front handle operated, four pole 415 V as per PWD specificationfor electrical Works conforming to IS/lEC 60947-3 : 1999 including connections , testing etc. as required .in the following rating.Appropriate type test certificate / OEM test report shall be submitted .All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
189Open execution type
190200 A
191SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalisedcubical panel as specifications andOther parameters requiredas per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:-
192(a)Thickness of CRCA sheet shallbe 2.0 mm,cable alley compartments having concealed hinged type doors with key type lock with / withoutdetachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided
193(b)complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting,pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel.The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire.
194[c)Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar(>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only.All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar/ Flexible wire for Interconnection between Main busbar and Switchgearis to be Paid Extra )
195(d)Wiring between components within switchgear and Incoming / outgoing cableshall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram.
196(e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.
197(f)Floor mounted panel shall be mounted on Base frame of ISMCchannel size 100 x 50 x 5 mm( to be paid Extra )
198(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out.
199(h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
200Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulatorwith standard short circuit withstand capacity, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
201Electrolytic grade Aluminium bus bar 6010 grade
202Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type(up to 500) V range Volt meter / Direct- Ammeter /CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracyas per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
203Threephase AMP+HZ+PF+KW+KVA+KVAR+T.ENERGY+THD-I, THD-V & RUN HRS
204Providing & Fixing of BIS approvedCurrent Transformeras per PWD specification for electrical Works ,ISI marked as perIS 2705-1992/ conforming to IEC 60044-1, with secondary terminalof CT shall be brought out suitable to a terminal block which shall be easier accessible for testing and terminal connection , with all necessary support in existing panel including connection etc. as requiredCurrent transformer Ring Type Tape Wound/Resin Cast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . All as per pre approved by Engineer in charge.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
205Ring type tape wound CT
206C T Class 1, Ratio 200/5 to 300/5, Burden 10 VA
207C T Class 1, Ratio 400/5 to 1200/5, Burden 15 VA
208Providing & Fixing ofCam operated rotary (Auto/manual) switches on existing panel with 2 way and off position using high grade engineering materialto international standards with cam assemblyinsulation of glass filled polyamide with high tracking index. For reliable and stable electrical and mechanical endurance double butt contacts with silver bi-metal on copper should provided . contact assembly is of operating temp range -25 degree C to 55 degree C, frequency upto 10 KHz. switch life under std. op. conditions shall be mechanically minimum 50000 operations @300 cycles/ hour and electrically 10,000 operations at 100% rated duty for 100 cycles/ hour including making connection etc.as required . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
20932 AMP
210Providing & Fixing of110/220 V, unibody LED Indicatinglamp IEC 60947with integral circuit, IP 65 above panel &IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min.29 mm, contact material phospher bronze for Led, PCB contacts shall be ofbrass (tin plated), impulsedielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDCincluding connection etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
211Red/yellow/Green colour
212Blue / white Colour
213Providing & Fixing of Electricalinsulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006with one sideanti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
21411 KV,Class B 2.5 mm thick with proof voltage 22 KV AC (rms) and Break Down Voltage45 KV AC (rms)
215Providing & Fixing of self healing IP20 MPP type shunt capacitor (banks) conforming to IS:13340-41 /IEC :831-1&2 OR IEC : 60831-1& 2 in existing panel or parallel with load terminals , the capacitor shall be fitted with discharge resistors, pressure sensitive disconnector ( PSD ) and shall have dissipation factor less than 0.0025 at 50 Hz, Operating loss less than 0.30 Watt per KVAR. Min over current capacity 1.8 times rated current & peak inrush current min. 300 times of rated current, llife expectancy greater than 100000hrs(temp class - 25 D)in 440 V/480 V Capacitor and for 525 V should life expectancy minimum 1,65,000 hrs (temp class - 25 D)including making connections, testing etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
216Heavy dutyThree phase 525V, 50 Hzcylindrical typecapacitor (Bank)
217Providing & Fixing of IP54 microprocessor based 3 CT’s for all 3 phasesensing compensationpower factor correction relay Size 139mm x 139 mm, Operating Voltage 415/440 V, IEC / EN 61000-6-(2&4)having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall havedigit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485,indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR, RMS Value, step switching time 2 sec to 1800 sec. Lead & Lag parameters, metering facility and3 no. Class- 0.5 Cast ResinCT ( refer CT specs in this chapter )for sensing the relay including making coonection with 1.5 Sq.mm copper wire etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
21812 to 14 stage
219Providing & Fixing of 3-Phase 415/440 V , 7 % / 14 % Detuned Reactors conforming to IEC 61558-2-20 & IEC 60076-6 Aluminium woundfor harmonics filter with 180% to 200 % Linearity, H - Class Insulation ( 180 degree C), high temp. Disconnection above 155 deg C., ambient temperature: +60 deg C. with thermal cut off switch in existing panel with following Capacitor ratings. including making connections, testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
22014 % (133 Hz) Aluminium wound Reactors (1-2-2-5-10-10-15-15-20-20-25-25)
221For 1 to 5 KVAR capacitor
22210 KVAR
22315 KVAR
22420 KVAR
22525 KVAR
226SITC of3 /4pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant materialhaving following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with frontface and centralised adjustable, trip free mechanisum, true contact position indicator,line load interchangeability,designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree,pollution degree 3, having positive isolation capability, push(test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage690 V.provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connectionsetc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
2274 pole MCCB With Thermal Magnetic release
228up to 100 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
229125 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
230160 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
231200 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
232250 Amp , 35 kA, adjustable O/L & adjustable S/C setting,
2334 pole MCCB With Microprocessor based release with adjustable O/L &S/C setting with Inbuilt Instantaneous and Ground fault Protection.
234630 Amp, 50 kA
235S I T C of star ratedAluminium wound distribution Transformerof following rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11,ONAN Cooled & as per BEE star - 1 & BIS approved as per IS 2026- 1977 & lossesas defined as per 2014 (Fourth Revision) Level-1 . including standardaccessories like conservator, silica gel breather, radiator, fins, HT cable box & LT cable boxes, temperature rise in winding/oil 35-40 degree C upto 200 KVA & 40-45 degree C for above 200 KVA, ISI marked drain valve, Dial type Temperature gauge, first filling of transformer oil as per IS :335-1953, Epoxy based paint,including carrying of pre-commission Testing & Charging of Transformer complete in all respect .
236The Transformer shall be subjected to routine factory tests (as per IS:2026 and IS:1180) including testing from CTLof discombefore charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, (CTL testing charges and Electrical Inspection charges shall be reimbursed by the department to the contractor). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
237400 KVA with Off -LTC (+5% to - 10% @ 2.5%)
238SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated, outdoor duty (IP54) , Extensible / Non extensible typeRing main unit (RMU)manually operated in combination ofVCB modules andLoad Break switch consisting of Copper busbar in SF6 insulated 304 (Non-Ferrite Non-Magnetic Grade) stainless steel enclosure of thickness 2.5mm with manometer.The HV switchgear and control gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The RMU should be internal arc tested for 21KA for 1Second with IAC-AFL classification for gas tank. Vacum Interrupter of VCB should be RMU Manufacturer’s own make.Each feeder of RMU should have voltage presence indicator. . and compring offollowings:- 1 no. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder. - 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy class 5P10for O/C and E/F protection for each VCB.- 1 No. Manometer for each tank,- 1 nos. Fault Passage indicator,-Right angle boots for all the feeder ModulesAll the type test certificates as per IEC from Third partyNABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation / Steel Structure to be paid Extra) All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR
239Non Extensible 3 way RMU with 1 no. VCB & 2 No. Load Break Switch
240SITC of HT metering cubical panel as approved By DISCOMs fabricated out of 18 SWG CRCA sheet steel in two compartment & MS angle of size 60mmX 6mm having provision for Following: (i)Provision for fixing Trivector / Import - Export Meter (To be supplied by DISCOMs) (ii)Provision for fixing of combined CT PT Set with Copper strip for Connection (To be supplied by DISCOMs), (iii)Test terminal Block, (iv) 6mm thick Bakelite sheet on all sides, (V) 3/6 corex 1.5 / 2.5 Sq.mm copper cable for interconnections,etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
241SITC of Radiator Cooled and Turbo charged Silent DG Set (As per latest CPCB emissionnorms) havingspecifications as per A, B, C, D, E, F,G,H & I
242A) 1500 RPM Diesel Engine conforming to BS:649/5514 of suitable BHP(up to 82.5 kVA 6 cylinder or Below required, 125 kVA & Above ratings 6 cylinder or aboverequired ) capable of taking 10% over loading for one hour after 12 hours of continuous operation.,Dry exhaust mainfold with Hospital grade silencer and catalytic convertor(isolated from main DG chamber),up to 3 M exhaust piping (with LRB insulation & Alum. cladding ) as required .
243B)AC Brush less SPDP Alternator conform to BS 5000 (part 99) or IS/IEC 60034-1. . Alternator shall be self regulated with standard Alternator Protection( Over voltage , over speed & under voltage, under speed warning & shutdown).Engine & Alternator mounted on a common base Frame & coupled through a flexible coupling or close coupled
244C) CPCB / ARAI approved Standard canopy with Weatherproof, powdercoated Accoustic enclosure for DG set for sound attenuation fabricated from 1.6 mm CRCA sheet steel (structure) with sidewall fabricated from 1.6 mm CRCA sheet & filled with glasswool (96Kg/m3) / Foam. as per IS8183 the doors of 28/40/50/85mm thick as perrating and fabricated from 1.6mm CRCA sheet packed with accoustic material, All doors/opening are sealed with neoprene /EPDNgaskets. The DG Set has Inbuilt / External in fuel tank to run 6 to 8 Hrs as per OEM standard, with protection and tripping of DG set against temperature of more than 50 degree centigrade.
245D) Electronic / Mechanical governor, Manual & electric Start ,Batteries with battry charger,Engine instruments panel,AVM pads All controls for operation of DG set are from outside the enclosure with DG control panel having Microprocessor based Genset monitoring like Running Hour, RPM, Low Lube Oil tripping & control system, Panel mounted MCCB/ACB of suitable rating, Ammeter, Voltmeter, PF meter, frequency meter, KWH meter,digital fuel display meter, Ind.lamps etc. mounted inside enclosure , visible and accessible from outside. The enclosure should be suitable for following capacity DG sets and alternator. Noise level shall be less than 75 dB at a distance of 1 Mtrs. duly certified by authorised agency etc. complete in all respect of following capacity :
246E) (i) Accoustic glass wool wall thickness should not be less then 40mm and not less then 20mm PU foam upto rating 100 KVA. (ii).Accoustic glass wool wall thickness should not be less then 65mm and not less then 50mm PU foam upto rating 250 KVA. (iii)Accoustic glass wool wall thickness should not be less then 100mm forrating above 250 KVA.
247F) First filling of the fuel tank shall be done by contractor and the prevailing fuel cost at that time shall be reimbursed to the contactor by department.
248G) Servicing Contract of DG Set from OEM"s Authorised Service Dealer as per OEM guidelines during the DLP period shall be done by contractor including all consumables, actual charges shall be reimbursed to the contractor by End User Department.
249H) Manufacturer / OEM must have its authorized service dealer in Rajasthan. Which can provide service within 6 Hours of compalint registration.
250I) DG set will be offered for Inspection and Testing at Manufacturer"s Works in presence of Departmental Engineers. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
251125 KVA at 0.8 pf 415V 50Hz 3-?
252SITC of PLC Based Auto main failure (AMF) Panel fabricated from CRCA sheet steel 2 mmThick , Powder coated finish , Engine Start & Stopcommands, control Relays , Ammeter & Voltmeterwith selector switches, Control & 2 nos 4 pole Power Contactors with 2 no. of required size 4 pole MCCB, Timers, Electronic Hooter ,Visual & Alarm indication for faults, UPS, operator interface panel complete in all respect suitable for following capacity DG sets: Appropriate Test Certificate/ report of product/accessories from OEM/Panel Manufecturer shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
253100 to 140 KVA
254Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as requiredcomplete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
255Supply and fixing of following accessories for Moulded case circuit breaker (MCCB)compatible to main MCCB OEM as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 including making connection etc complete in all respect. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
256Extended Rotary Handle
257SITC of Single Stage, water cooled, High Speed (2880 RPM), Horizontal, Centrifugal, Openwell Submersible pumps set pre filled with coolent water and fitted with mechanical seal - T/C Vs T/C, Thrust bearing shall be ofcarbon + S.S.The stator body of single phase pumpshall be of SS and rest of all shall be of cast iron. All casting parts should be cathod electro deposition (CED) coated and other construction material should be confirming to IS : 14220: 2018 . The overall performance of pump shall confirm to BEE energy efficiency level of 3 star. Valid BEE certificate from OEM must be submitted for the same. Motor should be IE2 class as per IEC 60034-2-1: 2007, IEC 60034-30: 2008,& IS12615:2011, including making connection etc as required complete in all respect. OEM shall have submitNABL / CPRI / ERDA accrediatedlab type test certificate before execution. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
2585.0 HP, 3-Ø, (14 -28) Mtr, (995-500) LPM
259SITC of ContactorOEM Fabricated DOL/Star-Delta Starter panel with switchgear selection as per Type-2 Cordinatiom Chart andmade out from 1.6 mm thick powder coated CRCA sheet, enclosure comprising of over load protection relay, short circuit & single phasing protection, Illuminated ON / OFFpush buttons,ammeter, voltmeter, indicating lamps etc.suitable for following rating motors complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
260For Three phase Submersible / Mono block pump
2613.0 HP to 5.0 HP ( DOL starter )
262Providing and fixing welded mesh/expanded metal mesh 25 mmx 25 mm x 3mm in frame work, flat iron beading 20x3mm including top cross laps inside and out sides welding, iron bolts, crews, clips etc. including two coat of red oxide and two coat of enamel paint or more requiredcomplete with frame work with 50 X 50 X 6mm angle iron post 30 cm in ground embeded in cement concrete 1:3:6 (30X30X45cm) at corner and every three mtr including painting with one coat of primer and two coat of enamel paint work will be done as per direction of engineer incharge of sizecomplete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
263Supply and Fixing of Test Joint (Folding Clamp) made of SS,suitable to connect 8mm round conductor with25 mm x 6 mm GI strip etc. as required. the test report accredited by third party accreditation body likeVDE/ILAC/ DAkkS/ UL/ NABL is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annex ure "A" attached with this BSR .
264SITC Of Low Height Ceiling Fanwith sweep (dia of blade) 400 +/- 5mm sweep, Air delivery 75CMM , Rated Power 95watt, supplyvoltage 230 v 50Hz single phase, rated speed 1750 RPM, power factor ->0.90 ,size- 580x580+/- 5 mm make- Halonix, havells, Crompton
265P & F of Early streamer Emission type lightning arrester on GI mast with air terminal configured as spheroid which is comprised ofseparate electrically isolated 4 panels surrounding an earthed central finial, the terminal shall be tested by CPRI for impulse current of 45 kA ( 8 / 20 Sec ) with 5 positive & 5 negative impulse, the arrester having following protection radius at level 1 Approved Makes :LPI (Australia ), LPSFR (France ), Sudafix ( UK ), EF ( Switzerland ), ABB
26630 - 48 Mtr.
267P & F Lightning counter - To count no of lightning strike & it can record the date and time of the lightning incident also tested as per IEC 62561-6. as approved makes LPI (Australia ), LPSFR (France ), Sudafix ( UK ), EF ( Switzerland ), ABB
268S & Laying of P.V.C. / XLPE insulated & P.V.C. sheathed down conductor of 70 Sq.mm single core insulated flexible copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withelectrolytic gradeCopper made of copper rodsconfirming to IS 613-1964, of purity >99.7 %,Inner / outer sheath confirming to IS:5831 with accessories as required. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810Approved Makes: polycab, RR, Finolex.
269Lan and CCTV work
270S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along withISI marked (IS:3419-1988) accessories as requiredinrecessincludingcutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
27125 mm
272Providing & Fixing of ISO certified company made virgin material PVC trunking systemas per PWD specification for electrical Works, with double lock feature for cable management including finishing accessories like corners, tees, adjustable angles, junction etc. as required . The trunking system shall haveadaptable system for modular type RJ 45 data socket/ wiring accessories/ power sockets and shall be covered with peal off plastic cover. OEM shall have submitNABL accrediated /CPET lab test reportsbefore execution & All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
27332mm X 20mm
274100/105mm x 50mm
275Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, UTP (Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected byPVC Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies up to 250 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack &ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
276Supply and Installation of unsheilded/360 degree sheilded Information outlets made of high impact plastic body with ABS, FR Grade halogen free material with provision for protection against dust in jack, suitable for Cat 6/6A application complying to latest ammendments, According. to Cat. 6/6A channel, It should support channel as well as components requirements of Cat.6/6A standards at frequencies of up to 250 to 500 Mhz. Cat 6/6A unshielded/shielded Jack should be suitable to terminate 4 pair, 23/24 AWG solid/stranded wire diameters, using 100 Ohm unshielded/shielded balance twisted pair cable, the jack should have tooless/impact termination on reliable copper tin plated Insulation displacement contact, with easy lock mechanism, It supports IEC 60603-7-4 and complied with ANSI/TIA/EIA 568 C.2 standard. jack should be RJ11,RJ12 & RJ45 compatible. Should support Ethernet 1.2 Gb/s ATM,Digital video and broadband/baseband analog video, Voice over internet protocal (VOIP) Specifications in existing modular/MS Boxes along with necessory connections as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
277Cat 6, Un-sheilded Information Outlet
278Supply & fixing of square Faceplate for Flush / Surface Mount Information Outlets Single/Dual or Quad Aperture ,material should bePC+ABS body, Suitable for RJ45 unshielded/shielded connection modules. Should match with I. O. OEM. Dimensions should be 86mm X 86mm as required complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
279Single Aperture
280Providing & Fixing of Wiring Accessories OEM fabricated following size virgin materialUPVCmodular boxes on surface suitable for modular accessories as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
2811-2-3 Module
282Supply, Installation, Testing and Comissioning of Rack mounted 19" 1U, Cat6 24 Port loaded, 1.5-1.6 MM CRS chasis, powder coated, sheet steel, made of plastic (ABS), Modular Patch Panelswith Rear Cable management system and mounting hardware to mount the patch panel. Should have port identification numbers printed/engraved on front of the panel. Etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
283Modular Patch Panel Loaded with Cat -6 I/O
284Supply , Installation and Testing of 4 pair, 100 Ohm impedance, Cat 6/6A /Class E/Ea patch cords should be constructed of minimum 23/24 AWG, stranded bare Copper cable with FRPVC/LSZH Jacket, with an enhanced performance by factory moulded RJ45 connectors with strain relief boots as per ANSI/TIA/EIA 568-C.2 suitable for Cat 6/6A application complying to latest ammendments Category 6/6A Standards, According. to TIA568C.2, ISO/IEC 11801, EN 50173, IEC 60603-7-51, EN 60603-7, IEEE 802.3an minimum requirement for 1G BASE-T to 10G BASE-T performance. Patch cords shall be straight thru cable compatible with both T568-A and T568-B wiring schemes, should support IEEE 802.3af / IEEE 802.3at for POE applications, Minimum 750 to 1000 mating cycles in plug contacts for long durability, Should support Ethernet 10GBASE-T, 1.2 Gb/s ATM, Token ring 4/16, Digital video and broadband/baseband analog video, Voice over internet protocal (VOIP).All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
2851 Mtr
2862 Mtr
287Supply, Drawing and Testing, of stranded Multimode (50/125 µm) glass optic fiber cable, as per latest ammendments of TIA/EIA 568/ISO/IEC 11801:2011/ IEC 60794-1-2 E1, E3,E11, F1/ EN 50173-1/ EN 187 000/ IEC 60974-2, 2-20, 2-21/ ITU G.652D, construction of LSZH outer sheath cable, cable should be used for LAN and WAN back bones, . With its LSZH sheathing these cables should be ideal for indoor/outdoorinstallations in existing MS/PVC /HDPE Conduits/ slotted channels with ferruling at both ends for identification complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
2886 fiber
289Supply, Installation, & Testing of Indoor duplex Multimode patch cord (50/125 µmmade of glass fiber optic with LSZH jacket, F8 2.0x4.1 mm, Multimode G652.D Mounted on both sides with ST/E-2000/SC/LC/MT-RJ/PC type Duplex connectors in acc. with IEC 61754-20. Zirconia (ceramic) ferrule with a PC polished endface geometry, connectors should be tuned in accordance with IEC 61755-3-1 and qualified in acc. with IEC 61753-1 for category U (uncontrolled environment, duplex clip and white plastic dust cover, should comply to delta IL < 0.2 dB after 500 mating cycles, there should be an optional Visual coding, mechanical coding and lock protection on the patch cords which can be added on later stage. patch cords"s performance should be acc. to IEC 61753-1 (Table A.12) as per latest ammendments of TIA/EIA 569B.3, as per requirements.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
2903 Mtr
291Supply, Installation, & Testing of 19" 1U Rack Mounted/ surface mounted aluminum/ CRCA 1.2mm powder coated, multimode glass Fiber Optic Cable Patch panel/LIU loaded with flangless/screwable adapters for ST/E-2000/SC/LC/MT-RJ/PC type, It should have easy removable Top plate with push buttons, there should be a splice tray installed in the Patch panel/LIU which can handle the fiber cores, splice tray should be PC+ABS material, it should include accessories like mounting hardware, gormetts, heat shrink tubes/sleevs, screws, nuts to install the panel for rack/wallmount applications as per requirement complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
292Multi Mode LIU 6 Ports
293Multi Mode LIU 24 Ports
294Supply, Installation, OTDR Testing & Fusion Splicing of Fiber Multimode Pigtail (50/125 µm) made of glass fiber optic,should be fitted at one end with any one type of single ST/E-2000/SC/LC/MT-RJ/PC type connector in acc., as per latest ammendments of TIA/EIA 569Standard Specification as per requirments complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
295Supply , Installation, Testing and Comissioning ofHot pluggable Small Form Factor Pluggable (SFP Module), 1000BASE-SX, 1.25/2.125G Fiber Channel, LC Type Duplex Connector, 850nm laser transmitter, Should support distance upto 500m on 50/125um of data rate upto 2.125 Gb/s on bi-directional data links. Should also support industrial temperature, should have metal enclosure for lower EMI. The transceiver should be ROHS Compliant. (For Each MM Fiber) all switches & related Fiber modules should be of same make & category for seamless integration with each other of Enterprise class, complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
296Supply , Installation, Testing and Comissioning of Managed Layer-2 Intelligent Giga Ethernet Switch providing 24 x 10/100/1000 MBPSGiga Ethernet ports and with min 4 SFP Giga Ports (provision for Fiber Giga connectivity) all switches & related Fiber modules should be of same make & category for seamless integration with each other of Enterprise class Catalyst Series including making connections etc as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
297Supply & Installation of IP-20 & IK-08 , UL ListedWall mounted Double Section Communication enclosure (Rack) made from powder coated (60 to 80 Micron) CRCA sheet, front sturdy sheet steel frame folded from one piece and welded with minimum 5mm toughened glass door,Vertical Mounting Rail 1.6 MM with "U"Marking , with All round protective channel on the door aperture, lock integrated on front door, top and bottom cover with cable entry provision with gland plates, integrated side walls, 2 pair of 19" angles with wall mounting provision on wall. Accessories like: 1 No of 19" 1U Horizontal Cable manager, 1 No of 90 cfm 230V AC Fan with 1 mts long cable, mounting hardware , 1 No of 19" 1U, mountable socket strips with 5 nos of 5A universal sockets with 2 mts long power chord for supplying power to switches, fans etc along with earth continuity kit, indicator, moulded power supply cable. fixing on wall with Suitable Anchor fastneretc as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
29812 U Rackwith Width 600 mm &Depth 400 mm + 100 mm
299Supply & Installation of IP-20 & IK-08 , UL Listed Communication enclosure (Rack) made from powder coated (60 to 80 Micron) CRCA sheet,Vertical Mounting Rail 1.6 MM with "U"Marking, front sturdy sheet steel frame folded from one piece and welded with 5mm toughened glass door, with All round protective channel on the door aperture, lock integrated on front door, top and bottom cover with cable entry provision with gland plates, integrated side walls, Set of 75 mm height 4 castors, 2 of which have brakes, Accessories like: 5 Nos of 19" 1U Horizontal Cable manager, 2 Nos of vertical cable managers, 1 no. Keyboard Tray,4 Nos of 90 cfm 230V AC Fan with 1 mts long cable, mounting hardware , 2 No of 19" 1U, mountable socket strips with 6 nos of 5A universal sockets with 2 mts long power chord for supplying power to switches, fans etc along with earth continuity kit, indicator, moulded power supply cable complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
30022 U Rack with Width 600 mm &Depth 800 mm
301Add Extra for Workstation latest Intel® i5 processor, Intel Chipset motherboard, 08 GB RAM, 1 TB SATA HDD at 7200 rpm, with 2 x 4GB GPU type higher end Graphic card for H.265 compression technique with dual display ports/DVI/ HDMI port, Giga LAN Card, wireless Keyboard, wireless optical Mouse. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
302Supply and Laying of PE Insulated jelly filledArmouredTelephone Cable. with 0.6 mm thick Solid Annealed Bare Copper Conductor and confirming to TEC specificationsconfirming. to DOT GR/CUG-01/Aug.2003 in existing pipe / open trench / Cable tray / on surface including making necessary connection, testing etc. as required of size. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
30320 pair
304P & F Krone module with base framein the recess / surface made out of 1.2 mm thicksheet steel box, front openable, having locking arrangements duly powder painted,including dressing, ferrulingandpunchingof telephone cable with krone tool etc. as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
30550 Pairs
306Supply, Installation, Testing & Commissioning of Managed Layer-3 Intelligent Ethernet Switch providing 24 x 10/100/1000 Fast Ethernet ports with 8 dual purpose uplink ports (provision for Fiber Giga connectivity) with provision of retundent power supply with Network Advantage Software,all switches & related Fiber modules should be of same make & category for seamless integration with each other of Approved Makes: Cisco Catalyst Series or Equivalent inAvaya, Juniper )
307CCTV
308Supply, Installation, Testing and commissioning of Server Storage with video management solution for up to Professional edition of 32 channels. It should also have IP video management solution loaded with 16 TB HDD storage, 120 mbps throughput per unitwith1GbE Network connectivity, withAdvanced user and alarm, management, Robust, secure operation — instant real time access to video. There should no separate need of NVR. i.e. The system should be such that the video recording should be done directly on storage array without the use of NVR/ DNR & be fully loaded and fully functional with Microsoft Operating System and OEM application;Video Management System & Video Recording Manager including Video Streaming Gateway, Dynamic Transcodingcomplete in all respect and makes & modelas per pre approved by engineer incharge. The camera, software, storage should be of the same make for seamless integration with each other. MAF: Tender Specific OEM authorisation is mandatory for bid consideration (Approved Makes: Axis, Bosch, Avigilon)
309Supply, Installation, Testing & Commissioning of ONVIF S/G Profile Compliance based Indoor 2MP PoE True IP IR Dome Camera with latest H.264 or H.265 Compression with 1/2.8" CMOS Sensor with built in IR Illuminator 30 Mtrs having automatic varifocal lens from 3.5 to 10 mm lens with autofocus for both day/Night operation with Camera Built In Video Analytics like as Line Crossing, Enter/Leave Field, Follow Route, Loitering, Idle/Removed,object,. Camera should having intelligent stream management and Bandwidth reduction facility for storage management and better bit rate optimization facility. Camera Should have TCP/IP recording (dual acknowledgement). Camera should have Edge based recording facility for approx 3-5 minutes without attaching any additional SD memory card in case of network failure, Camera Should support ISCSI protocol for direct communication with client station in case of management / recording server failure, Camera should have minimum Color Illumination of 0.07 lux, Mono 0.03 lux and IR on @ 0 Lux. Camera should have True WDR facility 120db or more. The on-board Trusted Platform Module (TPM) and Public Key Infrastructure (PKI) support, guarantee superior protection from malicious attacks. The 802.1x network authentication with EAP/TLS, supports TLS 1.2 with updated cipher suites including AES 256 encryption. Camera should have UL, CE, FCC certification with IP 66 and IK10 impact protection. The camera, software, storage should be of the same make for seamless integration with each other of Approved Makes: Bosch / Axis/ Avigilon
310Supply, Installation, Testing & Commissioning of ONVIF S/G Profile 2MP PoE True IP 30 mtr IR Motorised Varifocal lens Bullet Camera: Outdoor 2MP PoE True IP IR Bullet Camera with latest H.265 Compression with 1/2.8" CMOS Sensor with built in IR Illuminator 30 Mtrs having automatic varifocal lens from 3.2 to 10 mm lens with autofocus for both day/Night operation with Camera Built In Video Analytics like as Auto Tracking, Line Crossing, Enter/Leave Field, Follow Route, Loitering, Idle/Removed object, People counting, crowd density and 3D tracking. Camera should having intelligent stream management and Bandwidth reduction facility for storage management and better bit rate optimization facility. Camera should have Edge based recording facility up to 2TB. Camera should have minimum Color Illumination of 0.37 lux, Mono 0.04 lux and IR on @ 0 Lux. Camera should have True WDR facility 120db. Camera should have iDNR facility for reducing bandwidth and increasing storage. Camera should supports 4 Type of streams for viewing and recording. Camera should have onboard data security by using TPM (Trusted Platform Module) and PKI support for guaranteed and superior protection from hacking and malicious attacks. Camera should have UL, CE, FCC certification with IP 66 and IK10 impact protection. The camera, software, storage should be of the same make for seamless integration with each other(Approved Makes: Axis, Bosch, Avigilon)
311Supply ,Installation of 32 mm PN 6 grade HDPE pipe as per IS:4984 with nylon rope for fiber / LAN cable / telephone / power cable laying inclusive of digging with the help of bogi & sand finishing, making the surface in good condition as approved by engineer in charge etc
312SITC of 17"" Screen for viewing for Storage of approved Makes: Lenovo, HP, Dell.
313SITC of 55"" Flat Smart Screen HD Profesional LED with remote control and wall mount unit / floor stand complete with making connections etc of approved Makes: LG, Samsung, Panasonic.
314Supply, Installation, Testing & Commissioning of Managed Layer-2 Intelligent Ethernet POE Switches providing 08 x 10/100/1000 Fast Ethernet POE ports- 67W or better  and 2 dual purpose uplink ports (provision for Copper / Fiber Giga connectivity) all switches & related Fiber modules should be of same make & category for seamless integration with each other of Approved Makes: Cisco Catalyst Series or Equivalent in  Avaya, Juniper )
315Supply, Installation, Testing & Commissioning of IP Phones along with Dual switched auto-sensing 10/100/1000 Mbps Ethernet ports with integrated BUILT-IN PoE+ to power the device and give it a network connection, 2 line keys with dual colour LED and 2 SIP accounts, LCD graphical display, 3 XML programmable context-sensitive soft keys,13 dedicated function keys for: MUTE, CONFERENCE, PHONEBOOK, MESSAGE, RECORD, HOME, TRANSFER, HOLD, HEADSET, MUTE, SEND/REDIAL, SPEAKERPHONE, VOL+, VOL;. Supports HD audio both on handset and full-duplex handsfree speakerphone and 3-way conference.UL & FCC/CE compliance of Approved Makes: Cisco, Alcatel, Grandstream
316Supply, Installation, Testing & Commissioning of IP Main console desk (Reception Phone) with Dual switched auto-sensing 10/100/1000 Mbps Ethernet ports with integrated PoE, 4.3 inch (480x272) TFT color LCD, 10 line keys with up to 5 SIP accounts, 5 XML programmable context sensitive softkeys, 5 navigation/menu keys, 9 dedicated function keys for:MESSAGE(with LED indicator), phonebook, transfer, conference, hold, headset, mute, send/redial, speakerphone, vol+, vol-; Call Hold, transfer, forward, call waiting, 3-way conference, call park, call pickup,off-hook auto dial, auto answer, click-to-dial, flexible dial plan, hot desking, personalized music ringtones and music on hold, integrated dual-band WiFi 802.11 a/b/g/n/ac (2.4Ghz & 5Ghz),handset and full-duplex handsfree speakerphone with wideband audio, User and administrator level passwords, MD5 & MD5-sess based authentication, AES based secure configuration file, SRTP, TLS, 802.1x media access control, UL & FCC/CE compliance of Approved Makes: Cisco, Alcatel, Grandstream
317Supply, Installation, Testing & Commissioning of extension module with 4.3 inch (272x480) TFT color LCD 20 per page (each module contains 2 pages, for up to 40 lines per module Combine up 4 daisy-chained modules for 160 contacts/extensions BLF, call park /pick-up, speed-dial, presence, intercom, voice conferencing transfer/forward and more UL & FCC/CE compliance of Approved Makes: Cisco, Alcatel, Grandstream
318Supply, Installation, Testing & Commissioning of IP PBXs appliance BOX with 500 Users Call Capacity along with 75 concurrent calls, upto 75 parties voice conference, inbuit 32GB Storage (for call recording), Network Interfaces : Three self-adaptive Gigabit ports (switched, routed or dual card mode) with PoE+, supports router mode and switch mode, Up to 5 layers of IVR (Interactive Voice Response). Call Features: Call park, call forward, call transfer, call waiting, caller ID, call record, call history, ringtone, IVR, music on hold, call routes, DID, DOD, DND, DISA, ring group, ring simultaneously, time schedule, PIN groups, call queue, pickup group, paging/intercom, voicemail, call wakeup, SCA, BLF, voicemail to email, fax to email, speed dial, call back, dial by name, emergency call, call follow me, blacklist/whitelist, voice conference, video conference, eventlist, feature codes, busy camp-on/ call completion, voice control. UL & FCC/CE compliance of Approved Makes: Cisco, Alcatel, Grandstream
319Supply, Installation, Testing & Commissioning of E1/T1 Digital VOIP Gateway BOX for digital PSTN & ISDN trunks to be integrated with IP PBXs with VoIP network with 30 concurrent calls with Dual Gigabit autosensing RJ45 network ports, TLs and SRTP security encrption technology to protect calls and accounts, supports a wide range of voice codecs including G.722, G.729 iLBC, USB and SD card interface peripheral ports. UL & FCC/CE complianceof Approved Makes: Cisco, Alcatel, Grandstream
320SITC of 5 KVA 1 Phase Input, 1 Phase Output advance DSP controlled UPS with IGBT based rectifier, LCD display, double conversion / Digital Signal Processing UPS, with isolation transformer, with 26Ahx x 16 nos SMF Batteries for min 30 min back up, with MS Rack for Barreries and required cabling for incoming & outgoing connection of approved Makes: Numeric, Eaton, Emerson, APC.
321Lift work
322SITC of Machine room less Gear less 13 PassengerElevator with4stops, Stainless steel Car, Stainless steel door,Stainless steellanding doors, with speed1.0 MPS, Centre opening,VVVF drive controller, ARD and other standard accessories etc. as per Terms & conditions & specifications attachedwith 5 year defect liability period.Make : Otis / Kone / Mitsubishi / Johnson / Thyssen Krupp / Omega / Schindler or Eql.make
323Airconditioner work
324Supply , Installation, Testing and Comissioning of IS:1475 marked self contained drinking water cooler withhermeticallysealed compressor,non CFC refrigerent suitable for operation on 230V/1pH/50Hz AC supply,Full stainless steel (SS304)body (0.8 mm thick)and tank (0.5 mm thick) , stainless steel water tray,minimum two nosBrass Chrome plated faucets and suitable drainage system complete in all respect with requiredheight MS fabricated and Painted Angle iron frame( Cost of frame to be paid Extra )complete in all respect of the following capacity.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
325cooling capacity 150 Ltr./Hr. and storage capacity 150 Ltrs
326Supply , Installation, Testing and Comissioning of Air Cooled Cassette typeAir conditioners complete with Indoor unit(IDU), Out door unit (ODU), R-32/R410A Green Refrigerant, wireless Remote, inbuilt drain pump, suitable for 400/230V, +/- 10% 50 Hz ,1 /3 phaseACsupply, apable of performing cooling, dehumidification,Air circulation, filteration & ventilation of following capacity with Scroll /rotary/twin rotary compressor. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
327Inverter Type
3283.0 TR
329Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping withfittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing,support with MS hanger on ceiling or recessed in wallwith chasing & plastering with 6 mmthickclosedcellelastomeric nitrile rubberinsulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
33025 mm
331Supply, Fixing and testing of following capacity ISO certified company made wall mounted stabilizer having output voltage variation from 200 V to 250 V(+/-5%) with input voltage variation from 170 V to 260 V, time delay facility from 2 to 4 minute and high cutoff at 270 V with providing of 16 Amp /20 Amp Industrialplug top making connection etc complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
3324 kVA
3335 kVA
334Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia
33550 mm dia per running inch length
336Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
337Supply & fixing MS powder coated stand suitable for 2.5/3.0/4.0 Tr outdoor type of Split/Ductable/Tower AC.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
338SITC of Interconnecting refrigerantcopper pipe forsplit/Ductable/ Casseette AC of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink MarkBrand Printing on Hard Tubes should be present. Piping between each set of indoor & outdoor units of different sizesas per OEM requirement & specifications including class "O" Nitrile rubber sleeves, chase cutting, supports, making good the same with sand cement plaster etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
339Supplying and drawing flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existingsurface or recessed PVC/ MS conduit/casing capping/ Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
340Un Armoured
3414 core x 2.5 Sq.mm
342Supply , Installation, Testing and Comissioning ofInverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and50 hz , single phaseACsupply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. Make- LG, Samsung, Daikin, Hitachi, O General, Blue star, Mithshibushi.
3430.8-1.0 TR ISEER not less then 4.6
3441.3-1.5 TR ISEER not less then 4.6
3451.8-2.0 TR ISEER not less then 4.6
346SITC of Desert Cooler(Ashoka /Voltas/ Symphonyfitted) cooling capacity 5000 cum/Hr. Cooler Size 28"X28"X38" fitted and tank size 9" height with 20" 1400 RPM Cooler fan motor(cool home/CG make) with three speed control fan motor and submercible pump melborne or eq. make)made of 18 SWG GI sheet for tank,front and top of 20 SWG GI sheet,Filter panel of 22 or better SWG,Grill of 22 or better SWG and Grill size 22"X24" complete as required.(Cooler will be fixed on existing stand)
347SITC ofRO water system with Filtration stage = Particulate filter-Membrane life enhancer filter - sediment filter - Pre carbon filter -RO Membrane filter - Post carbon filter,Input power Rating - 230 V AC , 50 HZ, Percentage of Rejection TDS - 90% or better having following Features (a) Double purification by RO with ESS or latest technology with TDS indicator (b).Spin welded RO Membrane Housing to prevent tempering (c). Push fit components for leak proof performance (d). Fully automatic operation with auto start and auto off (e). SS construction for corrosion free lifespan (f). Equally suitable for water from all bore wells,,overhead storage tanks,water tankers and even municipal taps (g) RO Membrane Flushing - Auto Flush @ Every Start , Every Stop and every One Hourof working for one minute. complete in all respect with following capacity. Approved Make:Eureka forbes, Kent, AU Smith, Ion Exchange, pentair.
348Purification capacity- 50 LPH,Duty Cycle 270-500 liters/day,
349Fire fighting and fire Detection work
350Supplying, Installation, Testing & Commissioning ofElectrical Driven fire fighting duty pump as per TAC andIS 12469-1988., Factory assembledin Pump make OEM for Sprinkler / Hydrant applications suitable for automatic operation and consisting of following details given asA, B, C, D, E, F, G and H.
351(A) End Suction / Horizontal Axially split casing volute type Single / Multi stage Centrifugal pump complete for delivery of below mentioned discharge and Head
352(B) Material of construction : Pump Casing - Cast Iron, Impellor- Bronze, Shaft - SS 410, Packing - Mechanical Seal
353(C)Pump shall be capable of furnishing not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head
354(D) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed 2900 / 1500 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect .
355( E)Common bed plate fabricated frommild steel channel for installation of pump and Motor including anti vibration pads.
356(F) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works inPhysical presence of Department’s representatives.
357(G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeveand Dynamic Balance certificate is to be submitted by OEM
358(H)Suitable size Reinforced cementconcrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
3591620 LPM suitable for 70 Mtr Head End Suction Back pull type Single Stage, 2900 RPM
360Supplying, Installation, Testing & Commissioning ofDiesel Engine Driven fire fighting duty pump as per TAC andIS 12469-1988., Factory assembledin Pump make OEM for Sprinkler / Hydrant applications suitable for automatic operation and consisting of following details given asA, B, C, D, E, F, G and H.
361(A) End Suction / Horizontal Axially split casing volute type Single / Multi stage Centrifugal pump complete for delivery of below mentioned discharge and Head
362(B) Material of construction : Pump Casing - Cast Iron, Impellor- Bronze, Shaft - SS 410, Packing - Mechanical Seal
363(C)Pump shall be capable of furnishing not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head
364(D) Heat Exchanger cooled Diesel Engineas per NFPA 20 developing suitable BHP for the below mentioned dischargeat 1500 / 1800 RPM, flexible coupling and coupling guard with the Pump, common bed plate for mounting of the Engine and Pump,Antivibration damping arrangement by cushy foot, Diesel Engine starting Panel for starting of the engine automatically if the Normal electrical supply fails with a unit of battery bank of 12/24v,180 Ah, Lead Acid Battery with Boost / Trickle charger as required for operation of Diesel engine, Exhaust Pipe of suitable diameter upto 10 M length (with LRB insulation & Alum. Cladding), with muffler, Diesel tank of 300 Lts capacity (made out from 2 mm thick MS sheet with filling Cap) with drain cock, Diesel level Indicator, Suitable MS angle iron stand for placing tank, first Filling of Diesel tank.
365(E) Diesel Engine Control comprising Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication, Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0- 20 A DC Ammeter, All standard relays and accessories for automatic operation of diesel engine System Controller in Existing Fire Fighting Control panel
366(F) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Physical presence of Department’s representatives.
367(G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeveand Dynamic Balance certificate is to be submitted by OEM
368(H) Pump to be placed on Suitable size Existing Reinforced cementconcrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
3691620 LPM suitable for 70 Mtr Head End Suction Back pull type Single Stage, 1800 / 2300 RPM
370Supplying, Installation, Testing & Commissioning ofElectrical Driven fire fighting duty Jockey pump as per TAC andIS 12469-1988., Factory assembledin Pump make OEMsuitable for automatic operation and consisting of following details given asA, B, C, D, E,F and G
371(A) Horizontal End suction Single / Multi Stage Centrifugal Back pull type pump complete for delivery of below mentioned discharge and Head
372(B) Material of construction : Pump Casing - Cast Iron, Impellor- Bronze, Shaft - SS 410, Packing - Mechanical Seal
373(C) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed not Exceeding 2900 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect .
374(D)Common bed plate fabricated frommild steel channel for installation of pump and Motor including anti vibration pads.
375(E) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Virtual / Physical presence of Department’s representatives.
376(F) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeveand Dynamic Balance certificate is to be submitted by OEM
377(G)Suitable size Reinforced cementconcrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ) All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
378180 LPM suitable for 70 Mtr Single Stage
379SITC of pressure switches ofpressure range 3 to 15 Bar for Main, Jockey, Terrace pumpandDiesel pumps, Etc. as Required ( Control Cable from Pressure switch to Panel to be Paid Extra ). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
380SITC of UL listed and FM Approved Polyethelene vane type water flow switch with actuation & delay mechanism for sensitivity in the range of 4 to 10 GPM and suitable for installation in following sizes of Sprinkler pipe for a Staticpressure rating up to 250 PSIin cluding making connections, making hole in pipe for inserting the vane etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
381150 mm Dia.
382Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS "C " class (Heavy) pipes conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applicationsincluding cutting, screwing, welding etc. & forged steel fittings like elbows, tees, tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger and nuts bolts including cutting hole and chase in brick or RCC walls/ slab and making good the same. complete with painting of one coats of Red Oxide and two or more coats of synthetic enamel paint of requiredshade complete as required. (Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs.). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
38325 mm dia
38432 mm dia
38540mm dia
38650mm dia
38765 mm dia
38880 mm dia
389100 mm dia
390150 mm dia
391200 mm dia, 6.0 mm thick
392250 mm dia, 6.35 mm thick
393Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS "C" class (Heavy) pipe conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applications in Existing trench with cement concrete block as supportsincluding cutting,welding etc & forged steel fittings like elbows, tees,tapers, reducer with cleaning,wrapping and coating of the pipe with 4 mm thick tar based polymaric corrosion protection tape including applying uniform coat of cold pipekot primer as per IS; 10221 for protection against corrosion complete in all respect. ( Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs. & Excavation of Trench and refilling of trench to be paid extra). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
394150 mm dia
395Supplying and fixing cylindrical air vessel of continuous welded construction for pump room made of 450 mm dia,fabricated out of 10 mm thick dished ends and 8 mm thick MS sheet, 2000 mm in height withflanged connection,Provision for25 mm dia drain valve,air release valve,safety valve pressure gauge as required accessories and painting with two coats of Red Oxide and two coat of post office red enamel paint including The tank shall be installed on suitable vertical legs. The legs shall be provided with M.S. Angle of size 75 mm x 75 mm x 5 mm at the bottom. The legs shall be grouted in cement concrete foundation. as required. ( Air Release valve, Drain valve, PRV, Pressure Gauge shall be Paid Extra ). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
396Supplying and fixing cylindrical air vessel of continuous welded constructionfixed at riser top made of 250 mm dia, fabricated out of 8 mm thick MS sheet, 1200 mm in height withflanged connection, Provision for25 mm dia drain valve,air release valve,safety valve pressure gauge as required accessories and painting with two coats of Red Oxide and two coat of post office red enamel paint including The tank shall be installed on suitable vertical legs. The legs shall be provided with M.S. Angle of size 75 mm x 75 mm x 5 mm at the bottom. The legs shall be grouted in cement concrete foundation. as required. ( Air Release valve, Drain valve, PRV, Pressure Gauge shall be Paid Extra ). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
397Supplying and Fixing of PN 16 Flanged Y strainer fabricated out of cast iron body, SS 304 strainer with perforated screen with 3 mm. dia holesin existing MS / GI pipe complete with 2 no. Matching Flanges (Minimum 16 mm thick),nuts, bolts, washers, gaskets etc as required of following sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
398150 mm dia
399200 mm dia
400Supplying and Fixing of PN 16 Cast Iron Dual Plate Wafer Type Check Valve / Non return valve with SS / Bronze flap complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets,etc as required of following sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
401100 mm dia
402150 mmdia
403Supplying and Fixing of PN 1.6Butterfly Valve (Wafer Type) with S.G Iron Disc and confirming to IS:13095 complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets,etc as required of following sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
40450mm dia
40580 mm dia
406100mmdia
407150mm dia
408200mm dia Gear Operated
409Supplying and fixing of SS 304 Single / Double headed oblique pattern hydrant landing valve (internal/external) with 75 / 100 mm dia flanged inlet & 63 mm dia instantaneous type female outlet coupling with cast iron wheel complete with ABS cap and chain and all accessories as per IS:5290-93 (Type-A) in cluding matching flange (14 mm thick),nuts, bolts, washers, gaskets,etc as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
410Single Headed with 75 mm Dia. Flanged Inlet
411Supplying and fixing of flexible hose made with 100% polyester, black EPDM internal rubber lining with External coat of synthetic elastomer (IS:636, type-A)63 mm dia, 15 mtr. Long RRL hose pipe with instanteneous type 63 mm dia SS-304male and female couplings(IS:903) duly bound and riveted to hose pipes with copper rivets and SS wire etc. as required.Appropriate Test Certificate/ report with liable warranty of product/accessories from OEM shall be submitted.
412Supplying & fixing SS-304 Short Branch Pipeconforming to IS: 903:93 fitted with 20mm (nominal internal diameter)bore nozzle, for projecting water in form of solid jet. The Branch shall have 63mm Male Instantaneous Inlet, suitable for use with 63 mm size Fire fighting hoses. H.P. tested to 21 kgf/cm² for 2.5 minutes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
413Supplying and fixing first -Aid Fire hose reel Drum wall mounted swinging type with MS construction powder painted in post office Red, conforming to IS 884-1985 with upto date amendments, complete with the following as required.(A) Thermoplastic / Rubber Hose(B)20 mmdia UL, FM Bronze / SS nozzle with 5mm orifice (C)Drum and brackets for fixing the equipments on wall.(D) Connections from riser with 20/25 mm dia Brass/GM gate valves with screwed end and conforming to IS:778 Class-1through Forged steel Screwed Union & M.S. pipe. Etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
414With 30 m x 20 mm Thermoplastic hose as per IS:12585 Type-2 and Bursting pressure 42 Kg/sqcm
415Supplying and fixing of 750 mm x 600 mm x 250 mm Outdoor application Fire Hose Cabinet made of 1.6 mm thick MS sheetDuly powder coated in red color externally and white internally with 6 mm thick glazeddoors with Expanded Metal 2 mm thick Jali including necessary locking arrangement suitable to accommodate 2 Nos 15 Mtr. Long RRL Hose and 1 No. branch pipe on Existing Wall / Angle Iron Frame as required. (Cost of MS structure for mounting Frame is to be Paid Extra) All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
416Providing and Fixing of 15 mm dia Bronze quartzoid bulb type sprinkler headswith Maximum working pressure 11.6 Kg / Sqcm and suitable for 68 degree centigrade rating standard response (UL Listed) chrome plated complete in all respect of the following type. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
417Pendant/ Upright type
418Supply & Fixing of Fire Man"s Axe with carbon steel head & rubber moulde handel usable upto 20 KV and confirming to IS :926 with length approx 0.4 M & weight 3.0 Kg. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
419Providing & fixing Stainless Steel pressure gauge with dial of 150 mm dia size and range 0 to 20 kg/sq.cmwith 3 / 8 " BSP bottom entry , Ball valve , SS Syphon tube all fittings etc, dulycalibrated before installation in MKS and FPS units, Accuracy Level +/- 1% including Making Drilling in Existing MS PipeEtc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
420Supply & Fixing of Water + AFFF 6%Mechanical Foam typeFire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 25 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
421Capacity - 9 Ltrs.
422Supply & Fixing of CO2 type Fire Extinguisher conforming to IS:15683:2018, charged with CO2 gas (purity 99.7% conforming to IS 15222), Powder coated Internal & External Surface Manganese steel ISI marked as per IS 7285 cylinder body , Wheel type Forged brass release valve ISI Marked as per IS 3224 with Inbuilt safety release device ((Fusible plug and Rupture Disc Type), 1.0 Mtr. Metal wire braided hose having minimum bursting pressure of 140 Kgf/cm2, Horn with metallic thread connection, QR code for Product Traceability,including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
423Capacity 4.5 Kg.
424Supply & Fixing of Dry Powder Agent (as per IS 4308:2019), ABC typeFire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 28 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
4254 kg
426S&F following sizes (dia.) of ISI marked ( IS:9537 P - II ) rigid steel conduit with wall thickness according to IS Specified along withISI marked (IS:14768 P-II 2003) accessories inrecessed using saddles, clamps, fasteners, pvc bushes, check nuts, as required includingcutting jhiris in the wall and making good the same as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
42720 mm
428Supply & Installation of IP-20 & IK-08 , UL Listed Communication enclosure (Rack) made from powder coated (60 to 80 Micron) CRCA sheet,Vertical Mounting Rail 1.6 MM with "U"Marking, front sturdy sheet steel frame folded from one piece and welded with 5mm toughened glass door, with All round protective channel on the door aperture, lock integrated on front door, top and bottom cover with cable entry provision with gland plates, integrated side walls, Set of 75 mm height 4 castors, 2 of which have brakes, Accessories like: 5 Nos of 19" 1U Horizontal Cable manager, 2 Nos of vertical cable managers, 1 no. Keyboard Tray,4 Nos of 90 cfm 230V AC Fan with 1 mts long cable, mounting hardware , 2 No of 19" 1U, mountable socket strips with 6 nos of 5A universal sockets with 2 mts long power chord for supplying power to switches, fans etc along with earth continuity kit, indicator, moulded power supply cable complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
42922 U Rack with Width 600 mm &Depth 800 mm
430Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,in existingsurface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
4312 x 1.5 sq.mm
432SITC of UL 10th edition / EN54 / VDS certifiedAutomatic Floating Sensitivity type Analog addressable Multi criteria (two optical/Smoke sensor to reduce false alarm) detector with mounting base & LED etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
433SITC of UL 10th edition / EN54 / VDS certified Addressable type fault isolator with base for isolating shorted, dewired and loose circuits between two successive fault, isolators with automatic resetting arrangementetc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
434SITC of UL 10th edition / EN54 / VDS certified Addessable Manual Call point (MCP) with LED/ FIRE Indication Etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
435SITC of UL 10th edition / EN54 / VDS certified Addressable sounder with strobe light,Loop Powered / Direct powered from FACP with sound level 90 dB and programmablefrom the panel etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
436SITC of UL 10th edition / EN54 / VDS certified Addressable control (input/output) modules/ Relay Module for shutting down lifts, Hooters, AHU"s, Acknoledgement of Sprinkler system with potential free contact monitoring Etc. as Required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
437SITC of UL 10th edition / EN54 / VDS certified Microprocessor based inteligent, Analogue addressable,modular, expandable networkableloop Fire Alarm Control Panel with each loop capacity of min 125 detectors per loop with total of 125 detectors & devices with Loop length up to 1 KM as per NFPA 72 approval. The Panel shall be able to give pin point location of addressable units via the address code for each unit. The Panel shall also be able to automatically switch off all control switches when-ever any Alarm is triggered. . The panel shall have 230 + 5 % volts power supply, Automatic battery charger 24V, sealed lead acid maintanence free battries sufficient for 24 hours normal working and then be capable of operating the system for 30 minutes during emergency condtion. Loop interface cards, communication module,LCD/LED unit to indicate Fire / Fault Signal of individual unit,inbuilt networking port(both RS485&Ethernet),Serial port for printer,two supervisory inputs,two position key switch and USB port for programming.including the cost of all accessories Etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
4382 - Loop
439SITC of UL 10th edition / EN54 / VDS certified6 ZONE Digital Voice Command Center withFACP, it shall contain all equipment required for all audio control, signaling and supervisory functions. This shall include speaker zone indication and control, digital voice units, microphone etc. The Digital Voice Command Center shall have digital voice call station suitable for 6 zone, digital voice controller & router suitable for 6 zone, 4 nos 240 watt & 1no 480 watt amplifier& digital amplifier capable for 1440 watt load etc.including the cost of all accessories Etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
440Providing, fixing, testing & commissioning of resilient rubber lined single arch vibration eliminators suitable for raw water up to 45 deg. C temperature, working pressure 8.8 Kg/cm2 and test pressure 14 Kg/cm2 to provide relief from stresses at pipe flanges.It should be complete as per manufacturer"s specifications & as directed by Engineer- in-charge
441200 mm dia
442150 mm dia
443100 mm dia
444Providing & Fixing, of SS Fire brigade inlet connection (Suction collecting head) consisting of 4 nos 63 mm instantaneous type male coupling with built-in check valve and 150 mm dia flanged outlet complete with bolts,nuts and rubber insertions as per IS:904-1983 of as per approved
445Providing & fixing SS fire brigade suction hose coupling (draw-out connection) with nut for female coupling as per IS standards complete with 100 mm dia GI suction pipe and 100 mm dia foot valve (to be connected to static tank) of as per approved
446Providing and fixing 4Kg Halotron™ I (Clean Agent) Type Fire Extinguisher. pressurized with Argon gas at 15 bar. Design, construction and testing as per IS 15683 with Fire rating 1A 13B, Body Hydrotested at 35 bar, Operating temperature -30°C to +55°C, external epoxy powder coating with PO Red Shade No. 538 of IS 5, Supplied with standard accessories. and wall suspension bracketsas per approved
447Supplying and installingfire bucket stand including sheet metal (16 gauge) shade, platform and associated civil works each stand should have four nos fire buckets of 24 gauge galvanized steel sheet, standard 9 litre capacity and of round bottom shape, painted white inside and red outside and black on the bottom, inscribed with letters "Fire" in black and gold & one no fire man"s axe at approved locationas per approved make.
448Supply of strong rope ladder made from 18-20 mm dia Nylone/Polypropylene (PP) rope,with 20-25 mm solid wooden/aluminium rung of length 330-370 mm and span of 370-450 mm and loading capacity of 500 kg and loading of rung with 200 kg of following length and of approved make.
44930 meter
450Supply and fixing ISI marked (IS: 15683) Mono Amonia Phasphate (MAP 90)ABC type modular Fire Exitnguisher, finished externally with red enamel paint,complete in all respect incluing initial fil,Sprinkler head and ceiling suspension of following capacity
4515 ltr.
452SITC offloor mounted dust and vermin proof compartmentalisedcubical type main fire pump house panel made out of CRCA sheet , required hardware,duly treated for derusting in 7 tank process with dephosphating and with powder coating on both side of panel in desired shadeThe panel having PU/ Neoprene rubber gasket of not less than 3mm thickness , separate detachable gland plate M.S. base channel ,hinged door with locking arrangement for equipment/switchgear. Thickness of sheet shallnot be less than 1.6 mm up to 600 mm length / widthof any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall beof 2.0 mmthick sheet supported by base M.S. channel if required . Side walls and cable alley compartments having bolted type doors and having accessories ( Group -I ) as below:
453Incomer
454320 Amp. TPN MCCB (adj.O/L) with Extended ROM, 35 kA, with Thermal magnetic release,Digital Ammeter, Voltmeter, Selector switches,CT, Indicating Lamps, 400 AmpsAlum. Bus bar with with heat shrinkable sleeves.
455Out going
456(a) 200 Amp. TPN MCCB(adj.O/L) with Extended ROM, 35 kA, with Thermal magnetic release, Digital Ammeter, Voltmeter, Selector switches,CT, Indicating Lamps for "ON", "OFF", "TRIP" 1 no. star Delta Starter of 75 HP with thermal over load relay, timer, push buttons, Auto / Manual selector switch, Single phase preventor - 2 Sets
457(b) 63 Amp. TPN MCCB (adj.O/L) with Extended ROM, 25 kA, with Thermal magnetic release, Digital Ammeter, Voltmeter, Selector switches, CT, Indicating Lamps for "ON", "OFF", "TRIP" 1 no. Star Delta / DOL Starter of5 - 15 HP with thermal over load relay, timer, push buttons, Auto / Manual selector switch, Single phase preventor - 1 Set
458© One no. Diesel Engine Auto Starting kit with Auto . Manual selector switch & 3 attempt starting device, timers, relays, Indicating lamp for High / Low Lub. Oil pressure, High water temperature and engine ON indication, Battery charger, suitable for 12 V / 24 V DC with trickle / boost selector switch, DC ammeter & voltmeter
459(d) System controller to control Operation Main Electric pumps, Diesel pump, jockey pump in sequence as per specs. Consisting of relays, timers, sensors, annuciation window for fault indication.
460Supplying, Installing, Testing and Commissioning of speaker for PA system (Approved
4616-8 Watts metal body ceiling mounted speakers
462Supply, laying and commissioning of PVC insulated and PVC sheathed , 2 core shieldedflexible copper wire of size 1.5mm, in existing Surface /recessed conduits ,Cable race ways, Trenches including cost of excavation and refilling, existing Pipes etc using all saddles, clamps, fasteners glands, lugs Approved Makes: Finolex, RR Cables, Deepcab
463Solar System work
464Supplying , installation , Testing and commissioning of grid connected SPV power plant in accordance with latest MNRE approved ALMM List specifications and BISstandards approvals with free comprehensive maintenance for 5 years as per following details
465(a)SITC of MNRE specifications and ALMM Approved Mono Perc standard IP-65 SPV modules of followingcapacity with minimum rating of each module 445 Wp with equal no. of module to be in each series circuit . PV module made out from min.135 nos Mono Perc solar cells and frame made out from Anodized Allunimium alloy 35mm or better with hot dippedgalvanized steelmounting super structure , civil structure , lightning and over volage protection , earthing protection as per specification as required for making the solar system functional complete in all respect as required.
466(b) SITC of IP-65 rating wall/floor mountedstring inverter 3 phase, low maintenance , full sine wave ,50 Hz AC out put with grid tied features along with all protection , controlling arrangement and required accessories of following capacity .The inverter AC nominal power output rating must be equal or greater than the required KWp of the module at standard test condition(STC) and as per MNRE specification.The inverter unit shall be suitable for indoor and outdoor installations including all DC/Acplugs and socket , D.B."s and with all necessary electricalDC solar cables between modules and invertersand ac cables from inverter to AC panel ( Any length as required )&lugs and terminations with solar metering and net Metering, conduits and cable trays and all other material and workmanship required to connect with main distribution panel as per the direction of engineer - in- charge.
46760.0 KW capacity
468NOTE - SOLAR WORK BIDDER SHOULD UPLOAD MANUFACTURER"S AUTHORIZATION CERTICATE OFOEMWITH CONFIRMATION OF 5 YEAR WARRANTY
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail