| 1 | Supply and fix in repairs on load change over switch existing panel, wall or LT pole of any size and , triple pole and neutral, 400 Amps, 415 V, 50 Hz front handle operated, including connecting and testing all as directed. |
| 2 | Supply and fixing in existing panel board for replacement MCCB, 4 Pole, 400 Amps , with breaking capacity 36 KA , fixedtype(HBC Series),adjustable typethermal setting 70-100% and magnetic adjustable 5-10 times AC 415 volt ,50 HZ conforming to IEC:60947-II/IS:13947-II and connectingall as directed. |
| 3 | All as per item No 2 here in above but 200 Amps 36 KA breaking capacity. |
| 4 | Material and labour for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6.0 mm thick, buried verticallyin ground (Each pit not less than 2.25 mtrs deep below normal ground level with top edge of plate not less than 1.50 M below normal ground level) connected to GI strip 32 x 6 mm , by means of bolts, nuts, and check nuts and washers etc encased in GI protection pipe 40 mm dia light grade pipe for protection of GI earth strip both to be provided to the extet of 7.5 meters, all as shown on electrical plate No 3 of MES SSR - 2009 Part - I, GI protection pipe buried in ground, laid under floors / plinths or mixed on walls / pole etc or concealed in walls etc; with provision of mixture of charcoal dust and common salt packed upto minimum 150 mm all around the earth plate, including PCC 1:2:4 type B-1 earth pit with M.S angle iron frame, cast iron cover with locking arrangement, with GI 20 mm dia medium grade pipe and MS funnel with wire mesh for watering arrangement, including necessary excavation and earth work in any type of soil / strata and testing on completion complete all as specified and directed.Note:- i) Cost of GI strip 32 x 6 mm and protection pipe 40 mm dia is deemmed to be included in rate quoted ii) Excavation and returning filling of Soil any type is deemed to be included in rates. |
| 5 | S&F in replcement ofvertical type air break switch, gang operated, tripple pole, mechnically operated, outdoor type, with all fittings and accessories mounted on andincluding HT 11 KV porcelain insulators and steel channel frame, GI operating rod 25 mm dia of suitable length to worked from ground, including locking arrangements , suitable for 11000 volts, 400 Amps current rating complete including dismantling existing one all as specified and as directed. |
| 6 | S&F drop out fuse unit, explusion type for out door air break gang oprated switch, single pole mounted on and including insulators for 11 KV working pressure fixed to and including MS channel with nuts, bolts and washer etc synthetic bounded fuse tube complete with line capcity suitable for current carrying capacity upto 100 Amps all as directed including taking down old one all as specified and as directed |
| 7 | S&F in replacement of HT 11 KV out door non-linear type lightening arrestor with mountings, accessories complete fixed on cross arms of two pole structure /GI flat strip and connect with same size of ACSR conductor encashed in PVC alkathine pipe with all fittings connected to earth strip with nuts, bolts and washers, transmission class having discharge capacity of 10 KAand suitable for working pressure 9 KV RMS compelete including taking down old lightning arrestor all as specified and as directed including dismantling existing one all as specified and as directed. |
| 8 | M&L for cable jointing kit for 11 KV grade cable for straight through heat shrinkable joint suitable for XLPE armoured aluminium conductor cable of size 3 core 95 Sqmm all as specified and directed. |
| 9 | M&L for cable jointing kit for 11 KV grade cable for straight through heat shrinkable joint suitable for XLPE armoured aluminium conductor cable of size 3 core 120 to 185 Sqmm all as specified and directed. |
| 10 | M&L for end termination cable jointing kit for 11 KV grade cable heat shrinkable joint, out doorsuitable for XLPE armoured aluminium conductor cable complete with jointing materials and accessories suitable for3 core 120 to 185Sqmm all as specified and directed. |
| 11 | M&L for end termination cable jointing kit for 11 KV grade cable heat shrinkable joint, out doorsuitable for XLPE armoured aluminium conductor cable complete with jointing materials and accessories suitable for3 core 95Sqmm all as specified and directed. |
| 12 | Supply, erecting and fixing in true vertical position of steel tubular swaged pole, 11 mtr long complete with cast iron base plate, finial taper plug, bolt, nuts and screws as specified and of type 410 SP-55, conforming to relevant IS, including one primer coat of red oxide and two coats of aluminium paint and two coats of bituminous paint inside and outside of botton portion up to 1.8 mtr length all as specified and provide circular bend 1 No of width 2 cm complete all as specified and directed. (Excavation and earth work , foundation concrete and PCC coping shall be measured and paid separately) |
| 13 | M&L for cement concrete (1:4:8 ) type D2 using graded stone aggregate as in foundation for pole including necessary form work all as specified & directed. |
| 14 | M&L cement concrete (1:3:6 ) type C1 using graded stone aggregate as in foundation for pole including necessary form work all as specified & directed. |
| 15 | M & L for PCC(1:2:4) type C-2 using 20mm grade stone aggregates for coping including necessary form work and similar work all as specified and directed. |
| 16 | Demolation of u/s cement concrete in coppings etc complete all as specified and directed by Engineer-in-Charge. |
| 17 | Repair / Overhauling of air break switch by replacing stationary and moving contacts, flexible copper chord, GI nuts, bolts etc including alingment for smooth functioning from ground level all as required at site and all as specified & directed. |
| 18 | Decanning the transformer oil from leaking transformer by opening the stop valve.Checking for leakages, arresting the leakages, replacing cork sheet gasket 5 mm thick,bushing,washer, HV/LV Road,tapchanger gasket, reassembling the transformer completely refilling transformer oil, connecting HT / LT connection complete all as directed.NOTE:(i)Spares required shall be measured and paid separately under relevant items.(ii) Topping of transformer oil will be measured and paid separately. (iii) Gasket, cork sheet,washers are deemed to be included in the quoted rates. |
| 19 | Material only in replacement of silica gel including cleaning the breatherall as directed. |
| 20 | S & Freplacement, breather assembley with silica gel all as directed |
| 21 | S & F replacement of HT bushing, porcelain vitreous brown body suitable for 11 KV as per IS 334 all as per directed. |
| 22 | S & F in replacement of LT bushing, porcelain vitreous brown body 1100 V grade as per IS 3347 all as directed. |
| 23 | Supply& Fixin replacement of HV rod, brass, 12 mm dia, 300 mm longwith brass nut, 2 Nos and washers complete all as directed. |
| 24 | Supply and fixin replacement ofLV rod, brass, 15 mm dia, 300 mm longwith brass nut 2 Nos and washers complete all as directed. |
| 25 | M & L for taking down carefully transformer of following capacity, any make, any type from pole / plinth/ base, disconnecting HT & LT side connections, earthing strip of transformer, supporting angles, cross arm, shifting / transporting transformer carefully from the site to theworkshop minimum 30 Kms from site opening the top cover of the transformer, bushing,removing the tap changer, conservator,breather assembly, draining of oil from the transformer, lifting thecore complete taking out defective coils from the core, cleaning the tank and reassembling the transformer after carrying out the repairs/replacement of worn out part, ovening the complete unit till to get desired megger value, transporting returning back to the site installing re-commissioning and testing of the transformer at its original place, connecting up HT & LT sides, earthings, supports / cross arms etc all as directed by EICNote : (i)Spares, Rewinding of transformer ifwill be measured and paid separately under respectiveitems .(ii) Reinsulation & heating of coil is including of quoted rate.(iii) Insulating oil will be measured and paid separately.(iv) Painting of transformer is including of quoted rates |
| 26 | All as per item No 25 above but Transformer of capacity 50/100KVA |
| 27 | All as per item No 25 above but Transformer of capacity 200/250 KVA |
| 28 | All as per item No 25 above but Transformer of capacity 300/315 KVA |
| 29 | All as per item No 25 above but Transformer of capacity 400/500 KVA |
| 30 | Rewinding of old/burnt out coils of transformer by super enamelled copper winding wire/strips of appropriate size of superior quality including insulating, varnishing, heating, coil in position and charging completely all as directed in Engr-in-Charge. |
| 31 | Rewinding of old/burnt out coils of transformer by super enamelled Aluminium winding wire/strips of appropriate size of superior quality including insulating, varnishing, heating, coil in position and charging completely all as directed in Engr-in-Charge. |
| 32 | Supply & filling new insulating oil conforming to IS 335 for transformer etc all as specified and directed |
| 33 | Labour only for dehydration filtration and cleaning of transformer oil of 33 KV / 11KV power transformer/ distribution transformer / HT switchgear till achievement of die-electric-strength of 56 KV for new insulating oil and 45 KV for existing oil at 2.5MM Gapincluding testing of existing oil die eletric strength after and before withoil testing instrument including test report complete all as specified and directed Note : Toping of Transformer oil shall be measured and paid separately External Eletric supply/vehical mounted DG supplyrequired at the time of dehydration should be responsibility of contractor rate included in quated rate. |
| 34 | Excavation in trenches not exc 1.5 meter wide and not exc. 1.5 mtr in depth for laying of under ground cable, pole foundation and stays etc and getting out in soft / loose soil all as specified and as directed |
| 35 | Returning and filling in, including spreading and levelling, water and well remming in layers not exc. 25cm all as specified and directed. |
| 36 | Removing excavated soil to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point all as specified and directed. |
| 37 | Supply, laying, testing & commissioning of HT 11 KV (Earthed) XLPE insulated screened PVC bedded, electric power cable (heavy duty) ISI markedwith aluminium conductor 11000 volts grade,circular screened with extruded semi conducting compound in combination with copper tape , inner sheath of PVC tape galvanized steel strip flat , around and overall PVC sheathed, armoured conforming to IS 7098 Part II, 1985 amended upto date, of size 3 core 95 Sqmm, ISI marked, laid in trenches or passing through pipes/ducts including taking down old cable of any size all as specified and as directed. |
| 38 | Supply, laying, testing & commissioning of HT 11 KV (Earthed) XLPE insulated screened PVC bedded, electric power cable (heavy duty)ISI marked with aluminium conductor 11000 volts grade,circular screened with extruded semi conducting compound in combination with copper tape , inner sheath of PVC tape galvanized steel strip flat , around and overall PVC sheathed, armoured conforming to IS 7098 Part II, 1985 amended upto date, of size 3 core 120 Sqmm, ISI marked, laid in trenches or passing through pipes/ducts including taking down old cable of any size all as specified and as directed. Note for item no 37 & 38 : (i) Excavation and earthwork , sand cushioning , GI pipe, cable protection will be measured and paid for separately(ii) Cable shall be tested at high voltage test before & after laying.(iii) No straight through joint will be permitted inside pipe or duct.(iv) Cost of straight through if any deemed to be included in cost of cable. |
| 39 | Supply & laying of heavy dutyHDPE DWC pipefor HT cablepipe ISI marked of outer dia 110 mm and Inner dia 95 mm polythylenewith smooth internal and external surface for non pressure under ground cable icluding coupler and bends complete all as specified and directed |
| 40 | M & L for painting of Street light poles of any type (with hydrolic vehicle / ladder) including cross arms, channel, flat iron clamps etc 11 mtr longin two coats of aluminium paint and one coat of red oxide as primer including writing of pole nos (Yellow circle and Number in black) and providing 3 Nos of radium with width 50 mm size band / strap with Red, Yellow, Green colour 300 mm apart from plinth block around the pole etc complete as all as specified and directed in Engr-in- Charge.Note:- Hydrolic Vehicle / Ladder for painting is responsibility of contractor and rate of Hydrolic vehicle and ladder including in quoted rate. |
| 41 | Material and labour for spray painting of4 Pole structurewith two coats ofsynthetic enamel paint including channel,bracket of 4pole structure , prepartion of surfaces,Scraping the old paint and writingpole No in Black letter under yellow circle all as directed. |
| 42 | M&L for pin type, porcelain, vitreous, brown or green insulator including one galvanised mild steel spindle, steel washers and one galvanised nut of size 150mm height, 150mm dia for 11000 volts grade complete all as specified & directed. |
| 43 | M& L for disc type, pocelien, vitreous, white or brown 145mm hieght, 255 mm dia ball and socket type complete with tension assembly clamps for conductor for 11000 volts grade single disc assembly complete all as specified & directed. |
| 44 | Supply and stringing HT 11 KVACSR conductor (Weasel/ Ferret) for over head line securing on pole complete including binding wire, jointing sleeves aluminium tap and PG clamp etc of any size including dismantling all as specified and as directed. Note :- (a) jumper on cutout point/2 pole structer/4 pole structure shall be provided with PVC insulated sleeve. (b) Rate is inclusive of jumper & tree branch cutting to make a safe distance from over head line. |
| 45 | M&L for restringing of LT over head line consisting of 4/5 conductors by dismantling taking down, repairing wherever required including cutting, re-joining and restringing in situ, with proper sag, binding to insulator with and including aluminium binding wire complete all as specified and directed |
| 46 | M&L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, botls, washers, welding bending cold or hot, drilling holes for bolts, in any shape or size as indicated or irected and inclusive of one coat of red oxide primer, one under coat and one inishing coat of aluminium paintincluding dismantling all as specified and as directed. |
| 47 | S&F stay assembly complete with accessories as shown in Electrical Plate No 1 of SSR 2009 (Part I) using stay rod 20mm dia, including clamps made out of 50 x 6mm MS flat, MS galvansied stay plate 300mmx 300mm x 6mm and galvanised thimble including insulator 90x140mm including dismantling all as specified and as directed. (loop type insulator, stay clamps, excavation and concrete shall be measured and paid separately |
| 48 | M&L for prunning and removing of tree branches touching to electric over head lines wild growth around LT /HT over head lines and around pole and stay complete to make clear span of 1.5 Mtr of tree both sideof the OH line with JCB, Cutter and all tools, plants etc all as directed by Engineer-in-ChiefNote :(i) Distance between pole to pole will be measured and paid. (ii) Any breakdown of line caused during prunning shall be made good without any extra cost. (ii) Prunning of tree to be done twice a year (before & after rainy season) (iii) The contractor has to ensure the proper safety of the tradesmans to avoid any mishappening.If any mishappening occures the contractor will be solely responsible for it. |
| 49 | Supply and spreading in electrical outdoor installation yard, stone aggregate of size 20 mm at 11KV substations / Near DP structures after through cleaning, anti grass treatment etc all as specified and as directed. |
| 50 | Supply and spreading in electrical outdoor installation yard, stone aggregate of size 40 mm at 11KV substations / Near DP structures after through cleaning, anti grass treatment etc all as specified and as directed. |
| 51 | Supplying and laying factory made unreinforced precast concrete cable cover ISI marked, class HV, type 1, flat of size 300 mm x 180 mm x 40 mm duly embossed with \"HT CABLE 11 KV\", laid lengthwise perpendicular to the axis of cable including pcc foundation(1:3:6)complete all as specified and as directed. |
| 52 | Material and labour for spray painting the 11 KV transformerupto 250 KVA capacitywith two coats ofsynthetic enamel paint including prepartion of surfaces,Scraping the old paint and writingSM MES No in Black letter all as directed. |
| 53 | Supply,installation,testing and commissioining factory made LT feeder pillar panel CPRI approved, size of panel as per CPRI Specification,double door floor mounted outdoor type,as per IP-65 grade,made out of CRCA sheet 3.15 mm thick of outer bodywith Aluminium bus bar 600 Amps,4 strip,(3 phase & Neutral) complete drilled,insulated with colour coaded insulation tape,mounted on insulators etc. Panel should be dust proof,vermin proof,powder coated,locking should be screw type,mechanical type,inter locking,should have danger noticefor 415 volt,AC,mounted on 50 x50 x6 mm angle iron frame having minimum 2 feet ground clearanceduly embedded in and including PCC block(1:2:4) type B1 foundation for fixing of panel complete including ternination of all incoming and outgoing cables with suitable size thimbles/lugs, glands , Nuts & Bolts complete all as required and directed. (santoshi line) |
| 54 | Incoming : - (i) MCCB 400 Amp adjustable type with , 4 Pole, 36 KA - 01 No.(Ics=100%Icu)(ii) Volt meter 0 to 500 Volts,Square flush pattern, digital type with CTs – 01 No (iii) Amp meter square flush pattern 0 to 400 Amps digital type with CTs -01 No. (iv) Indicating lamp LED type one set in incoming phases.(v) Internal wiring with PVC insulated copper conductor multi stranded cable 1100 Volt grade IS 694 marked of appropriate gauge including all copper lugs(vi) Connection from MCCB to Busbar shall be of solid Aluminium conductor(vii) MCCB shall be provided with suitable spreader of aluminium conductor for fixing of incoming cable |
| 55 | Outgoing ways :- MCCB 200 Amps adjudtable type ,4 pole,25 KA-02 Nos(Ics=100%Icu)MCCB 100 Amps adjudtable type ,4 pole,25 KA-02 Nos(Ics=100%IcuMCCB 63 Amps adjudtable type ,4 pole,25 KA-01 Nos(Ics=100%Icu) |
| 56 | Supply,installation,testing and commissioining factory made LT feeder pillar panel CPRI approved, size of panel as per CPRI Specification,double door floor mounted outdoor type,as per IP-65 grade,made out of CRCA sheet 3.15 mm thick of outer bodywith Aluminium bus bar 600 Amps,4 strip,(3 phase & Neutral) complete drilled,insulated with colour coaded insulation tape,mounted on insulators etc. Panel should be dust proof,vermin proof,powder coated,locking should be screw type,mechanical type,inter locking,should have danger noticefor 415 volt,AC,mounted on 50 x50 x6 mm angle iron frame having minimum 2 feet ground clearanceduly embedded in and including PCC block(1:2:4) type B1 foundation for fixing of panel complete including ternination of all incoming and outgoing cables with suitable size thimbles/lugs, glands , Nuts & Bolts complete all as required and directed.( Armament wing) |
| 57 | Incoming : - (i) MCCB 400 Amp adjustable type with , 4 Pole, 36 KA - 01 No.(Ics=100%Icu)(ii) Volt meter 0 to 500 Volts,Square flush pattern, digital type with CTs – 01 No (iii) Amp meter square flush pattern 0 to 400 Amps digital type with CTs -01 No. (iv) Indicating lamp LED type one set in incoming phases.(v) Internal wiring with PVC insulated copper conductor multi stranded cable 1100 Volt grade IS 694 marked of appropriate gauge including all copper lugs(vii) MCCB shall be provided with suitable spreader of aluminium conductor for fixing of incoming cable |
| 58 | Outgoing ways :- MCCB 200 Amps adjudtable type ,4 pole,25 KA-02 Nos(Ics=100%Icu)MCCB 160 Amps adjudtable type ,4 pole,25 KA-02 Nos(Ics=100%IcuMCCB 63 Amps adjudtable type ,4 pole,25 KA-02 Nos(Ics=100%Icu) |
| 59 | Supply,installation,testing and commissioining factory made LT feeder pillar panel CPRI approved, size of panel as per CPRI Specification,double door floor mounted outdoor type,as per IP-65 grade,made out of CRCA sheet 3.15 mm thick of outer bodywith Aluminium bus bar 600 Amps,4 strip,(3 phase & Neutral) complete drilled,insulated with colour coaded insulation tape,mounted on insulators etc. Panel should be dust proof,vermin proof,powder coated,locking should be screw type,mechanical type,inter locking,should have danger noticefor 415 volt,AC,mounted on 50 x50 x6 mm angle iron frame having minimum 2 feet ground clearanceduly embedded in and including PCC block(1:2:4) type B1 foundation for fixing of panel complete including ternination of all incoming and outgoing cables with suitable size thimbles/lugs, glands , Nuts & Bolts complete all as required and directed.( DMR 141/142) |
| 60 | Incoming : - (i) MCCB 400 Amp adjustable type with , 4 Pole, 36 KA - 01 No.(Ics=100%Icu)(ii) Volt meter 0 to 500 Volts,Square flush pattern, digital type with CTs – 01 No(iii) Amp meter square flush pattern 0 to 400 Amps digital type with CTs -01 No. (iv) Indicating lamp LED type one set in incoming phases.(v) Internal wiring with PVC insulated copper conductor multi stranded cable 1100 Volt grade IS 694 marked of appropriate gauge including all copper lugs(vi) Connection from MCCB to Busbar shall be of solid Aluminium conductor(vii) MCCB shall be provided with suitable spreader of aluminium conductor for fixing of incoming cable |
| 61 | Outgoing ways :- MCCB 200 Amps adjudtable type ,4 pole,25 KA-02 Nos(Ics=100%Icu)MCCB 160 Amps adjudtable type ,4 pole,25 KA-02 Nos(Ics=100%IcuMCCB 100 Amps adjudtable type ,4 pole,16 KA-01 Nos(Ics=100%Icu) |
| 62 | Excavating in post holes (or similar holes) each n exc 0.5 cu. m, getting out, returning,filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm in hard dense soil etc complete all as specified and directed by Engineer-in-Charge |
| 63 | Supply and fix 50 x 50 x 6 mm thick angle iron frameflat iron 40 x6 mm cut length including drilling holes for fixing of nut and bolts to hold chain link fencingincluding painting with two coats of synthetic enamel paint over one coat of red oxide primer on all exposed surface complete all as specified and directed. |
| 64 | Supplyand Fixingchain link fencing including line wires, any mesh, size dia 4 mmthick and steel wire mesh aperture 50 mm ofstandards, rails, straining bolts, etc.including provission of binding wire fixing 10 mm diamild steel round bar to tighten chain link fencing including necessary hooking binding cutting etc complete all as specified and directed by Engineer-in-Charge |
| 65 | Supply and laying of bricks surrounding the stone aggregate at sub station including necessary excavation,returning and removing complete all as specified and directed. |
| 66 | M &L for construction ofplinth (of size 2000mm x 2000 mm x 1500 mm) including excavation in trenchs in any type of soil,PCC 1:4: 8 in foundation LAND fly ash bricks masonry cement mortor 1 : 6 ,filling with moorum inside the plinth and RCC 1:2:4 over plinth including 16 mm TMT bar reainfrocement with center to centre distane 100mm and external surface of masonary shall be plasterd with cement morter 1:4 andpainted with weather coat paint ( double coat paint ) of shade complete all as specified and directed by Engr in charge |
| 67 | Supply and fixing in replacementofHT single core power cable 11 KV (earthed) strandred of size 95 Sqmm ,compacted,circular,aluminium conductor, conductor screen with extruded semiconducting compound XLPE Insulated, insulation screening with extruded semiconducting compound in combination with copper tape,aluminium round wire armored and FRLS PVC inner and outer sheathed,oxygen index cable confirming to IS 7098(Part II) 2011 up to date amendments complete all as specified. |
| 68 | M & L for replacement of Galvanised iron strip 32 x6mm buried in ground |
| 69 | M/L for GI Tubes,of size 80mm dia Medium grade, galvanised, with all fitting , laid in trenchesfor protection of cable in road /drain crossing complete all as specified and as directed. |
| 70 | M&L for road cutting upto 300mm deep and 200mm wide for crossing GI pipe line through road including making good the disturbed surface by filling mass concrete( 1:2:4)etc complete all as specified and directed by Engineer-in-Charge.Note : Rate of mass concrete is included in quated rate. |
| 71 | Supply and fixing in replacement of synthetic insulatingrubber mat testedfor HT 11/22 KV with test certificate forinstallation of size 2m x1m x12mm etccomplete all as specified and directed by Engineer-in-Charge |