Tender For Provision Of Fire Detection And Alarm System In Certain Bldg At 24 Ed Under Age (I) Manauri., manauri-Uttar Pradesh

Military Engineer Services-MES has published Tender For Provision Of Fire Detection And Alarm System In Certain Bldg At 24 Ed Under Age (I) Manauri.. Submission Date for this Tender is 09-04-2024. Alarm Systems Tenders in manauri Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

42653886
Corrigendum : Tender For Provision Of Fire Detection And Alarm System In Certain Bldg At 24 Ed Under Age (I) Manauri.
Open Tender
Indian
Uttar Pradesh
manauri
09-04-2024

Tender Details

Tender For Provision Of Fire Detection And Alarm System In Certain Bldg At 24 Ed Under Age (I) Manauri.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 08-Mar-2024 Corrigendum No 01 Date 26-03-2024
2 15-Mar-2024 CORRIGENDUM NO 02 Date 01-04-2024
3 22-Mar-2024 Revised BOQ and corrigendum BOQ 02-04-2024
4 22-Mar-2024 Corrigendum No 03 Date 02-04-2024
5 02-Apr-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 09-04-2024

Key Value

Document Fees
INR 1000 /-
EMD
INR 220000.0 /-
Tender Value
INR 1.44 Crore /-

BOQ Items

Name of Work: PROVN OF FIRE DETECTION AND ALARM SYSTEM IN CERTAIN BLDG AT 24 ED UNDER AGE (I) MANAURI
Sl. No. Item Description
1Supply, Installation, testing and commissioning of surface mounting Analague Addressable fire alarm control panel 1 loop with EN 54. The panel shall be compliant with EN 54-2 and EN 54-4, capacity from 99 detector and 99 moduls devices upto 200 detector single loop, The panel must have 2 inbuilt programmable sounder circuits, each circuit rated at 1 amp, 16 Zonal LED indicators, 5 programmable inputs, 3 programmable relays, 3 A power supply, large graphic display, real time clock. The panel must have expandable feature from 1 to 2 loops. The panel shall have up to 512 sub addressable programmable Inputs/Outputs via optional RS 485 COMMS serially connected expansion cards. Powerfull wide cause and effects, sensitivity adjustment and drift compensation, stores 500 last events in event log, indicating panel sounder circuits complete with LCD Display with back light illumination and push button to acknowledge alarm, including 7 Ah 12 V (2 per panel) battery, panel constructed by 1.2 mm thick mild sheet steel, epoxy powder coated finishing, display 8 line of 40 characters graphic LCD, testing and reset suitable for operation 230 volts single phase 50 Hzs AC supply 24 V DC supply with suitable capacity charger including maintenance free batteries and battery charger,mains voltage 110 or 230 V AC 50 or 60 Hz, mains supply fuse 1.6 A 250 V, IP 30, fire contact rating 30 V DC1 Amp, alarm contact rating, 30V DC1 Amp, sounder output rating fused at 1 Amp each, detection loop 400 miliamp output, Dimension of Panel 385x310x90mm, requires network card and modules including Flush mounting accessories, Large enclosure and all fixing accessories complete all as specified and directed by Engr-in-Charge.
2Supply, Installation, testing and commissioning of surface mounting Analague Addressable fire alarm control panel 2 loop with EN 54. The panel shall be compliant with EN 54-2 and EN 54-4, capacity from 99 detector and 99 module devices upto 200 detector (per each loop) for two loop,The panel must have 2 inbuilt programmable sounder circuits, each circuit rated at 1 amp, 16 Zonal LED indicators, 5 programmable inputs, 3 programmable relays, 3 A power supply, large graphic display, real time clock. The panel must have expandable feature from 1 to 2 loops. The panel shall have up to 512 sub addressable programmable Inputs/Outputs via optional RS 485 COMMS serially connected expansion cards. Powerfull wide cause and effects, sensitivity adjustment and drift compensation, stores 500 last events in event log, indicating panel sounder circuits complete with LCD Display with back light illumination autodialler and push button to acknowledge alarm, including 7 Ah 12 V (2 per panel) battery, panel constructed by 1.2 mm thick mild sheet steel, epoxy powder coated finishing, display 8 line of 40 characters graphic LCD, testing and reset suitable for operation 230 volts single phase 50 Hzs AC supply 24 V DC supply with suitable capacity charger maintenance free batteries and battery charger,mains voltage 110 or 230 V AC 50 or 60 Hz, mains supply fuse 1.6 A 250 V, IP 30, fire contact rating 30 V DC1 Amp, alarm contact rating, 30V DC1 Amp, sounder output rating fused at 1 Amp each, detection loop 400 miliamp output, Dimension of Panel 385x310x90mm, 2 sounder circuits PTR requires network card and modules including Flush mounting accessories, Large enclosure with all fixing accessories complete all as specified and directed by Engr-in-Charge.
3Supply, Installation, testing and commissioning to addressable intelligence having inbuilt microprocessor with twin blinking LED, memory and decision alogrithm twin angle with both forward and backward light scattering mechanism cum thermal multicriteria detector (Analogue Multi-sensor) with heat and smoke combination, high performance chamber, operating voltage 17-41 VDC, operating temprature range -10 degree Centigrade to +50 degree centigrade, pulsing /non pulsing controlled from panel,including detectorbase with locking features to prevent unauthorised removal, stainless steel contact, confirms EN 54-5 & FN 54-7 LPCB and Vds approved complete all as directed by Engr-in-charge.
4Supply, installation, testing and commissioning ofIR3 based flame detector with relay type module, IP65 protection, mounting stand (stainless steel adjustable mount), detector detects multi spectral sensitivity of fire by using IR sensors, detectors complying with and type certified to EN-54-10, design for long distance detection range of more than 25-40 mtr (detection of 0.1 sqm flame at 25 mtr straight line from flame detector and detection of 0.4 sqm flame at 25 mtr to 40 mtr in straight line from flame detector) for viewing angle,response time typically less than 5 second, field of view 90 degree conical field of view or 45 degree either side of the viewing axis centre line, supply voltage 17 to 28 VDC typically 24 VDC, LED indication system, operating temprature and storage temprature-40 degree C to 70 degree C, humidity less than 95% LPCB approved confirming to EN 54-10 complete and all as directed by Engr-in-Charge. Note:-(a)Contractor shall quote the rate meeting the all power input requirement and accessoriesas required for functioning the flame detectors except wiring.Wiring shall be measured andpaid separately under respective items. (b) Contractor shall provide guarantee of flame detector as per OEM but not less 02 yearsfrom the actual date of completion
5Supply, installation testing and commissioning of Analogue Addressable Manual call point with integral short circuit isolator, with flush mounting glass box resettable type, unique plug and play installation concept, confirms to EN 54-11 & EN-54-17, LPCB approved, Vds approved resettable glass type compatible with main fire alarm control board microprocessor basedand blinking facility complete Analogue addressable protocol having, Bi-coloured status LED, Non-frangible element fitted as standard (confirms to EN 54), complete all as specified and directed by Engr-in-Charge.
6Supply, installation, testing and commissioning of addressable wall mounted intelligent loop powered electronic sounder cum strobe, with 30 inbuilt tones(all tones as per EN54-3), low power requirement, 07 volume levels, IP 65 rating, LPCB approved in accordaance to EN-55 part -3 complete as specified as per Engineer in charge.
7Supply, installation, testing and commissioning of sensor common mounting base, features integral short circuit isolator, slim profile,EN-54-17 Approved by LPCB and Vds approved operating voltage 15 to 30 Vdc complete all as specified and directed by Engr-in-Charge.
8Material and labour for unarmoured sheathed and twin core twisted cable FRLSHmulti stranded copper conductor 1.50 Sqmm 2 core1100 volts control cable as perIS-7098 and including drawing through on wall/ceiling in rigid PVC conduit medium grade pipe,20 mm diain suitable size with all necessary fittings, tee, elbow, u-clip, etccomplete all as specified and as directed. Note : (i) unarmoured sheathed 1.50 sqmm2 core with one run of PVC conduit pipe 20 mm dia medium grade shall be measured as one unit.
9Supply,laying, Jointing, testing and commissioning in trenches/fixing with clamp on wall connecting, thembling, glanding of XLPE insulated PVC innersheathed, armoured, galvanised steel strip or wire, LT control cableFRLSH multistranded copper conductor, 1100 volts grade, cross-sectional area 2.50 Sqmm 4 core as per IS 7098 (Part I) 1988 complete all as specified and directed by Engr-in-Charge.
10Supply, installation, testinngUPS 1 KVA (1000 VA),40-50 Min backup, boost function for low input over voltage protection Extended input voltage range of 135 to 300 volt UPS to battery backup mode including Battery back up system for 48 hrs suitable size of Battery should be includefor fire alarm control panel all as directed by Engr-in-Charge.
11Supply and fixing fire alarm sirens Electronics horizontal type continous normal operation for atleast 50 minutes with sound level 65 db to 120 db Measured, single phase, 220/250V, 6000 RPM, 50 Hz, AC supply,at 1.5 Mtr with sound output variation of +5 db 500 m range, IP-65 Weatherproof, with suitable size of mounting stand and protection cover for siren.
12Supply and fixing of control unit for siren with Addressable Control Module for integration with main Fire Alarm panel.
13Supply, Installation, testing and commissioning of Network module. The module shall connect panels and repeator panels through RS 485. The modules shall use RS 485 data at a baud rate. The Network module must be configured master/slave, multiple Master/Slave and peer to peer Networking, Net work card for integration of 2 loop Panels into a networked system complete all as specified and directed by Engr-in-Charge.
14Supply, installation, testing and commisioning of Active Repeater panel to be integrated with Fire alarm control panel, IP30 rating, larger display full colour 800 x 480 LCD with resistive touch screen and automatic back-light dimming and the status of any fire/fault of integarated fire alarm panels, panel should compliant with EN54-2, 1.2 mm mild sheet steel construction, Epoxy powder coated finishing, 3 knockouts top, 3 knockouts back cable entry, connection via RS485 control panel network, 24 programmable function buttons,operating voltage 18-32 Vdc, rated voltage 24 Vdc, Alarm current 120 mA, Ambient temprature 5 to 45 deg celcius,approved by LPCB complete all as directed by Engr-in-Charge.
15Excavation in trenches in hard/dense soilnot exceeding 1.5 mtr deep and notexceeding 1.5 mtrwide for laying of cables, foundation, etc or for shaft well, cesspits, manholes, pierholes, etc not exc 10 Sqm plan and getting out in soft/loose soil complete all as specified and directedat site.
16Returning,filling inincluding spreading, levelling, watering and well ramming excavatedsoil inlayers not exceeding 25 cm thickeach, backin trenches after cableshave been laid and tested , poles, stays, struts havebeen erected and tested all as specified and directedat site.
17Removing excavatedsurplus soil (Soft/Hard soil)obtained from exavation to a distance not exceeding 50 mtrand deposting where directedat a level not exceeding 1.5 m above the starting point all as specifed and directed
18Material and labour for sand cushioning with a layers of dry clean Gangariver sand 8 cm thick before laying of cable and 15 cm thick after laying of cable in trenches complete all as specified. Note: Punned thickness 18 cm shall only be measured.
19Supply and laying old size sub class "B" bricks laid flat in trenches over the cable with the length of brickperpendicular to the directionof cable length, adjacent/abutting each other for cable protection complete all as specified and directed.
20M&L for boring of holes under road/drain/PCC path by manual method for insertingupto 40 mm dia light GI tubing for cable protection in minimum 60 mm depth from normal ground level all as specified and directed.
21Supply and laying 40 mm dia GI tubing light grade complete with all fittings (ISI Marked) laid in trenches/fixed complete to walland ceiling or laid in floors, trenches, under road crossing, fixed on poles/walls for cable protection all as specified.
22M&L for fixing of LT cable route indicator aluminium cast material, 100 mm dia, round with 5-6 mm thick, two hole for mounting, 3 mm Embossed letter as appropriate, includingstand of made out of angle iron of size 40 x 40x 6mm thick of length 90cm (60 cm above ground level) as directed and to be grouted 2 feet from the ground level including all excavation and earth work complete all as specified and directed.
23S & F grid false ceiling in GI system powder coated prelude main runner section 35x24x0.40mm, cross T 28x24x0.40mm, wall angle 24x24x0.40mm and including providing and fixing designer 4mm thick non asbestos fibre fire resistant cement building board of approved texture, design and pattern with all finishes size 595x595mm fixed in ceiling frame work with all necessary hanging materials such as GI suspenders "J" bolts, necessary washers expansion holding fasteners etc for securing framework to ceiling wherever required complete all as specified and directed
24S & F rolled mild steel joist, channel, angle, tee or hollow sections, fixed independently or support for holding ceiling as required confirming to grade E-250 (Fe-410W quality) of any size and shape complete all as specified and directed.
25M&L for preparation of new steel surfacesof any description over 10cm in width or girth not otherwise described and applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
26NOTE applicable for item no 1 to 7,10 to 14: Contractor shall provide guarantee forflame proof itemsas per OEM but not less 02 yearsfrom the actual date of completion.