Military Engineer Services-MES has published Tender For Repairs / Maintenance Of Fire Fighting Services, Fire Alarm System And Connected Misc Works At Cad Pulgaon. Submission Date for this Tender is 28-03-2024. Alarm Systems Tenders in pulgaon Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

42741725
Corrigendum : Tender For Repairs / Maintenance Of Fire Fighting Services, Fire Alarm System And Connected Misc Works At Cad Pulgaon
Open Tender
Indian
Maharashtra
pulgaon
28-03-2024

Tender Details

Repairs / Maintenance Of Fire Fighting Services, Fire Alarm System And Connected Misc Works At Cad Pulgaon

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 19-Mar-2024 Corrigendum_01 BOQ 28-03-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 84000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work:REPAIRS / MAINTENANCE OF FIRE FIGHTING SERVICES, FIRE ALARM SYSTEM AND CONNECTED MISC WORKS AT CAD PULGAON UNDER GE PULGAON
Sl. No. Item Description
1Upkeep offollowing equipment /machinery installed at pump house in/near building No. P-6 comprising offoam sprinkler and water sprinkler system for cooling and washing of floor, stainless steel piping with large No of opening to maintain the required discharge of water, regular flow of foam for detecting defective items and periodical minor repairs such as oiling, greasing, rubber gaskets and providing glands and all as necessary minor repairs required for proper functining of equipments complete all as specified and as directed including all the items listed in below:-
2Automatic foam sprinkler system including stainless steel tank complete and filling of foam as per direction.
3Centrifugal pumping set electric driven -01 set
4Standby diesel engine operated centrifugal pumping set auto/manual start- 01 set
5Jockey centrifugal pump electric drivenauto/manual start- 01 set
6Sluice valves, NRVs off sizes alongwith pipe line
7LT Panel Board with all accessories and power cables.
8Note:- (i) Testing will be carried outon Monthly basis and contractor submit the test report duly signed by users rep every month and all as specified and directed by Engr-in-charge .Testing shall be measured and paid separately. (ii)The rates of Oil, grease, rubber gaskets, and gland are deemed to be incl in above quoted rates. (iii) Anywelding work , cutting of exisitng pipes inserting MS/GI / CIfittings , replacing steel pipe , sprinkler is deemed to be incl in above quoted rates. (iv) Documents as specified are maintined and put to EIC monthly. (v) Contractor shall arrange transportation of foam drum from AGE E/M store to Pump houseand filling of foam in stainless steel tank insatalled at above bldgs deemed to included in above quoted rates. (vi) Connected Spares required for replacement of unserviceable parts shall be measured and paid separately in supply and fix in repairs. Note:- The Rate mentioned in Item No 1 For1 Year Duration. Panel recovery of Rs 2000 Per Month shall be recovered if contractor fails to testing on monthly basis at due time.
9All as per item No 1 ……………. but for buildings No P-14 complete all as specified and directed.
10Upkeep offollowing equipment /machinery installed at pump house in/nearbuilding No P-1 water sprinkler system for cooling & washing of floor of bldg No P-1,P-10 comprising of stainless steel piping with large No of opening to maintain the required discharge of waterfor detecting defective items and periodical minor repairs such as oiling, greasing, rubber gaskets and providing glands and all as necessary minor repairs required for proper functioning of equipments complete all as specified and as directedincluding all the items listed in below:-
11Cetnrifugal pumping set electric driven -02 set
12Sluice valves, NRVs off sizes alongwith pipe line
13LT Panel Board with all accessories and power cables.
14Note:- (i) Testing will be carried out on monthly basis and contractor submit the test report duly signed by users rep every month and all as specified and directed by Engr-in-Charge. Testing shall be measured and paid separately under respective items. (ii) The rates of Oil, grease, rubber gaskets, and gland are deemed to be included in above quoted rates. (iii) Anywelding work , cutting of exisitng pipes inserting MS/GI / CIfittings , replacing steel pipe , sprinkler is deemed to be incl in above quoted rates. (iv) Documents as specified are maintined and put to Engr-in-Charge monthly. (v) Connected Spares required for replacement of unserviceable parts shall be measured and paid separately in supply and fix in repairs. (v) The quoted rate shall cover for entire period of 365 days(including Sunday and Holiday). Note:- The Rate mentioned in Item No 3 For1 Year Duration. Panel recovery of Rs 2000 Per Month shall be recovered if contractor fails to testing on monthly basis at due time.
15Testing of Foam Sprinkler system installed at P-6 and P-14 sheds complete all as specified and as directed. Note: One testing in one building will be one Job
16Testing of water sprinkler system installed at P-1, P-6 P-10 and P-14sheds complete all as specified and directed. Note: One testing in one building will be one Job
17Supply andfix in repairs foam spray nozzle made of stainless steel (SS304) construction with 1/2 " male BSP threaded inlet. The nozzle shall have K Factor of 30/45 and shall have aeratingarrangement to give foam of expansion 1:3 to 1:6 and suitable pattern for covarage of risk area
18Supply & fix in repair Conventional 24 V DC ElectronicHooter cum Flasher.Make : spencer / Honeywell / Fire Light / NotiFier/ Ravel
19Supply & fix in repair15 mm (½") dia. NBCM Body chrome finishedside wall type sprinkler / Spray nozzle Medium Velocity having rating with deflector disc of conventional construction with all accessories require to install. Make: Kartar / Shah Bhogilal / HD / Newage
20Maintenance repair& testing of fire hydrant system installed at bldg shed No P-1to P-17"F" sub Depot including maintenance of followingParts complete all as specified and as directed.
21Fire hydrant valves from outside and inside
22Fire boxes from outside and insde
23Female coupling lugs and repair to spring nut
24Hose reel leakage and make good the same
25Gland, all rubber parts
26Note:- (i) Testing will be carried out quaterly basis and contractor submit the test report duly signed by users rep every quarter and all as specified and directed. Testing charges shall deemed to be included in unit rate quoted. (ii) Oil, grease, rubber guskets, and gland are deemed to be included in above quoted rates. (iii) Any lathe work, welding work , cutting of exisitng pipes inserting MS/GI / CIfittings , replacing steel pipe , sprinkler is deemed to be incl in above quoted rates. (iv) Documents as specified are maintined and put to Engr-in-Charge monthly. (v) Connected Spares required for replacement of unserviceable parts shall be measured and paid separately as supply and fix as and when required. (vi) M & R shall be quarterly and considered one job for one bldg. (vii) Panel recovery of Rs 3000 Per Qtr shall be recovered if contractor fails to testing on quarterly basis at due time.
27Supply and fix in repairWeather proof hose cabinet of size 750 x 600 x 250 mm fabricated from M.S. angle iron sections and 18 GMS sheet with full glass door and locking arrangement suitable to accommodate - 2Nos 15 M long hoses and 1 No branch pipe and nozzle including stand of exisitng height .The cabinet shall be painted with one coat of primer and two or more coats of synthetic enamel paint of approved make and shade and shall be suitably mounted.
28Supply and fix in repairs SS 304 Short Branch Pipe 63 mm with necessary accessories conforming to IS : 903 ISI marked. (Make : Newage / Swati / Shah Bhogilal /. Arihant)
29Supply and fix in repair of Hydrant Valve Oblique Type 63 mm complete made out of SS 304 fitted with PVC main blank cap and GI Chain IS 5290 with ISI mark complete all as specified and as directed (Make : Newage/Kartar/Shah Bhogilal / Arihant)
30Supply and fix in repair Hydrant valve wheel cast iron type suitable for 63mm dia hydrant valve complete all as specified and as directed
31Supply and fix in replace RRL hose pipe 63 mm dia & 15 meter long with male and female coupling with ISI mark completeall as specified and as directed.
32Supply and fix in repair Hydrant cap with chain for 63mm dia hydrant valve.
33M & L for painting of fire hydrantboxes with stand, Hydrant Valves and MS pipe over the ground level after preparation of old painted surface withtwo coat of exisiting colour synthetic enamelled paint complete all as specified and as directed.
34Maintenance & repairs to smoke / heat detector as well as repeater automatic fire alarm system complete with fixed temperature,heat detector,main control panel cabling 24 volt SC with FRLScable with rectifier,24 volts battery with charger unit complete installed at P-1, P-6 P-10 and P-14 sheds of "F" sub depotand 104 AC shed in "B" sub depot complete all as spcified and as directed.
35Supply & fix in repair ionization smoke detector from shed with base plate complete all as specified and directed. Make: System sensor / Honeywell/Fire light/ Notifier
36Supply & fix in repairs heat detector in shed with base plate complete with base plate complete all as specified and directed. Make: System sensor / Honeywell/Fire light/ Notifier
37Supply & fix in repairs Beam detector with Reflectors range 15 mtr x 15 mtr x 60 mtr Operating voltage 24 V DC with adjustable convex mirror(all required Accessories.) complete all as specified and as directed Make : System Sensor / Honeywell / Fire Light / Notifier
38Supply & fix in repair Conventional Manual call point.complete all as specified and as directed. Make : spencer / Honeywell / Fire Light / Notifier
39Supply and layin replacement of copper conductor armoured cable FRLSH of size2 corex 1.5 Sqmm on wall / ground with necessary clamps complete all as specified and as directed . Make : POLYCAB/ PLAZA/ HAVELLS.
40Supply and layin replacement of copper conductor armoured cable FRLSH of size4 corex 2.5 Sqmm on wall / ground with necessary clamps complete all as specified and as directed. Make : POLYCAB/ PLAZA/ HAVELLS.
41Supply and fix in replacement of 12 Volts 7 Amps maintenance free dry cell battery, complete all as specified and as directed. Make : EXIDE / AMCO / TATA GREEN.
42Supply and lay in replacement of copper conductor PVC cable FRLSH of size2 corex 2.5 Sqmm on wall / ground with necessary clamps complete all as specified and as directed. Make : POLYCAB/ PLAZA/ HAVELLS.
43Taking down existing pipe of any type &supply and laying MS Pipe "C" Classby of following bore all as specified and directed by Engr-in-Charge.Make:-Prakash Surya,Jindal
44200 mm bore
45150 mm bore
46100 mm bore
4780 mm bore
4850 mm bore
49Note :- Cutting of exisitng pipe, welding works and inserting any type of fittings for above bore pipe deemend to including in above quoted rates
50Taking down existing union and supply and inserting GI union of 50mm bore complete all as specified and directed. Note :- Cutting of exisitng pipe, welding works and inserting for fixing of gate valve deemed to in included above quoted rates
51Taking down existing union and supply and inserting GI union of 25mm bore complete all as specified and directed. Note :- Cutting of exisitng pipe, welding works and inserting for fixing of gate valve deemed to in included above quoted rates
52Taking down existing gate valve and supply and fix gun metal gate valve of 50mm bore all as specified and directed. Note :- Cutting of exisitng pipe, welding works and inserting for fixing of gate valve deemed to be included in above quoted rates.
53Taking down existing NRVand supply and fix new Stainless steel NRV of following bore complete all as specified and directed. Note :- Cutting of exisitng pipe, welding works and inserting for fixing of gate valve deemed to be included in above quoted rates.
5450 mm bore
55100 mm bore
56Taking down existing sluice valve and supply and fix new sluice valve PN 1.6 of following bore complete all as specified and directed.
57200 mm bore
58150mm bore
59100mm bore
6080mm bore
6165mm bore
62Note :- Cutting of exisitng pipe, welding works and inserting any type of fittings for fixing of sluice valve deemed to be includedin above quoted rates.
63Taking down existing foot valve and supply and fix CI foot valve of latest modelof following bore complete all as specified and as directed . Make:- Normex or as equivalent.
64200 mm bore
65150mm bore
66100mm bore
67Note :- Cutting of exisitng pipe, welding works and inserting any type of fittings for fixing of sluice valve deemend to be included in above quoted rates.
68Taking out the burnt electric motor of capacity 5.0 HP to 7.5 HP from existing position, transporting to civil work shop, separating the stator and rotor housing, cutting and removing the existing winding of stator completely, cleaning the slots and rewinding with existing gauge of super enamelled copper winding wire with suitable insulation, applying insulation varnish and heating in heating chamber till completely dried and reassembling the motor including supply and replacement of DE(01 No.) &NDE(01 No) bearings (make: NBC/SKF/TATA), transporting back to site and re-installing in its original position including proper alignment for smooth running and testing on completion complete all as specified and directed .
69All as per item no 32.00 but for 12.5 HP to 15 HP motor
70All as per item no 32.00 but for 40 HP to 15 HP motor
71All as per item no 32.00 but for75 HP to 80 HP motor
72M&L for taking out the defective pump set of capacity upto 5 HP to 15 HP ofAC plant fromexisting position by carefully disconnecting all water pipe lines and electrical cablesand carrying out overhauling by dismantling the pump casing, cleaning of the impeller and supply and replacement of Gunmetal bush(01 No), gland plate (01 No.) alongwith studs, nuts, gland packing rope, greasing and re-assembling and re-installing in its original position and testing on completion complete all as specified.Note:-spare parts other than mentioned above under this itemwill be measured and paid separately as supply only.
73All as per item No 36.00but forpump capacity 40 HP to 80 HP
74supply only end ball / roller bearing set with good quality grease suitable for pump setsupto 5 HP to 15 HPMake:NBC/SKF/Tata
75supply only end ball / roller bearing set with good quality grease suitable for pump sets 40 HP to 80 HP Make:NBC/SKF/Tata
76Supply only star coupling key any size as per sample complete all as specified and as directed.
77supply only pump shaft suitable for pump sets 5 HP to 15 HP capacity complete all as specified and as directed.
78supply only pump shaft suitable for pump sets40 HP to 80 HP capacitycomplete all as specified and as directed.
79Supply only pump impeller brass suitable for pump sets5 HP to 15 HP capacity complete all as specified and as directed.
80Supply only pump impeller brass suitable for pump sets40 HP to 80 HP capacity complete all as specified and as directed.
81Supply only gun metal bush bearingset complete set of two as per sample for 5 HP to 15 HP Pump complete all as specified and as directed.
82Supply only gun metal bush bearingset complete set of two as per sample for 40 HP to 80 HP Pump complete all as specified and as directed.
83Material and labour for CI special/fittings suitable for CI flanged/socket ends pipe upto 200mm bore such as bends, (any radius and angle), tapers any type (straight, bend, increasing, decreasing or double socket etc) tee piece, single branch "Y" junctin, double branch, cross (all flanged), collars, caps & plug, tail pieces, reducers, mechanical joint etc complete including taking out old fittings complete all as specified and as directed.
84Repair and Maintenance of Electric operated siren of range 3 to 5KM directly coupled with 3 HP 415 V 3 phase electric motor complete all as specified and directed . (Note Items such as PVC copper wire, lugs, thimbles, nuts, bolts, washer, PVC termination ,lathe work if any are deemend to be included in above quoted rates). Note: rewinding shall be measured and paid separately
85M&L for Re-winding of motor of Electric operated siren 3 HP with exisitng sizes/ guage copper wire , testing complete
86Servicing of Diesel Engine installed at P-4, P-6 and P-14 and taking out the defective/unserviceable parts and re-assembling the same after repair/replaced and testing complete all as specified and directed.(Note : U/S spare parts shall be measured and paid separately as supply only here in after).
87Diesel filter exisitng size
88Oil filter exisitng size
89Air filter exisitng size
90Fan belt exisitng size
91Supply and pouring of coolant suitable for radiator as per the requirement of time to time as directed by Engr-in-charge for various capacities of DG Set complete all as specified and as directed.
92Supply and filling lubrication oil SAE-40 ( 20 W- 40 grade) ofMake SERVO OF IOC/HINDUSTAN PETROLEUM/BPCL/ CASTROL) as approved by GE.
93Supply and fix BatteryTerminals (Positive and Negative - one set) copper 12V suitable for 100 / 120/ 180 AH as per existing complete all as specified and directed .
94Supply and fix Batteryled (Positive and Negative - one set) copper not less than 1 meter with suitable for 180 AH as per existing complete all as specified and directed.
95Supply and filling distilled water for exisitng power backup system complete all as specified and as directed.
96M & L for paintingcomplete equipments/ machinery / pipes / valves / Elect Panels etc installed at pump house for P-1, P-6 and P-14 after prepation of old painted surface with two coat of exisiting colour synthetic enamelled paint complete all as specified and directed.
97M & L for paintingcomplete equipments/ machinery / pipes / valves / Elect Panels etc installed at foam pump house ofP-6 and P-14 after prepation of old painted surface with two coat of exisiting colour synthetic enamelled paint complete all as specified and directed .
98Supply, Installation in repairsTesting & Commissioning of 8 Zone Microprocessor based conventional type Fire Alarm Panel incl following items
99Panel indicator LCD.
100Fault Indicator
101Short Indicator
102Zone Isolate Indicator
103System Ok Indicator
104Fire Indicator
105Supply Fault Indicator
106Panel fabricated of 16SWG CRCA Sheet Make : spencer / Honeywell / Fire Light / Notifier
107Supply and fix in replace of MCCB 3 Pole 100Amp 16kA 415VAC, 50 Hzoffixed type magnetic releaseto the existing panel board complete all as speciifed and directed.Make L&T/Havels/CG
108Supply and fix in replace of MCCB 3 Pole 160 Amp 36kA 415VAC, 50 Hz offixed type magnetic releaseto the existing panel board into the existing panel board complete all as speciifed and as directed .Make L&T/Havels/CG
109Supply and fix in replace of MCCB 3 Pole 200Amp 36kA 415VAC, 50 Hz offixed type magnetic releaseto the existing panel board to the existing panel board complete all as speciifed and directed .Make L&T/Havels/CG
110Supply and fix in repairs MNX power contactor 3 Pole, 415 V, Current rating 70 A, 2NO + 2NC having coil voltage 240 Volts complete all as specifiedand as directed.
111Supply & fix in replace MNX power contactor3 Pole, 415 V, Current rating 110 Amps, 2NO + 2NC having coil voltage 240 Voltscomplete all as specifiedand as directed.Make : L&T/Havells/CG.
112Supply & fix in replace spare parts kit for 3 pole MNX power contractor 50Amps, 415 volts, with coil rating 230/415 volts,type ML-3 complete all as specifiedand as directed. Make L&T/Havells/CG.
113Supply and fix in replaceBimetalicOverload relays suitable for MNX Power Contactor 50Amps, 415 volts, with coil rating 230/415 volts complete all as specifiedand as directed. of make L&T/Havells/CGtype ML-3.
114Supply and fix in replaceBimetalicOverload relays suitable for MNX Power Contactor 70Amps, 415 volts, with coil rating 230/415 volts complete all as specifiedand as directed. Make L&T/Havells/CG .
115Supply and fix in replace from the exisitng panel single phase preventor complete all as specifiedand as directed.
116Supply and fixingof Cast Iron strainer of flange type of latest design of size 200/150 mmcomplete all as specifiedand as directed.
117Supply and fixingstainless steel rope wire of size 4 mm for existing water level indicatorfor Overhead tank, Under ground sump of any height/depth complete all as specifiedand as directed.
118Supply and fixingstainless steel float of free size for existing water level indicatorfor Overhead tank, Under ground sump of any height/depth complete all as specifiedand as directed.
119M & L for paintingto existing water level indicator with two coatalongwith proper level markingfor overhead tank, Under ground sump of any height/depth complete all as specifiedand as directed
120Supply and fixing float valve of size 25 mm for primingoverhead tank complete all as specifiedand as directed.
121M&L for MS Fabrication work,made out of structural steel sections as in frame work for cable & piping ducts/MS door panels etc at sewage installation ,MS angle /flats/plain sheet of appropriate gauge ,cut to size and made to the existing shape suitable for fixing MS chequred duct cover /door panel including nut and bolts and washers ,welding bracing work bending cold or hot drilling holes for bolts in any shapes or sizes as reqired including one coat of primer and two coat of synthetic enamel paint to the entire steel surface all as specified and directed.
122Material and labour for PCC 1:3:6 type C 1 (using 20 mm graded stone aggregate) for making pump , motor,hydrant foundation orany size as specified including necessary form work if any for fixing GI pipe/air termination rod complete all as specified and asdirected.
123Labour includingtool & plant with any pestiside for cuttinggrass and bushes on monthly basis for general cleaning ofPump house,AC Plant , Sub Station, Lt Panel, Fire Hydrant including hose reel box, UG Sump, Overhead tank, Valve Pit Chamberand approach and path way for following locations :-. 5 meter sorrounding of building/ pump house and other connected area :- (a) Pump House & AC Plant BuildingsBuildings- 7 Nos (b) Substation Building - 6 Nos (c) UG Sump- 05 Nos (d) Over Head Tank- 02 Nos (e) LT Panel - 10 Nos (f) Fire Hydrant and hose reel boxes including path way-62 Nos (g) Valve pit chamber- 20 Nos Note:- The rate of above JOB for duration of 12 month. However the above cleaning will be done on quarterly basis.
124Excavation in trenches not exceeding 1.50m wide and not exceeding 1.50 metre depth for foundation, laying of cables/pipes/poles etc., and getting out in soft/loose soil complete all as specified and directed.
125Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm in soils complete all as specified and directed.
126Removing excavated material/soil to a distance not exceeding 50mand depositing where directed at a level not exceeding 1.50m above the starting point complete all as specified and directed.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail