Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 19-03-2024 | AMENDMENT No. 1 | Date | 01-04-2024 |
| Sl. No. | Item Description |
| 1 | GENERAL NOTES : |
| 2 | The Contractor shall visit the site and shall satisfy himself as to the conditions under which the work ittobeperformed.Heshallalsocheckandascertainthelocationofanyexistingstructureor equipment or any other situation which may affect the work. No extra claim as a consequence of ignorance or on ground of insufficient description will be allowed at a later date. |
| 3 | All equipment and material shall be IS approved. |
| 4 | All approvals shall be obtained from Project Manager or EIC. |
| 5 | All equipmentand materialshall be inspectedat manufacturer’sworks as per relevant IS by the Client or his representative before dispatch to site. |
| 6 | All vendor drawings shall be approved by the Project Manager or EIC before fabrication work starts. |
| 7 | All testing and commissioningshall be as per relevant IS for equipment and IS: 732, 1989 for the installation. All testing records are to be maintained and submitted for Project Manager or EIC. |
| 8 | Minor Civil work like core cutting,RCC Pedastal, foundation,wall opening and closing , work for pipe routing, other works and making damages to repair are also in vender scope with no extra cost.the rate for these should be included in the rate quoted. |
| 9 | Making necessary alteration by means of civil work in the AHU / LT panel area and various other places to meet the installation requirements without any extra cost. As per CPWD Standard for civil construction and repair or as per instruction of EIC. |
| 10 | HVAC WORKS : |
| 11 | AIR COOLED SCREW WATER CHILLING MACHINE WITH VFD (AHRI Certified) |
| 12 | Suppy, installation, testing & commissioning ofAir-Cooled Screw Chiller water plant of 500 TR actual capacity each (AHRI Certified comprising of 1 working and to be sychronised with existing chillers of same capacity)(a) Semi-hermetic Screw compressor suitable for R 134a refrigerant.(The chiller machine manufature should be the OEMof Compressor also )(b) Air-cooled Condensor having duly epoxy coated Copper Coil & Aluminium Fins with protective coating with other accessories.(c) Flooded / DX type shell & Tube Chillers with accessories having entering /leaving condition of water 52 Deg F/ 43 Deg F with maximum pressure drop of 7M .(d) Steel structure for assembling / mounting the equipements, finished with powder coated painting, spring type vibration isolators for installing the Equipement on foundation.(e) Control Panel incorporating all the safety functions including HP & LP cutout, single phase preventor, internal control wiring for sequential operations, contractors for sensing flow through leaving chilled water control, compressor & expansion valve modulation with automatic capacity / load limiting devices.(f) Interconected refrigerant piping with safety controls viz liquid line solenoid valves, HP/LP controls.(g) Full charge of Refrigerant R134A (h) Unit mounted Starter panel comprising of disconnect switches,3 Phase current transformer and other essential compressor motor protecting devices.(i) Insulation of shell &tube chiller with nitrile rubberCooling Capacity: 500 TR (Actual)Ambient Condition : 45.0 Deg CChilled Water \"In\": 12.2 Deg CChilled water \"Out\": 6.6 Deg CChiller Flow Rate : 1200 USGPMMaximum 1KW : 1.5 KW/TR Including condenser Fans .Configuration:1 Working + 1 Standby |
| 13 | The unit mounted starter panel shall be complete with IP-65 protection consisting of power disconnecting switches with fuses, starters for compressor motors, under/over voltage trip, single phase preventers, communication card which can accept 4-20 mA or 2-10 Vdc analog signal. All components shall be mounted on welded steel base frame, structural steel profiles / panels made out of galvanised sheet steel, protected with primary coat & finished with acrylic paint. The chiller shall be mounted on the spring isolators and earthing shall be included in the scope of work. The chiller shall be compatible with BMS.(MODBUS / Bacnet card to be included with scope of supply). |
| 14 | Chiller shall be designed as per super ECBC Building Code in respect of COP/IPLV |
| 15 | Chiller Plant Manager |
| 16 | Supply, installation, testing & commissioning of chiller plant manager as per above chillers requirement. The plant manager shall be suitable to controll all the chillers and all suitable modules ( I/ O) shall have to be provided so individual Micro Processor controlled panels of machines can be synchronised for chillers, pumps, others, etc. and to enable sequential operation to achieve equal operating time and take care of load patterns, etc. complete including all accessories and as per EIC. |
| 17 | The controller shall able to communicate to BMS with Modbus/ BACnet/ Lonworks/ IP protocol. |
| 18 | Plant Manager shall be procured from quoted Pump / Chiller manufacturer. |
| 19 | HOT WATER SYSTEM |
| 20 | Supply Installation Testing and Commissioning of Electric Hot Water Calorifier (Hot Water Generator) of following Capacity Hot water calorifier to be of Stainless Steel construction complete with vertical type shell. dished ends, all accessories and as per tender specifications. The calorifier is Insulated with 50 mm thick 48Kg/cum density mineral wool insulation and covered by 26G aluminium sheet. The scope of works are complete with Electrical panel metering devices, inside power & control wiring digital thermostat, Thermometers, Pressure gauges control panel etc and as per tender specification. |
| 21 | Hot Water Generator of Capacity 250 KW |
| 22 | Hot Water Pump with VFD |
| 23 | Supply, installation, testing and commissioning of vertical Inline Pump/ Vertical split casing , back pull out flexible coupled End Suction Pump mounted on a common base with electric motor for re-circulation of water for the central air conditioning system. The pumps shall be flexible coupled protected by OSHA complaint coupling guard, withCI casing, SS (CF8)/bronze impeller, high strength steel shaft (prefarably SS 304) and MS fabricated base plate .The pump motor shall be suitable for 415± 10% volts, 50cycles, 3phase AC power supply of (IE3) efficiency class.Motor shall be squirrel cage, Class F insulation, 1500RPM(Max.)Pump, base, coupling and motor shall be factory assembled. The capacity of motor shall be at least 10% in excess of BHP requirement of pump. The internal components of pumps including mechanical seal shall be suitable to sustainrequired temperature. Minimum efficiency of pump shall be as mentioned below. |
| 24 | The pump shall have foundation, suitable support/Mounting Arrangement including making connection of inlet & outlet with fittings including nut, bolts, packing etc.) with plaster, Antivibration arrangement of cushy foot mountings is deemed to be included in this item cost.Suction guide to be provided by pump manufacturar for unit responsability. Pump curves & loss calculations shall be furnished during approval from competant authority.Pumps shall be BMS compatible.Pump rating shall be PN 16 preferably.Contractor to submit proposed pump model with duty curve.The entire work shall be complete as per specifications & as per directions of Engineer-in-charge. |
| 25 | The Hot water pumps shall also include the cost of thermal insulation and suitable for operation on variable frequency drives & conforming to the specifications of variable speed pumping system.The capacity of motor shall be at least 10% in excess of BHP requirement of pumpWaterflowrate : 500 USGPMHead : 40 MeterMotor HP :25 KW(Max) or as per OEM standard or meeting functional requirements |
| 26 | Efficiency : 75 % or nearest as per OEM |
| 27 | Variable Speed Pumping System for Hot Water Pumps |
| 28 | Supply of VSPS for Secondary Hot water pumps in parallel operation having individual VFD with Pump Logic Controller mounted seperately in an enclosure, having necessary isolators, view panel , terminals , cooling fan and cabling ( power & control ) with M.S frame for mounting. VSPS shall consist of necessary differential pressure transmitters with control cabling to provide signal to VSPS Controller to make a complete system. The PID controller shall be able to communicate with BMS. VFD Panel (IP 41) comprising of I/C & O/G Feeders & associated accessories, VFDs, Pump Logic Controllers etc. shall be part of the above system |
| 29 | DP Sensors- included in above system |
| 30 | 2 nos VFD - 1 no Controller DPT 2 nos etc. |
| 31 | Expansion Joints (Flexible Connections)- Hot water pumps |
| 32 | Supply, installation, testing and commissioning of Expansion Joints (Mettalic flexible Connections) complete with accessories of the following sizes as per specification (Flexible connections to be used across Hot water Pumps): |
| 33 | 125 mm dia |
| 34 | Chilled and Hot Water Piping, Valves and accessories |
| 35 | CHILLED WATER PIPING : |
| 36 | Supply, laying, testing and commissioning of duly insulated as per below Chilled Water piping with Mild Steel \"C\" class pipe of size as mentioned below on exposed surface or connecting chiller, pump, etc. fabrication of bends, tees, reducers, shoe, support(MS angle support- clamp of suitable size with woods support for exposed surface) insulation of piping shall be with preformed pipe section of high density with minimum 24 Kg/Cu.mt. density of 30mm thick upto 50mm, 40mm thick upto 80mm and 50mm thick above 80mm and below 250mm with fire retardant quality poly UrethaneFoam(PUF) covered with vapour barrier, Tarfelt sheet, chicken wire mesh and finished using 26 gauge Al cladding.Note:- The pipes o sizes 150mm & below shall be M.S.\"C\" class as per IS: 1239 and pipes size above 150mm shall be heavy class of thickness minimum 7.0mm as per IS : 3589.This includes MS structure ifrequired(separate rate of items), MS / GI pipe sleeve of suitable higher size shall be provided wherever the pipes are crossing the walls/floors. |
| 37 | 200mm dia. |
| 38 | 150mm dia. |
| 39 | 125mm dia. |
| 40 | 100mm dia. |
| 41 | 80mm dia. |
| 42 | 65mm dia. |
| 43 | 50mm dia. |
| 44 | 40mm dia. |
| 45 | 25mm dia. |
| 46 | Insulated Valve |
| 47 | Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. |
| 48 | Y-STRAINER |
| 49 | Supply,Installation,Testing and Commissioning of CI bodyand S.S.Screen type Y-strainer of following size with compatible to MS pipe i/c all necessary support /hanger, etc. conform to PN-16 rating duly insulated as per Chilled Water Pipe as per specifications complete as required. |
| 50 | 150mm dia. |
| 51 | 125mm dia. |
| 52 | 100mm dia. |
| 53 | 80mm dia. |
| 54 | 65mm dia. |
| 55 | 50mm dia. |
| 56 | 40mm dia. |
| 57 | BUTTERFLY VALVE |
| 58 | Supply and fixing of butterfly valvescast iron body with SS 304 disc & PN-16 rating of following size (200mm to 400mm gear type with removable hand lever and below 200mm hand lever operated) including nut, bolt, flanges, gasket duty insulated as per Chilled Water Pipe as per specifications complete as required. |
| 59 | 200mm dia. |
| 60 | 150mm dia. |
| 61 | 125mm dia. |
| 62 | 100mm dia. |
| 63 | 80mm dia. |
| 64 | 65mm dia. |
| 65 | 50mm dia. |
| 66 | 40mm dia. |
| 67 | BALL VALVE |
| 68 | Supply and fixing of Gun Metal Ball valve of following size with socket and nipple of approved make conform to PN-10 ratingduly insulated as per Chilled Water Pipe as per specifications complete as required. |
| 69 | 50mm |
| 70 | 40mm |
| 71 | 32mm |
| 72 | 25mm |
| 73 | Motorized Butterfly Valve (UL Approved actuators) with CI Body, SS Disc, O - ring and minimum PN-16 pressure rating, conforming to BS 5155, IS 13095, with IP-55 actuator, capable of accepting upto 10V DC ,and upto 20 mA electric signal and providing similar transduced feedback output to control system ,BMS compatable as per engineering standards and specifications for Chilled water circulation including insulation as specified. |
| 74 | 200mm dia |
| 75 | 150mm dia |
| 76 | BALANCING VALVE |
| 77 | Supply,Installation,Testing and Commissioning of Balancing Valve with built in measuring facility with brass body, precise balancing double regulation type with protected out pipe insulation and PN-16 pressure rating duly insulated as per Chilled Water pipe as per specification complete as required. |
| 78 | 200mm dia. |
| 79 | 150mm dia. |
| 80 | 125mm dia. |
| 81 | 100mm dia. |
| 82 | 80mm dia. |
| 83 | 65mm dia. |
| 84 | 50mm dia. |
| 85 | 40mm dia. |
| 86 | NON RETURN VALVE |
| 87 | Supply,Installation,Testing and Commissioning of in position the following water type dual plate check valves with SS spring & pin C heck valves shall conform to PN-16 rating duly insulated as per Chilled Water Pipe as per specifications complete as required. |
| 88 | 150mm dia |
| 89 | Electronic, self-balancing, pressure independenttype dynamic balancing valve with integrated 2 way modulating control valve in a single accepting upto 10V DC and upto 20 mA electric signal and shall be with screwed end. The actuator shall be capable of provide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 25 Bar minimum as per engineering standards and specifications.for chilled water circulation including insulation as specified. |
| 90 | 100mm dia |
| 91 | 80mm dia. |
| 92 | 65mm dia. |
| 93 | 50mm dia. |
| 94 | 40mm dia. |
| 95 | TEMPERATURE GAUGE |
| 96 | Supply and fixing of Dial type Thermometer in SS finish of proportioning length with adjustable angle, direct reading includind thermowell, socketetc. Thermometer shall be suitable to read water temperature of range 0 deg C to 50 deg C complete as required. |
| 97 | PRESSURE GAUGE |
| 98 | Supply and fixing of 0 to 100 PSIG Dial type Pressure Gauge in position of 100mm dia. In SS finish with petcock valves(gun metal/brass) complete with pressure snubber, nipple etc. complete as required. |
| 99 | AIR PURGER |
| 100 | Providing, fixing,Testing and Commissioning of 25mm BSP automatic air purging valves having brass body complete with socket, ball valves etc.suitable for maximum operating pressure of 10 B ar all complete as per requirement. |
| 101 | Water flow meter |
| 102 | Probe type water flow meter to measure the flow in pipe line. The flow meter shall be provided with necessary fittings & electronic digital read out. |
| 103 | PRESSURISATION UNIT & EXPANSION TANK |
| 104 | Supply installation, testing and commissioning of Pressurization unit comprise of two nos (1 working + 1 stand-by) high pressure pumps of suitable pressure rating mounted on MS frame complete with interconnecting piping, isolation valves NRV Y-strainer pressure gauge pressure transmitter control panel electrical MCB and interconnecting wiring, control panel, pressurized expansion tank of adequate capacity with 16 bar pr rating, interchangeable EPDM-BUTYL rubber membrane, complete with safety resef valve pressure reducing valve and pressure gauge tank pressure rating to suit the system pressure adequately sized to compensate for water expansion due to operating temperature vanations, insulated and cladded with 26G-aluminium cladding, necessary valves fittings and accessories etc and as per tender specification |
| 105 | TEST POINTS |
| 106 | Providing fixing of 1 BSP PN10 test points having brass body with Nitrile sealing bushes along with attachable screwed cover as & where required complete with socket ball valves etc. suitable for maximum operating pressure of 10 Bar & maximum operating temperature of 110deg C etc all complete as per arrangement. |
| 107 | MAKE-UP TANK |
| 108 | Providing fixing of 1000 Its capacity Make-up tank of HDPE material complete with Makeup connection, Quick fill outlet connection, drain with valve overflow connection, air-vent, brass ball float valve etc along with necessary Structural supporting arrangement |
| 109 | AIR SEPARATOR |
| 110 | Supply andinstallation of Microbubble Air & Dirt Separator of 200mm dia. NB PN-16 with matching Flange and Gasket in chilled water pipe line including all accessories. The centrifugal air separator shall be manufactured from welded black mild steel plate, treated internally/externally with rust inhibiting primer to be complete with a set of supporting feet and all mounted on a small concrete base The air separator shall be complete with chilled water inlet & outlet flanged connections on periphery of tank ie, on circumference, arrangement in such way that the air entrapped in water separated with centrifugal action of water, adequately sized to achieve maximum air-seperation, automatic air vent provided on top of convex portion of tank and constructed for working pressure of 16 bar The air separator shall be insulated with 50 mm thick insulation to the specifications and cladded with 26G aluminum cladding. |
| 111 | Scale Guard(Chilled water Line) |
| 112 | Supply, Installation, Testing, Commissioning of Scale Guard to be fixed at the inlet of Chilled water unit of suitable flow rate to match the Chilled water pump capacity |
| 113 | GI PIPING FOR WATER SUPPLY / DRAIN |
| 114 | Supplying, laying / fixing,Testing and Commissioning of Un-insulated G.I. \"B\" class pipe of following sizes for water supply / drain water piping on surface including fabrication of bends, tees, reducers with support and fittings as per standard specification complete as required. |
| 115 | 50mm |
| 116 | 40mm |
| 117 | 25mm |
| 118 | INSULATED HOT WATER PIPING |
| 119 | Supply, laying, testing and commissioning of duly insulated as per below Hot Water piping with Mild Steel \"C\" class pipe of size as mentioned below on exposed surface or connecting Hot Water Generator, pump, etc. fabrication of bends, tees, reducers, shoe, support(MS angle support- clamp of suitable size with woods support for exposed surface) insulation of piping shall be with preformed pipe section of high density with minimum 24 Kg/Cu.mt. density of 30mm thick upto 50mm, 40mm thick upto 80mm and 50mm thick above 80mm and below 250mm with fire retardant quality poly UrethaneFoam(PUF) covered with vapour barrier, Tarfelt sheet, chicken wire mesh and finished using 26 gauge Al cladding. |
| 120 | Note:- The pipes o sizes 150mm & below shall be M.S.\"C\" class as per IS: 1239 and pipes size above 150mm shall be heavy class of thickness minimum 7.0mm as per IS : 3589.This includes MS structure ifrequired(separate rate of items), MS / GI pipe sleeve of suitable higher size shall be provided wherever the pipes are crossing the walls/floors. |
| 121 | 125mm |
| 122 | 100mm |
| 123 | 80mm |
| 124 | 65mm |
| 125 | 50mm |
| 126 | 40mm |
| 127 | Insulated Valve |
| 128 | Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the Hot water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. |
| 129 | Y-STRAINER |
| 130 | Supply,Installation,Testing and Commissioning of CI bodyand S.S.Screen type Y-strainer of following size with compatible to MS pipe i/c all necessary support /hanger, etc. conform to PN-16 rating duly insulated as per Hot Water Pipe as per specifications complete as required. |
| 131 | 125mm |
| 132 | 100mm |
| 133 | 80mm |
| 134 | 65mm |
| 135 | 50mm |
| 136 | 40mm |
| 137 | BUTTERFLY VALVE |
| 138 | Supply and fixing of butterfly valvescast iron body with SS 304 disc & PN-16 rating of following size (200mm to 400mm gear type with removable hand lever and below 200mm hand lever operated) including nut, bolt, flanges, gasket duty insulated as per Hot Water Pipe as per specifications complete as required. |
| 139 | 125mm |
| 140 | 100mm |
| 141 | 80mm |
| 142 | 65mm |
| 143 | 50mm |
| 144 | 40mm |
| 145 | BALL VALVE |
| 146 | Supply and fixing of Gun Metal Ball valve of following size with socket and nipple of approved make conform to PN-10 ratingduly insulated as per HotWater Pipe as per specifications complete as required. |
| 147 | 50mm |
| 148 | 40mm |
| 149 | 32mm |
| 150 | 25mm |
| 151 | Motorized Butterfly Valve (UL Approved actuators) with CI Body, SS Disc, O - ring and minimum PN-16 pressure rating, conforming to BS 5155, IS 13095, with IP-55 actuator, capable of accepting upto 10V DC ,and upto 20 mA electric signal and providing similar transduced feedback output to control system ,BMS compatable as per engineering standards and specifications for Hot water circulation including insulation as specified. |
| 152 | 125mm dia |
| 153 | BALANCING VALVE |
| 154 | Supply,Installation,Testing and Commissioning of Balancing Valve with built in measuring facility with brass body, precise balancing double regulation type with protected out pipe insulation and PN-16 pressure rating duly insulated as per Chilled Water pipe as per specification complete as required. |
| 155 | 125mm |
| 156 | 100mm |
| 157 | 80mm |
| 158 | 65mm |
| 159 | 50mm |
| 160 | 40mm |
| 161 | NON RETURN VALVE |
| 162 | Supply,Installation,Testing and Commissioning of in position the following water type dual plate check valves with SS spring & pin C heck valves shall conform to PN-16 rating duly insulated as per Hot Water Pipe as per specifications complete as required. |
| 163 | 125mm dia |
| 164 | Electronic, self-balancing, pressure independenttype dynamic balancing valve with integrated 2 way modulating control valve in a single accepting upto 10V DC and upto 20 mA electric signal and shall be with screwed end. The actuator shall be capable of provide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 25 Bar minimum as per engineering standards and specifications.for Hot water circulation including insulation as specified. |
| 165 | 100mm |
| 166 | 80mm |
| 167 | 65mm |
| 168 | 50mm |
| 169 | 40mm |
| 170 | TEMPERATURE GAUGE |
| 171 | Supply and fixing of Dial type Thermometer in SS finish of proportioning length with adjustable angle, direct reading includind thermowell, socketetc. Thermometer shall be suitable to read water temperature of range 0 deg C to 100 deg C complete as required. |
| 172 | PRESSURE GAUGE |
| 173 | Supply and fixing of 0 to 100 PSIG Dial type Pressure Gauge in position of 100mm dia. In SS finish with petcock valves(gun metal/brass) complete with pressure snubber, nipple etc. complete as required. |
| 174 | AIR PURGER |
| 175 | Providing, fixing,Testing and Commissioning of 15mm BSP automatic air purging valves having brass body complete with socket, ball valves etc.suitable for maximum operating pressure of 10 B ar all complete as per requirement. |
| 176 | Water Flow meter |
| 177 | Probe type water flow meter to measure the flow in pipe line. The flow meter shall be provided with necessary fittings & electronic digital read out. |
| 178 | Expansion Tank(Hot Water Line) |
| 179 | Precharged steel closed expansion tank for hot water line including insulation as specified with replaceable heavy duty butyl rubber bladder, mounting stand with all necessary system connection & charging valve connection to facilitate on site charging. Tank to meet ASME Boiler & pressure vessel code along with all necessary valves & fittings. |
| 180 | 500 Liters |
| 181 | Scale Guard (Hot Water Line) |
| 182 | Supply, Installation, Testing, Commissioning of Scale Guard to be fixed at the inlet of Hot water unit of suitable flow rate to match the Hot water pump capacity |
| 183 | Insulaed Hot Water Pipeline and Accessories as above |
| 184 | AIR HANDLING UNIT FOR CLEAN ROOM 100, ISO 5 (With VFD) |
| 185 | Supply, Installation, testing and commissioning of Eurovent certified factory fabricated double skin type Air Handling Units (BMS compatible) for above as per specifications given below:-AHU Construction:-It shall be made out of 0.8 mm pre -coated Galvanised steelsheet outside & 0.8 mm plain steel sheet inside with 40 mm thick PUF insulation factory injected between them by injection moulding m/c, with density not less than 40 kg/Cum between them. Drainpan(made out of 1.2mm stainless steel (SS Grade 304)sheet insulated with 19 mm think closed cell insulation nitrile rubber with thermal brake profile. AHUs Inner skin of panels & all parts which comes with air contact shall be minimum 22 G anodized aluminum. Necessary foundation required & antivibration pads shall be provided & cost for the same shall be included in this item. AHU to have UV disinfectant section. |
| 186 | Supply Air Stream:-1) Filter section consisting of pre filter,fine filter & HEPA filters in aluminum casing .Pre-filtersection shall bewith nonwoven synthetic media of 10micron particle size with an efficiency of 90%, fine/microvee filter section will be with filters of non woven synthetic media of 3 micron particle size of efficiency 99%. HEPA filter section with non woven synthetic media of 0.3 micron particle size with an efficiency of 99.997% at terminals. Cost of HEPA filter not to be included in this item only space shall be considered in AHU. The quoted price shall also include VCD, pressure differential indicator across Fine filters and HEPA filters with audible and visual alarms. 2) Plug Fans with aerofoil profile blade, CENTRIFUGAL type (with min. 70% efficiency) with motor (VFD compatible) ,volume control damper and duct flexible connection. The supply fan shall be provided with variable frequency drive and input/ output signal compatible to BMS system with TEFC drive motor of efficiency class IE3 suitable for 415±10% volts, 50Hz, 3Phase AC supply suitably designed for variable frequency drive applications shall be as per actual selection meeting other technical requirements.3) Coil Section- along with 6 Row deep chilled water coil with aluminum fins to suite TR required & 2 Row deep Hot water coil to suit required KW.4)Pan Type Humidifier complete as required(but not included)5) Discharge Plenum Section. |
| 187 | COIL-Copper tubes and Aluminum fins 12-13 fin./inch, Coil size shall be selected for air velocity of 350 ft./minute &velocity across filters at 350ft./minute.In Built VFD:- VFD designed for HVAC applications with built-in PID controller, control panel (keypad & display) , IP-54/55 enclosure for use on standard centrifugal plug fans. The display should be in alpha-numeric characters and programming facility should be in user-friendly HVAC terminology.VFD’s shall have built-in harmonic filters. The inter connecting wires between driver and MCC shall be included Item tabulated separately. Sound level 65 db. at the distance of 1.5 mtr. maximum. Necessary potential free contacts shall be provided for BMS operation.Isolators:Rubber Block type isolators below fan structure required to avoid vibration & direct contact of fan with AHU structureSleeves in Panels:Suitable Rubber bellow required for chilled and hot water pipes to avoid the direct contactAutomatic Control VFD Panel to control speed, 2 way valve for chilled water & Hot water along with all Necessary sensors.HEPA Filter shall be separately provided (Supply by Department) |
| 188 | Floor mounted 26500 CFM, 33.16 TR, 165 mm SP, Fan motor of meeting the functional requirement- Room- E BMF-1(AHU-1) |
| 189 | Floor mounted 8800 CFM, 12.70 TR, 150 mm SP, Fan motor of meeting the functional requirement.- Room- E BMF-2 /ASHER Room(AHU-2)- shall be negatively pressurised |
| 190 | Floor mounted 28500 CFM, 35.51 TR, 165 mm SP, Fan motor of meeting the functional requirement.- - Room- E BMF-3(AHU-3) |
| 191 | Floor mounted 42800 CFM, 46.66 TR, 165 mm SP, Fan motor of meeting the functional requirement. - Room- LPG+REPAIR(AHU-4) |
| 192 | Floor mounted 75300 CFM, 86.60 TR, 165 mm SP, Fan motor of meeting the functional requirement. - Room- O.C.+CORRIDOR CL 100(AHU-5) |
| 193 | AIR HANDLING UNIT FOR CLEAN ROOM 1000, ISO 6 (With VFD) |
| 194 | Supply, Installation, testing and commissioning of Eurovent certified factory fabricated double skin type Air Handling Units (BMS compatible) for above as per specifications given below:-AHU Construction:-It shall be made out of 0.8 mm pre -coated Galvanised steelsheet outside & 0.8 mm plain steel sheet inside with 40 mm thick PUF insulation factory injected between them by injection moulding m/c, with density not less than 40 kg/Cum between them. Drainpan(made out of 1.2mm stainless steel (SS Grade 304)sheet insulated with 19 mm think closed cell insulation nitrile rubber with thermal brake profile. AHUs Inner skin of panels & all parts which comes with air contact shall be minimum 22 G anodized aluminum. Necessary foundation required & antivibration pads shall be provided & cost for the same shall be included in this item. AHU to have UV disinfectant section. |
| 195 | Supply Air Stream:-1) Filter section consisting of pre filter,fine filter & HEPA filters in aluminum casing .Pre-filtersection shall bewith nonwoven synthetic media of 10micron particle size with an efficiency of 90%, fine/microvee filter section will be with filters of non woven synthetic media of 3 micron particle size of efficiency 99%. HEPA filter section with non woven synthetic media of 0.3 micron particle size with an efficiency of 99.997% at terminals. Cost of HEPA filter not to be included in this item only space shall be considered in AHU. The quoted price shall also include VCD, pressure differential indicator across Fine filters and HEPA filters with audible and visual alarms. 2) Plug Fans with aerofoil profile blade, CENTRIFUGAL type (with min. 70% efficiency) with motor (VFD compatible) ,volume control damper and duct flexible connection. The supply fan shall be provided with variable frequency drive and input/ output signal compatible to BMS system with TEFC drive motor of efficiency class IE3 suitable for 415±10% volts, 50Hz, 3Phase AC supply suitably designed for variable frequency drive applications shall be as per actual selection meeting other technical requirements.3) Coil Section- along with 6 Row deep chilled water coil with aluminum fins to suite TR required & 2 Row deep Hot water coil to suit required KW.4) Pan Type Humidifier complete as required(but not included)5) Discharge Plenum Section. |
| 196 | COIL-Copper tubes and Aluminum fins 12-13 fin./inch, Coil size shall be selected for air velocity of 350 ft./minute &velocity across filters at 350ft./minute.In Built VFD:- VFD designed for HVAC applications with built-in PID controller, control panel (keypad & display) , IP-65 enclosure for use on standard centrifugal plug fans. The display should be in alpha-numeric characters and programming facility should be in user-friendly HVAC terminology.VFD’s shall have built-in harmonic filters. The inter connecting wires between driver and MCC shall be included Item tabulated separately. Sound level 65 db. at the distance of 1.5 mtr. maximum. Necessary potential free contacts shall be provided for BMS operation.Isolators:Rubber Block type isolators below fan structure required to avoid vibration & direct contact of fan with AHU structureSleeves in Panels:Suitable Rubber bellow required for chilled and hot water pipes to avoid the direct contactAutomatic Control VFD Panel to control speed, 2 way valve for chilled water & Hot water along with all Necessary sensors.HEPA Filter shall be separately provided (Supply by Department) |
| 197 | Floor mounted 16300 CFM, 23.77 TR, 165 mm SP, Fan motor of meeting the functional requirement.- Room- Change room & Entry to 1K(AHU-6) |
| 198 | AIR HANDLING UNIT FOR CLEAN ROOM 1000, ISO 7 (With VFD) |
| 199 | Supply, Installation, testing and commissioning of Eurovent certified factory fabricated double skin type Air Handling Units (BMS compatible) for above as per specifications given below:-AHU Construction:-It shall be made out of 0.8 mm pre -coated Galvanised steelsheet outside & 0.8 mm plain steel sheet inside with 40 mm thick PUF insulation factory injected between them by injection moulding m/c, with density not less than 40 kg/Cum between them. Drainpan(made out of 1.2mm stainless steel (SS Grade 304)sheet insulated with 19 mm think closed cell insulation nitrile rubber with thermal brake profile. AHUs Inner skin of panels & all parts which comes with air contact shall be minimum 22 G anodized aluminum. Necessary foundation required & antivibration pads shall be provided & cost for the same shall be included in this item. AHU to have UV disinfectant section. |
| 200 | Supply Air Stream:-1) Filter section consisting of pre filter,fine filter & HEPA filters in aluminum casing .Pre-filtersection shall bewith nonwoven synthetic media of 10micron particle size with an efficiency of 90%, fine/microvee filter section will be with filters of non woven synthetic media of 3 micron particle size of efficiency 99%. HEPA filter section with non woven synthetic media of 0.3 micron particle size with an efficiency of 99.997% at terminals. Cost of HEPA filter not to be included in this item only space shall be considered in AHU. The quoted price shall also include VCD, pressure differential indicator across Fine filters and HEPA filters with audible and visual alarms.2) Plug Fans with aerofoil profile blade, CENTRIFUGAL type (with min. 70% efficiency) with motor (VFD compatible) ,volume control damper and ductflexible connection. The supply fan shall be provided with variable frequency drive and input/ output signal compatible to BMS system with TEFC drive motor of efficiency class IE3 suitable for 415±10% volts, 50Hz, 3Phase AC supply suitably designed for variable frequency drive applications shall be as per actual selection meeting other technical requirements.3) Coil Section- along with 6 Row deep chilled water coil with aluminum fins to suite TR required & 2 Row deep Hot water coil to suit required KW.4) Pan Type Humidifier complete as required(but not included)5) Discharge Plenum Section. |
| 201 | COIL-Copper tubes and Aluminum fins 12-13 fin./inch, Coil size shall be selected for air velocity of 350 ft./minute &velocity across filters at 350ft./minute.In Built VFD:- VFD designed for HVAC applications with built-in PID controller, control panel (keypad & display) , IP-65 enclosure for use on standard centrifugal plug fans. The display should be in alpha-numeric characters and programming facility should be in user-friendly HVAC terminology.VFD’s shall have built-in harmonic filters. The inter connecting wires between driver and MCC shall be included Item tabulated separately. Sound level 65 db. at the distance of 1.5 mtr. maximum. Necessary potential free contacts shall be provided for BMS operation.Isolators:Rubber Block type isolators below fan structure required to avoid vibration & direct contact of fan with AHU structureSleeves in Panels:Suitable Rubber bellow required for chilled and hot water pipes to avoid the direct contactAutomatic Control VFD Panel to control speed, 2 way valve for chilled water & Hot water along with all Necessary sensors.HEPA Filter shall be separately provided (Supply by Department) |
| 202 | Floor mounted 35600 CFM, 58.85 TR, 165 mm SP, Fan motor of meeting the functional requirement.- Room- all CL-10000(AHU-7) |
| 203 | AIR HANDLING UNITES (1 STAGE FILTERATION) FOR COMMON SITTING AREAS -With VFDs |
| 204 | Supply, Installation, testing and commissioning of Eurovent certified factory fabricated double skin type Air Handling Units (BMS compatible) for Waiting&Public areas asperspecifications givenbelow:-AHU Construction:-Itshall be made out of 0.8 mm pre -coated Galvanized steelsheet outside & 0.8 mm plain steelsheet inside with 40 mm thick PUF insulation factory injected between them by injection moulding m/c, with density not less than 40 kg/Cumbetweenthem.Drainpan(made out of 1.2mm stainless steel (SS Grade 304)sheet insulated with 19 mm think closed cell insulation nitrile rubber with thermal brake profile. AHUs Inner skin of panels & all parts which comes with air contact shall be minimum 22 G anodized aluminum. Necessary foundatio nrequired & antivibration pads shall be provided & cost for the same shall be included in this item. AHU to have UV disinfectant section. 1) Filter section consisting of pre filter.Pre-filtersection shall be with non woven synthetic media of 10 micron particle size with an efficiency of 90%2) Plug Fans with aerofoil profile blade (with min. 70% efficiency) with motor(VFD compatible), volume control damper and duct flexible connection. The supplyfan shall be provided with variable frequency drive and input/output signal compatible to BMS system. Squirrel cage induction motors suitable for 415±10% volts, 50Hz, AC supply & high efficiency (IE-3 Efficiency), H.P of motor shall be as per actual selection meeting other technical requirements.3) 6 Row Deep Cooling Coil, with aluminum fins.4) Discharge Plenum Section.COIL-Coppertubes andAluminum fins 12-13 fin./inch, Coilsize shall be selected for air velocity of 350 ft./minute &velocity across filters at 350 ft./minute. Sound level 65 db. at the distance of 2 mtr.(maximum). Necessary potential free contacts shall be provided for BMS operation |
| 205 | Isolators:Rubber Block type isolators below fan structure required to avoid vibration & direct contact of fan with AHU structureSleeves in Panels:Suitable Rubber bellow required for chilled and hot water pipes to avoid the direct contactAutomatic Control VFD Panel to control speed, 2 way valve for chilled water & Hot water along with all Necessary sensors. |
| 206 | Floor mounted,5500 CFM, 9.75TR, 50 mm SP,Fan motor of meeting the functional requirement. Room- sitting area (AHU- 8 & 9) |
| 207 | VFDs -Variable Frequency Drives for AHU |
| 208 | Supply, installation, testing & commissioning of VFDs.VFD designed for HVAC applications with built-in PID controller, control panel (keypad & display), IP-54/65 enclosure (for outdoor applications) & IP-20 enclosure (for indoor applications) for use on AHU fans. The display should be in alpha-numeric characters and programming facility should be in user-friendly HVAC terminology. VFD’s shall have built-in harmonic filters with THD less than 5%. VFD panel to be provided with digital display showing necessary parameters. The inter connecting wires between driver and MCC shall be included. Necessary transformer, power adapters, sensors, relay etc. as required for satisfactory operation shall be in the scope of VFD supplier. It should be BMS Compatible.DP Sensors- included in above system |
| 209 | 3 nos VFD - 1 no Controller DPT 2 nos etc |
| 210 | Thermostat / Humidistat for AHU (Proportional type ) |
| 211 | Supply, installation, testing and commissioning of latest generation digital display type BMS compatible thermostat / humidistat with controller for cool/heat application suitable for two/four pipe system & humidistat suitable for working with humidifier and hot water coil control valves for various air handling Units. The thermostat shall have provision of setting of space temperature and display of the same. The humidistat shall have provision of setting space RH and display of the same. The quoted price of thermostat / humidistat shall include the cost of 20mm MS conduits, control cabling, MS Box etc. asrequired. The cost quoted shall be excluding the control valves and humidifier. It shall include all accessories ,mountings, wiring between thermostat & unit, terminations etc.(BMS Compatibility to be provided). |
| 212 | Display panel |
| 213 | Display panel showing temperature, RH, cleanliness level, velocity, with auto feedback control which can rectify errors itself. |
| 214 | HUMIDIFIERS |
| 215 | Supply, Installation, Testing and Commissioning of Pan Type Humidifier made out of 2 mm SS-304 sheet and tank to be adequately sized based on KW capacity The Humidifier comprise of connection for make-up water, over flow and drain. sight glass on the tank to see inside the tank inside marine light Electrical panel, top of tank provided with nozzle for the outlet of steam, top of the tank is openable with sufficient numbers of nuts and bolts as per standards Humidifier is air tight and leak proof and insulated with fibre glass & finished with 26gauge aluminium cladding sheet Electrical panel is made out of 16 gauge CRCA sheet both sides powder coated, electrical panel consist of MCB, Contractor, low water level cut-out, heating thermostat for individual bank high temperature cut-off, humidistat, fault indicating lamp, heaters etc and internally wired |
| 216 | Humidifier capacity 6 kW(8.07 Kg/hr saturated steam) |
| 217 | Humidifier capacity 9 kW(12.10 Kg/hr saturated steam) |
| 218 | Air Distribution |
| 219 | Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports with vibration isolator etc. as per approved drawings and specifications of following sheet thickness complete as required |
| 220 | 24 Gauge ( Thickness 0.63mm) |
| 221 | 22 Gauge (Thickness0.8mm) |
| 222 | 20 Gauge (Thickness1.0mm) |
| 223 | Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports with vibration isolator etc. as per approved drawings andspecifications of following sheet thickness complete as required. |
| 224 | 24 Gauge (Thickness 0.63 mm sheet) |
| 225 | 22 Gauge (Thickness 0.80 mm sheet) |
| 226 | 20 Gauge (Thickness 1.00 mm sheet) |
| 227 | Supply, installation, testing & commissioning of thermal insulated flexible ducting for HEPA filters. All ducting should be sealed with silicon sealant. Duct should be UL 181 CLASS I AIR DUCT LISTED AND LABELLED WITH NFPA 90A & 90B with double lamination of tough polyester which encapsulates steel helix wire forms the air tight inner core, double layer core wrapped in a multiple thickness of fiberglass wool with R Value 4.2 , Green guard certification of fiberglass wool must. , Reinforced and sheathed in a rugged and durable tridirectionally reinforced matlized polyester jacket. Strapping the flexible duct connections with flexible duct strap ties following sizes duly supported at regular interval as per site requirement etc. complete as required as per specifications. |
| 228 | 200mm dia. |
| 229 | Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications |
| 230 | Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required |
| 231 | Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core |
| 232 | Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core. |
| 233 | DUCT THERMAL INSULATION |
| 234 | Supplying & Fixing of thermal insulation on ducts with approved sample of Nitrile rubber insulation of following thickness with density 50 Kg Cum 10% applied with appropriate recommended proper adhesive and sealed with 3 wide BOPP tape on all longitudinal transverse joints duly cladded with 28G SS Sheet complete as per specifications. |
| 235 | 19mm |
| 236 | 25mm |
| 237 | DUCT ACOUSTIC LINING |
| 238 | Supplying & Faxing of acoustic lining with 25mm thick fibre glass insulation of 32 kg/cum density & finished with 2 layers of RP Tissue Paper and finahed with 280 Aluminium perforated sheet with nut bolts all complete as per approved drawings & specifications. |
| 239 | FLEXIBLE CANVASS CONNECTION |
| 240 | Supply installation testing and commissioning of flanged end connection type Fire Retardant nonporous double layer flexible canvass connection between each equipment and ducting as required all complete as per approved drawings & specifications. |
| 241 | VOLUME CONTROL DAMPER |
| 242 | Supply, installation testing and commissioning of opposed blade flange type Low Leakage Volume Control Damper (suitable for modulating Actuator in extruded aluminium construction within ducts to be provided with opposed blade aerofos blades & suitable links levers and quadrants suitable for manual & automatic control of volume of air flow and for proper balancing of the air distribution system Axle shall be 12mm SS with heavy guage quadrant with position indicators along with neoprene gasket as per approved shop drawings(Rate shall be quoted without Actuator) |
| 243 | MOTORIZED FIRE DAMPER |
| 244 | Supply installation testing and commissioning of motorized combination fire and smoke damper(spring return type) in GI construction and approved for 120 minutes rated as per UL-555S- 1995 and CBRI and as per the specifications as detailed earlier in the relevant sections The fire damper shall be complete with electronic temperature sensor and electrically operated actuator. The fire dampers shall be located in the supply return air ducts at all fire rated crossovers (shaft/walls etc) as & where required of requisite sizes along with its control panel The control panel will be such located that the reset can be easily done These combination smoke and fire dampers shall be interlocked with the building management system for fire detection HVAC and shall trip/close in the event of fire smoke in the respective zone |
| 245 | Providing and fixing Bare Fire Dampers with sleeve and fixing arrangement |
| 246 | Control panel |
| 247 | Providing and fixing Control panel including Electrical spring type actuator onfoff actuator mechanical for proof open and close 2-position operation only, suitable for control voltages 24VAC/230VAC power supply manual over nide and lock in switch with smoke sensor and remote indication of the Fire damper position. |
| 248 | Providing and fixing Interconnecting wiring for the fire alarm system with the AHU and the smoke dampers. |
| 249 | FRESH/EXHAUST AIR LOUVERS |
| 250 | Supply installation testing commissioning and balancing of Powder coated extruded aluminium Fresh / Exhaust Air Louvers with opposed blade fange type low leakage Volume Control Damper (suitable for modulating Actuator) in extruded aluminum construction to be provided with opposed blade aerofoil blades & suitable links levers and quadrants suitable for manual & automatic control of volume of air flow and for proper balancing of the air distribution system. Bird Screen Mesh and Fresh Air Filters with non woven synthetic media of 10 micron particle size with an efficiency of 90% (EU4) all complete as per approved drawings & specifications. |
| 251 | Precision Air Conditioning & Split Acs: |
| 252 | PRECISION AIR-CONDITIONING SYSTEM |
| 253 | Supply Installation testing and commissioning of Precision Package Air conditioning system as per specifications given below.Floor Mounted Bottom discharge Air Cooled DX type Precision Air conditioners of 11 TR actual cooling capacity unit which work on individual circuit Gross Total cooling Capacity at return air temperature of 23 deg CDB 1C variation in set value) & 45 % RH (+5% variation in set value) and Outdoor Ambient Condition 42 Deg C with R410a/R407c Refrigerant Gas Size WxDxH 1800 mm x 1000 mm x 2000 mm approximate Supply air temperature Below 20 deg C Set value for return air temperature between 18\"C to 27°CThe indoor unit shall comprise of Scroll Compressor DX type with totally Double skin sandwitched panels on all four side with 20 mm 32 Kg/ cum Glass wool internal insulation Indoor and outdoor unit body matenal GI powder coated with minimum 18 SWG Evaporator Fan complete with Backward curved type with EC motor 60kW Actual Capacity@ 12000 CFM at 40mmwg External static pressure. Evaporator DX Cooling Coil with hydrophilic coating Microprocessor controllers Electronic Expansion valves Driers G4 Filter Suction and Discharge piping internal power and Control wining Crankcase heaters Humidifiers Heaters, HP/LP Cut- outs Power and Control contactors filters, Liquid receiver water leak detector for unit and Other Electrical accessories.The Air-cooled Outdoor Condenser unit shall comprise of Condenser fans & motor Condenser cooling coil (Copper coil with aluminium fins) isolator switch The Air cooled condenser shall be with fan speed regulator.The unit shall be suitable for operation on 375 to 455 volts 50 Hz 3 Phase 4 Wire AC supply aching should be having individual display panel which shaii display date, time, actual & set values, operating conditions, signal faults collective faults, limiting values and PAC wellness atarm service alarm to reduce the down time and unit memory shall hold minimum 200 most recent events with ID numbers, time and date stamp for each event. |
| 254 | Precision Package Air conditioning unit controller for synchronising the multiple numbers of identical units towards as single system with required communication & power cables and can be used for timely rotation as required Dunng breakdown of any of unit remaining units should work normal with out disturbing output condition |
| 255 | REFRIGERANT GAS |
| 256 | Supply and charging of R410a/R407c refrigerant gas in above system as complete and as per directions given by Engineer in charge |
| 257 | MS STAND FOR INDOOR UNIT |
| 258 | Suoply and fixing of MS stand for 11 TR precision Package Air conditioning unit indoor as per site requirement and as instructed by Engineer-in-charge. |
| 259 | MS STAND FOR OUTDOOR UNIT |
| 260 | Supply and fixing of MS stand for 11 TR precision Package Air conditioning unit indoor as described above & as per site requirement and as instructed by Engineer-in-charge. |
| 261 | REFRIGERANT PIPING |
| 262 | Supply installation testing and commissioning for pair required hard drawn copper piping of required dia as per design (5/8 & 7/8\" or More) for Precision Air conditioning unit for gas and liquid (Suction & discharge) including necessary pipe joints & branching for the above ODU & IDU with 19 mm thick Nitrile rubber insulation along with structural supports for laying the piping & required accessories Refrigerant piping should be laid on ladder type cable tray complete as per direction of Engineer in charge Length of copper pipe line laid at site as per final approved layout shall be measured for payment Rate shall be inclusive of the cost of all the materials joints MS trays structural supports etc all complete as per direction of Engineer in charge. |
| 263 | EXTENDED REFRIGERANT PIPING KIT |
| 264 | Supply installation testing and commissioning of Extended pipe kit as per site requirement etc all complete as per direction of Engineer in charge |
| 265 | DRAIN PIPING |
| 266 | Supply installation, testing and commissioning of Gt B-Class) Drain piping of 40 mm inner dia with 6 mm thick nitrile rubber insulation along with support, joints & required accessones. |
| 267 | WATER PIPING |
| 268 | Supply installation testing and commissioning CPVC water piping of 25 mm inner dia along with support joints & required accessories for humidifier etc all complete & as per direction of Engineer in charge |
| 269 | WEATHERPROOF ISOLATOR |
| 270 | Supply, installation, testing and commissioning of 40 Amp weather proof isolator etc all complete & as per direction of Engineer in charge |
| 271 | ELECTRICAL PANEL |
| 272 | Supply erection, testing and commissioning of main LT Panel of the following extensible cubicle type floor/ wall mounting Powder coated, modular compartmentalized, dead front, dust and vermin proof floor mounting 2 mm thick sheet steel clad switchboard suitable for use at 415 volts 3 phase 4 wire 50 cycle system and to withstand a symmetrical fault level of 25 MVA at 415 volts (35 kA) with indication lamps accessories etc as required and complete with following incoming and outgoing switchgears with protection and metering and etc as per specification and schematic diagram. |
| 273 | INCOMING |
| 274 | 1No 160 Amp 36 KA 4P MCCB with thermal magnetic release having over current, short circuit protection Each incomer shall be complete with following3 Nos Cast resin current transformers of 160/5 ratio Class 10 for metering Voltmetre (0-500V) with Selector SwitchAmmetre (0-200A) with Selector SwitchThree phase indicating lamps (LED type) with MCBMultifunction meter showing voltage, Amperage etc |
| 275 | BUSBAR |
| 276 | Electrolytic high conductivity aluminium three phase and neutral busbars rated at 200 Amp having a maximum current density of 0.8 amp per sq mm suitable to withstand symmetrical fault level of 25 MVA at 415volts. The neutral busbar is to be of 100% capacity. |
| 277 | OUTGOING |
| 278 | 03 Nos 63 Amp 18 KA 4P MCCB complete with Thermal-magnetic release having overcurrent, short circuit protection |
| 279 | The Panel shall be complete with all interconnections, risers internal wiring, labels etc complete as required. |
| 280 | Power Cable |
| 281 | Supply, laying and commissioning of Power Cabling of copper for Indoor / Outdoor units to be suitable laid in PVC conduit as per site requirement including and terminations. |
| 282 | 4C X 16 Sq.mm. (copper)- from outdoor to a/c panel |
| 283 | 3C X 2.5 Sq.mm. (copper)- from indoor to outdoor |
| 284 | 3.5C X 95 Sq.mm. Al armoured (Aluminium) |
| 285 | Cable End Termination |
| 286 | Supplying & Providing of following size cable end terminations for the above cable with single compression type SS gland, bi-metalic heavy duty lugs, Insulation tape, Identification tags, etc. including end termination and earthing of gland. |
| 287 | 4C X 16 Sq.mm. (copper)- from outdoor to a/c panel |
| 288 | 3C X 2.5 Sq.mm. (copper)- from indoor to outdoor |
| 289 | 3.5C X 95 Sq.mm. Al armoured (Aluminium) |
| 290 | Control Cable |
| 291 | Supply, laying and commissioning of Control Cabling 2C x 1.5 Sq.mm. copper cable for communication between indoor and outdoor units to be suitable laid in PVC conduit as site requirement. |
| 292 | Air Conditioning System |
| 293 | Supply installation, testing and commissioning of 1.5TRinverter controlled Split AC of 5 star rating of make VOLTAS/DAIKIN/ BLUSTAR or equivalent with complete standard fittings. Other specification as per GeM quotation attached. |
| 294 | Supply of MS powder coated stand for split airconditioners including all accessories etc. all complete. |
| 295 | Supply installation, testing and commissioning of Soft Copper Refrigerant Piping of 18 SWG for cassette units of following sizes with necessary supports, fittings interconnecting the liquid and suction lines between the aircooled outdoor unit and the indoor unit. Both supply and return line between the aircooled outdoor unit and the indoor unit. Both the suction and return line shall be insulated with 13mm thick nitrile rubber tubes as insulation material and shall be covered with treated woven fibre reinforced covering etc. complete. |
| 296 | 1/4\"Pipe |
| 297 | 5/8\" Pipe |
| 298 | Supply installation, testing and commissioning of CPVC (Chlorinated Poly Vinyl Chloride) pipes condensate drain piping insulated using 9mm thick nitrile rubber tubes including fittings and supports as per the specifications. |
| 299 | 25mm dia |
| 300 | Supply and laying following size of FRLS PVC insulated copper conductor single core cable in the existing surface / recessed steel / PVC conduit as required. |
| 301 | 4C X 2.5 Sq.mm. (copper) |
| 302 | INTEGRATED BUILDING MANAGEMENT SYSTEM |
| 303 | Supply, Installation, Testing and commissioning of the following equipments forming part of the Integrated Business Management System complete with all accessories and components required for proper funcing of the system all as specified. |
| 304 | BMS WORK STATION |
| 305 | Supply, Installation, Testing and commissioning of operator work station BMS Machine complete as specified including the following accessories.Operator Server/Workstation with PC having Intel Quad Core precessor (Latest Technology), Windows 2010 SP2 or above operating System, including serial ports(RS232) and USR ports and following accessories etc. all as specified. RAID 5 category redundancy for power supply of PC.16 GB of DDR3 RAM memory1 TB of HDDDVD combo drive40\" TED screen colour monitorx 02 SetOptical Mouse with 2 mouse padsStandard key boardLatest Windows Operating System(Windows NT)1 GBPS LAN cardLatest laser jet full duplexprinter A4 size with WIFIAnti virus |
| 306 | GRAPHICAL INTERFACE SOFTWARE |
| 307 | Supply, Installation, Testing and commissioning of licenced copy of single centralised Web Based Graphical interface software. The system should be accessible from anywhere on LAN or WAN OR Ethernet without additional licences. The communication protocol shall be one of the industry Standard Open Protocols such as BACnet, Modbus & LON works etc. Software shall have vector graphics, should be scalable and software should be integrable with access control, CCTV, VMS seamlessly to generate a holistic view with unlimited soft points licensing & unlimited users with 5 simultaneous users. |
| 308 | THIRD PARTY INTEGRATION |
| 309 | Provision of Third party Integration required UL/BTL listed Gateway / Open Protocol Software from same OEM as DDC controllers for integrating the third party system communicating on one of the Standard Open Protocols such as BACnet, MODBUS, M-Bus etc. Vendor to consider required Nos. of integrators for qty\"s mentioned in IO summary. Gateway shall be server grade with at least 3 GB memory to store data integration of following services should be considered.i) Chillersii) Pumpsiii) Hotwater Generatoriv) Access Controlv) Fire Alarm, Detection and Gas Suppression Systemvi) CCTVvii) Energy Metersviii) AHUix) Scrubbersx) RO & ETPxi) UPS Power Quality Analyzer |
| 310 | NETWORK SWITCH |
| 311 | Supply, installation, testing and commissioning of Layer 2/3 managed switch with 16 or 24 ports(RJ-45) port. The switch shall have 2 RSTP enabled ports to communicate with other switches to built a ring topology network on CAT6 A cable. The switch shall have 1 GB port to communicate with other switches including Passive components inbuilt 2 SFP ports including SFP modules,rack mountable, SMPS power supply & other termination accessories (Like Pigtails/LIUs/ Convertors/Splicing equipment, Patch panel, Patch Cord, Etc) complete as per specifications and as required for BMS DDC Panel Networking. The switch to switch distance shall not exceed beyond 80meters. Vendor to decide the quantity of network switches based on their network design. |
| 312 | PORTABLE OPERATION TERMINAL |
| 313 | Supply,Installation,Testing & Commissioning of displays for memic panel 15\" touch screen display with HMI display from BMS server. The HMI display should work with windows 10 with complete authorisation authentication. HMI should have all features so that of main BMS system. |
| 314 | IP BASED DDC CONTROLLER |
| 315 | Supply, Installation, Testing & Commissioning of IP Based Controllers with I/O modules as per I/O summary. The controller shall be UL/BTL Listed capable of networked operations to exchange data with other controllers and workstations. The DDC Controllers shall be web enabled, RAM of min 3 GB and processor speed of min 1.2 GHz.All DDC Controllers and accessories shall be housed in a vandal proof, lockable control panel housing conforming to IP55 standard. The housing will be pre-wired all as per specifications and of reputed make only. Apart from the controllers, the enclosures shall house the terminal blocks, load relays and associated equipments. The internal wiring in the enclosure shall be factory wired. The packaging shall be such that complete installation of the field equipments and field wiring can be done prior to the installation of the electronics. The controller shall be independent in operation and the failure of any other device / controller or the operator workstations shall cause any disruption to function of the rest of the system. The DDCControllers shall have the facility to implement the user modifiable time schedules as daily, weekly, monthly, annual temporary schedules.The DDC controllers would \"reboot\" automatically on resumption of power. Controoler shall not require manual intervention for the reboot of the controller software.The DDC controllers shall have integration facility with at least 2 ports of integration.The DDC controllers shall have provision for 15% IO ports. |
| 316 | HVAC |
| 317 | DDC for Plant Manager includes Chiller, Primary, Secondary, Hot Water Pumps. |
| 318 | DDC for Hot Water Generator and Pumps. |
| 319 | DDC for Air Handling Units (Max 1 AHU per DDC) |
| 320 | Electrical System |
| 321 | DDC for Building LT Panel |
| 322 | DDC controllers for AccessControl System |
| 323 | DDC controllers for CCTV System |
| 324 | DDC controllers for Fire Alarm & Gas Supression System |
| 325 | Field instruments |
| 326 | Supplying, installing, testing and commissioning of the following various electromechanical field devices, sensors, transducers, transmitters complete with all accessories etc. all as per specifications. |
| 327 | Supply,Installation,Testing & Commissioning of Immersion temperature sensor100mm Pt1000 with Brass Thermowell for CHW |
| 328 | Supply, Installation, Testing & Commissioning of Outside air temperature+humidity sensors for measuring outside air temperature. It should be provided with sun sheild andrain protection. |
| 329 | Supply, Installation, Testing & Commissioning of Differential Pressure for AHU run status and filter status. |
| 330 | Supply, Installation, Testing & Commissioning of Differential Pressure Transmitter for pumps |
| 331 | Supply, Installation, Testing & Commissioning of Differential Pressure Transmitter for clean room |
| 332 | Supply, Installation, Testing & Commissioning of Modulating Actuator for VCD |
| 333 | Supply, Installation, Testing & Commissioning of Water Flow Switch |
| 334 | Supply, Installation, Testing & Commissioning of Duct Temperature & Humidity Sensor/ transmitter for AHUs. |
| 335 | Supply,Installation,Testing & Commissioning of Differential pressure switch for Blower Status (Pa Range 50…300 Pa) |
| 336 | Supply, Installation, Testing & Commissioning of Ultrasonic Water Flow Meter- Dia. Size. 350 mm |
| 337 | Supply, Installation, Testing & Commissioning of PH Analyser |
| 338 | Supply, Installation, Testing & Commissioning of TDS Analyser |
| 339 | Supply, Installation, Testing & Commissioning of Tri-Level Switch/Trandmitter forwater tanks High-Medium-Low level |
| 340 | Supply, Installation, Testing & Commissioning of CO2 sensor |
| 341 | Supply, Installation, Testing & Commissioning of O2 sensor |
| 342 | Supply, Installation, Testing & Commissioning of Occupancy Sensor |
| 343 | Supply, Installation, Testing & Commissioning of Voltage Transducer |
| 344 | Supply, Installation, Testing & Commissioning of Current Transducer |
| 345 | Cabling and Conduiting |
| 346 | Supplying, laying,termination, testing and commissioning of signal cables. (2 core x 1.5 Sq.mm), PVC insulated, Shielded tinned copper conductor cable. |
| 347 | Supplying, laying,termination, testing and commissioning of signal cables. (4 core x 1.5 Sq.mm), PVC insulated, Shielded tinned copper conductor cable. |
| 348 | Supplying,laying,termination,testing & commissioning of UTP 4 pair CAT6ALAN unarmoured Cables with required accessories like RJ45 connector etc. |
| 349 | Supply, Installation, Testing & Commissioning of MS Conduit 25 mm for Signal & Communication Cable. |
| 350 | Supply, Installation, Testing & Commissioning of GI Flexible |
| 351 | Supplying, installing, testing and commissioning of 2 mm thick GI perforated cable trays of the following sizes complete with angle iron supports/hanging arrangement etc. |
| 352 | 100 x 50 x 1.6 mm |
| 353 | 200 x 50 x 1.6 mm |
| 354 | ACCESS CONTROL SYSTEM |
| 355 | Supply, Installation, testing and commissioning of following equipments forming part of the Access Control System complete with all accessories and components required for proper functioning of the system all as specified. |
| 356 | ACS WORKSTATION |
| 357 | Supply, Installation, testing and commissioning of Processor Intel Core i5 -5550U or higher, Intel Chipset , Minimum 16-GB DDR3 SDRAM 1600MHZ, Minimum 1 TB SATA 3 Gbps HDD , 7200rpm HDD Capacity, Minimum 2 GB Nvidia Graphic Card, Integrated 100/1000 Mbps Ethernet Controller, 43\" LED full HD monitor or Higher & wireless Keyboard & mouse with required Windows, IP Web cameras. The Workstation shall be able to compatible / communicate with BMS |
| 358 | ACS MANAGEMENT SOFTWARE |
| 359 | Supply, Installation, testing and commissioning of Access Control Software which is a modular, networked access control and alarm monitoring system, comprised time scheduling & attendance management , capable of handling large proprietary corporations with alarm monitoring, email mobilization, BAS integration. The system shall assure long time performance, cost effective upgrade capability and allow for easy expansion or modification of inputs, outputs and remote control stations. Software shall be NIST certified and have AES-256 encription. |
| 360 | ACS CONTROLLER |
| 361 | Supply, Installation, testing and commissioning of IP Based 2 Door Reader Controller expandable upto 128 doors via expansion modules which supports all major reader technologies such as Wiegand or Encripted RS-485 and biometrics on the same network. The Door Controller will allow four readers per system over RS-485/RS-232 or Ethernet/LAN connection. Controller shall have Users memory 4 million user & offline event 50000. The same shall include fail safe/fail secure lock jumper, power supply, housing, in-built battery bachup as per technical specification with all mountingaccessories, power supply and housing complete as required. Controller shall have min. 7 inputs & 2 outputs on board. Controllers shall be supplied with UL listed power supply that will power controller and expansion modules and communicate info Such as Battery status , communication status etc. |
| 362 | DOOR EXPANSION MODULES |
| 363 | Supply, Installation, testing and commissioning ofDoor Expansion Modules provides upto 2 Doors inputs and 2 locking device outputs. It should be designed with industry standard DIN Rail mounting 2 Readers ports configurable for either Wiegand or RS-485 reader operations per technical specification with all mounting accessories power supply & housing complete as required. |
| 364 | SMART CARD READER |
| 365 | Supply, Installation, testing and commissioning ofCE/UL Approved Blutooth/NEC enabled smart card reader, IP-65 protection, having range upto 50mm with features such as clone card detection as per technical specifications. |
| 366 | SMART CARD |
| 367 | Supply of Smart Cards for 13.56Mhz/125Khz radio frequency |
| 368 | BIOMETRIC READER |
| 369 | Supply, Installation, testing and commissioning of CE approved Biometric Card reader having 4 MB flash memory upto 10000 finger print reader template capacity. |
| 370 | SINGLE EM LOCK |
| 371 | Supply, Installation, testing and commissioning of Single Leaf Electromagnetic lock, 600 lbs along with magnetic contact. UL certified as per technical specifications. |
| 372 | DOUBLE EM LOCK |
| 373 | Supply, Installation, testing and commissioning of Dual Leaf Electromagnetic lock, 600 lbs along with magnetic contact. UL certified as per technical specifications. |
| 374 | PANIC BAR |
| 375 | Supply, Installation, testing and commissioning of Panic Bar with Local Scare Alarm & other accessories as required. |
| 376 | PUSH BUTTON |
| 377 | Supply, Installation, testing and commissioning of Exit Push with required accessories as per technical specifications. |
| 378 | EMERGENCY BREAK GLASS |
| 379 | Supply, Installation, testing and commissioning of Emergency Break Glass with required accessories as per technical specifications. |
| 380 | CABLES |
| 381 | Providing and laying of cables, weatherproof, outdoor grade and as per BIS standard. |
| 382 | 8 core 20 to 22 AWG, 6 or 8 conductor, standard, shielded armoured cable with required accessories. |
| 383 | 2 core 20 to 22 AWG, 2 conductor, standard, shielded armoured cable with required accessories. |
| 384 | CCTV SYSTEM |
| 385 | OUTDOOR CAMERA |
| 386 | Supply, Installation, testing and commissioning of 2 MP, 100P, 2.8-12mm auto vari-focal lens, 60mtr. Bullet Camera, Built-in essential video analysys, full configurable qaud-stream, two-way audeo and audeo alarm , Tamper and motion detection, MicroSD card slot upto 2TB for edge recording cloud based service. true day-night switching, 85 dB WDR, H.264/H-265/M-JPEG video compression white balance, BLC, Intelligent Defog, iDNR, privacy masking, 12VDC/POE, IP-67, IK10 UL Certified Operating Temperature -10 dec C to 50 deg C and 3 years warranty. Rest technical specification as per attached sheet. |
| 387 | INDOOR CAMERA |
| 388 | Supply, Installation, testing and commissioning of 2 MP, 3-10mm auto vari-focal lens, 30mtr. IR Indoor Dome Camera, Built-in essential video analysys, full configurable qaud-stream, built-in microphone, two-way audeo and audeo alarm , Tamper and motion detection, MicroSD card slot upto 2TB for edge recording cloud based service. true day-night switching, DWDR, H.264/H-265/M-JPEG video compression white balance, BLC, Intelligent Defog, iDNR, privacy masking, 12VDC/POE, UL Certified Operating Temperature -10 dec C to 50 deg C and 3 years warranty. Rest technical specification as per attached sheet. |
| 389 | WORK STATION |
| 390 | Supply, Installation, testing and commissioning of PC Client Intel i7 processor (for Workstation) with clock speed minimum 3.6GHz, RAM 16 GB and expandable. Window 10 professional 64 bit, 2 x 43\" LED full HD monitor, 2 TB(for Workstation) with read and write functions. LAN INTERFACE 10/100/1000 Mbps Etthernet, Mouse optical, USB port at front Dual and dual monitor support in 2.5GB graphic card. The Workstation shall be able to compatible / communicate with BMS. |
| 391 | VIDEO MANAGEMENT SYSTEM SOFTWARE |
| 392 | Supply, installation, testing and commissioning of Video Management System (VMS) software shall be used to view live and recorded video from capture cards and IP devices connected to local and wide area networks. The VMS software shall have a client/serverbased architecture that can be configured as a standalone VMS system with the client software running on the server hardware and/or the client running on any networkconnected TCP/IP workstation. Multiple client workstations shall be capable of simultaneously viewing live and/or recorded video from one or more servers. Multiple servers shall also be able to simultaneously provide live and/or recorded video to one or more workstations. The VMS server software shall also have the ability to be installed on an IP edge device—such as an IP camera or encoder that allows for 3rd party applications—allowing the device to serve as both a server and IP video recording device.The VMS shall not charge for the number of concurrent clients (min. 50 thick clients and 16 mobile clients to be provided along with VMS). |
| 393 | VIDEO STORAGE APPLIANCE / DEVICE |
| 394 | Supply, installation, testing and commissioning of IP Video Storage Appliance shall be a RAID-5 protected shall utilise \"enterprise-rated\" hard drives in a fault tolerant RAID-5 configuration shall offer a bandwidth of 550 Mbit/s shall offer a dual port Gigabit Ethernet network interface, 8 GB system memory and an Intel xeon Core Processor, redundant power supply and hot swappable HDD with Windows 2012 R2 operating system, UL, CE, FCC for 32 cameras storage of 310 TB or more suitable for recording of 90 days at 15 fps and 720p including license cost upto 50 cameras to con sidered. |
| 395 | POE SWITCH |
| 396 | Supply, installation, testing and commissioning of 8-10/100/1000 POE ports with 120W or above power budget with 2 combo mini-GBIC port and switching capacity 20 gbps or above. |
| 397 | Supply, installation, testing and commissioning of 24-10/100/1000 ports (24 POE+ ports with 360W or above power budget) with 2 gigabit copper / SEP combo + 2 SEP ports and switching capacity 50 gbps or above. |
| 398 | RACK |
| 399 | Supply, installation, testing and commissioning of Wall mount following size Rack with front glass door and lock arrangement with suitable size of fan and ACD power socket. |
| 400 | 42U Rack |
| 401 | 9U Rack |
| 402 | CABLES |
| 403 | Supply and laying of 1.5 Sq.mm., 3 core copper armoured cable on existingcable tray / GI coduit. |
| 404 | Supply and laying of UTP 4 pair CAT6LAN Cables in existing GI conduit as required. |
| 405 | CONDUIT |
| 406 | Supplying and fixing of following sizes medium class PVC conduit along withaccessories in surface /recess including cutting the wall and making good the same as required. |
| 407 | 25 mm |
| 408 | RO WATER SUPPLY SYSTEM |
| 409 | Supplying Installation testing and Commissioning of the following equipment forming part of the RO Water Supply System complete with all accessories and components required for proper functioning of the system all as specified. |
| 410 | Supplying Installation testing and Commissioning of pre-fabricated plant room fitted 1000 LPH Capacity MIMIC based atest technology dual operation type ready to install Reverse Osmosis Plant specially designed & install Reverse Osmosis Plant specially designed and suitable for treatment of mentioned raw water quality. The CIP system shall be complete with 1+1 feed pumps DMF , Antiscallallant PH Correction Disinfectant dozers, Members Module System, CIP system, Online pressure indicators, TDS Meter , PH indicator, Flow indicators for onsite quality control and check. The system shall also be incorporated for low-high pressure control and on board display of treatment scheme andwater level control of raw/manual selection mode operation and shall be comprised for ready to install at site complete with MSEC fabricated plant roomfor smooth operation, maintenance, energy efficient and handling of entire plant as required for satisfaction of Engineer Incharge for the parameters as described.Make : GE/Thermax/ion Exchange or equivalent |
| 411 | Raw water qualityResultPH7TDS 2930MG/LTurbidity sightly TurbidColourUnopjectionable Total Hardness as CACO3 737 mg/LTotal Alkanity as CACO3 427 mg/LCalcium as Ca :376 mg/LMagnesium Hardness as CACO3 : 361 mg/LTemporary Hardness as CACO3 :427 mg/LPermanent Hardness as CACO3 :310 mg/LPhenolphthalein Alkalinity in CACO : NilChloride as cl : 745 mg/LSulphates as SO4 :729 mg/LMolybdate Reactive Silica ad SiO2 : 14 mg/LDissolved Iron as Fe :0 mg/L |
| 412 | Treated Water QualityParametersResultOdourUnobjectionable Taste AgreeableTurbidity<0.4 NTUPpH7 to 7.5Total Disolved Solid TDS<150mg/LChlorides<50mg/LChloformsZeroE Colt ; AbsentFeccal Coli FormZeroResidual Free Chlorine0.2 to 0.5Flow 3000LPHSystem Recovery60% |
| 413 | WATER STORAGE TANKS |
| 414 | Providing and placing on terrace(at all floor levels) polyethylene water storage tank of capacity 10000 Liters, ISI : 12701 marked with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes including fittings and the civil foundations for tank etc. all complete for RO Water Supply System. |
| 415 | ROUTINE RO CONSUMABLES |
| 416 | Supply of consumables items as per actual requirement to achieve the desired quality of water fSystem.or the period of 12 months for above RO System |
| 417 | RO CONTROL PANEL |
| 418 | Supplying Installation testing and Commissioning of 3 Phase and Neutral 415V 4 wire Free Standing Floor mounted MV panel made out of 14 SWG PVC sheet after seven tank process and painting with Epoxy power coating. The panel shall consist of suitable rating TPN Aluminium bus bar(at the rating of 0.8A/Sq.mm.) supported with DMC/SMC barriers and colour coded with Heat Shrinkable Sleeves. The Mtering shall be provided as specified. The panel shall have short circuit withstanding capacity of minimum 50KA and consists of the switchgear as mentioned below. The panel shall be got fabricated from manufacturers with CPRI Test Certificates only. The PCC shall have at least two separate cubicles for the maximum rating. The size of all panel mounting meters shall be 96x96mm. The panels shall be mounted on U channelsincluding supply and fixing the same. |
| 419 | Incoming |
| 420 | RO PANEL |
| 421 | Incoming 100A, 25KA 4P Pole MCCB with O/C, S/T Thermal Manetic Release Busbars 100A TPN Aluminium Bus bar Metering Incomer:0-500V Digital Voltmeter with selector switch and fuses - 1set0-100A Digital Ammeter with resin cast CTs of ratio 100/5A Class 1 Accuracy and 15VA burden with selector switch- 1 set |
| 422 | Outgoings |
| 423 | (a) 63 Amps 3 Pole MCCB for 5 H.P.and above having Star-Delta : Each compartment shall contain direct oprated 3 phase digital electronic ammeter of suitable range with auto/manual selector switch and indicating lamp with MCB\"s and ON/OFF/TRIP status of motor. All phases have single phase preventor - 5 Nos.(b) 15 Amps 3 poles MCB for Less than 5 HP DOL Stater and outgoings feeders : Each compartment shall contain direct operated three phase digital electronic ammeters of suitable range with auto/manual selector switch and indicating lamps with MCB\"s and ON/OFF/TRIP status of motor. All phases have single phase preventor - 7 Nos.( c ) Single phase stater - 10 Nos.(d ) 15 Amps MCB SPN, 10KA- 1 No. |
| 424 | UPVC PIPE |
| 425 | Supplying Installation testing and Commissioning of anticorrosive Unplasticized Polyvinyl Choloride(UPVC) ball mounted quarter turn internally EPDM/Viton lined trimetric UPVC ball valves having the high quality EPDM shaft with inbuilt taper pin, plug and silicon/viton/neoprin ORINGS complete as required for smooth operation of high pressure water treatment plant line. |
| 426 | 50 NB |
| 427 | 40 NB |
| 428 | 25 NB |
| 429 | 16 NB |
| 430 | POWER CABLE |
| 431 | 4C X 16 Sq.mm.(Aluminium) |
| 432 | 4C X 6 Sq.mm.(copper) |
| 433 | 4C X 4 Sq.mm.(copper) |
| 434 | SHOP ELECTRIC |
| 435 | CUBICLES & SWITCHBOARDS |
| 436 | Supply, installation, testing and commissioning of front operated cubicle type compartmentalised as per form 3B (BS 5486 Part-1 1990) front access free standing, dust and vermin use at 415 volts, 3 phase 4 wire 50 Hertx system suitable for fault level of required value symmetrical at 415 volts fabricated from 2 mm thick CRCA MS sheets with hinged, gasketted (metal based neoprene) and lockable doors having structural reinforcement with suitable angle/channel/T/flat sections including 3 mm thick gland plates on top and bottom and including 3 mm thick gland plates on top and bottom and including Gl earth strip 50 x 6 mm with 2 Nos earthing terminals and including powder coated paint finish of approved shade over metal surface cleaned and treated with seven tank process complete with interconnections etc complete as per specifications as required and as below.NOTE: The following provisions shall be required to be made in the switchboard detailed below. The switchboard shall have provision for entry of all PVCA cables/. Bus duct from the top/bottom as required.All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The bus bar insulation shall be with heat shrinkable sleeves, SMC /DMC shrouds and bus bar supports shall be used. Padlocking facility shall be provided on all outgoing feeders doors and switch handles shall be locakble in OFF position.All the incomer breakers shall be interlocked with micro PLC\"s and interlocking of 3 Nos DC supply sources so that only one supply available to micro PLC The micro PLC. The micro PLC\"s shall have interconnectability with each other. |
| 437 | All panels shall be complete with accessories required for monitoring complete Electrical Distribution System on existing BMS system |
| 438 | BUILDING MAIN LT PANEL(Location: LT Panel Room) INCOMERS- 2 NOS.EACH EQUIPPED WITH FOLLOWINGS1 Nos 3200 Amps 415 Volt 4-P EDO ACB 65kA complete with Microrpocessor based release with protection functions-over current, short circuit and earth fault time characteristics and reverse power relay.3 Nos cast resin current transformers of 4000/5 ratio, 15 VA class 1.0 for metering. 1-square 96mm x 96mm multi functional digital meter2 sets of 3 Nos cast resin current transformers of 3200/5 ratio. 15 VA class 1.0 for APFCR relay as summation CT3 Nos cast resin current transformers of 4000/5 ratio, 15 VA class 5p 10 of protections.Phase reverse relay6 Nos No/NC contacts for remote opening & closing.Microprocessor based release with protections for earth fault, over load and short circuit with time chractertics.Red/Green ON/OFF indicating lamps with control fuse1 set of three phase indicating lamps along with control fuses.Amber healthy trip indicating lamp with control fuse1 clear indicating lamp for auto trip240 volt motor wound spring closing mechanismTerminals to receive XLPE aluminium cablesBreaker On/OFF switch240V AC shunt trip coil |
| 439 | BUS COUPLER ACB INCOMER-1 NOS EACH EQUIPPED WITH FOLLOWINGS1 Nos 3200 Amps 415 Volt 4-P EDO 65kA ACB complete with Microrpocessor based release with protection functions-over current short circuit and earth fault time characteristics and reverse power relay3 Nos cast resin current transformers of 4000/5 ratio, 15 VA class 1.0 for metering 1-square 96mm x 96mm multi functional digital meter2 sets of 3 Nos cast resin current transformers of 4000/5 ratio 15 VA class 10 for APFCR relay as summation CT3 Nos cast resin current transformers of 4000/5 ratio, 15 VA class 5p 10 of protectionsphase reverse relay6 Nos No/NC contacts for remote opening & closing Microprocessor based release with protections for earth fault over load and short circuit with time characteristicsRed/Green ON/OFF indicating lamps with control fuse1 set of three phase indicating tamps along with control fuses. Amber healthy trip indicating lamp with control fuse1 clear indicating lamp for auto trip 240 volt motor wound spring closing mechanism.Terminals to receive XLPE aluminium cablesBreaker On/OFF switch240V AC shunt trip coilNOTE THE MAIN INCOMING ACB AND PHASE REVERSAL ACB SHOULD BE INTERLOCKED IN SUCH A WAY THAT ONLY ONE ACB IS ON ALL THE TIMES AND THE INCOMING CABLE SHALL BE CONNECTED TO SECOND ACB IN SUCH A WAY THAT THE PHASES GET REVERSED AS ON REQUIRED ONLY |
| 440 | BUS BARElectrolytic high conductivity aluminium three phase and neutral bus bars rated at 3200 amps having a maximum current density of 0.8 amp per sq mm suitable to with stand symmetrical fault level of 50 KA at 415volls The neutral bus bar is to be of 100% Capacity |
| 441 | OUTGOINGSChiller Panel 1 No 1250 Amps 50 kA 415 volt 4P EDO ACB with fixed neutral link each, complete with followingsMicroprocessor based release with protection functions over current, short circuit and earth fault with time characteristics and reverse power relay3 Nos Cast resin 1250/5 Class 10 15 VA Burden CT\"s for metering1-square 96mm x 96mm multi functional digital meterRed/Green ON/OFF indicating lamps Terminals to receive XLPE Aluminium cables240 V AC shunt trip coilUPS Panel 630 Amps 50 KA 415 volt 4P MCCB with in built Microprocessor based release with protection for short circuit and over load 04 Sets & each equipped with followings (3W+1SB)3 Nos Cast Resin 630/5 Class 10, 15 VA burden CT\"s for metering1-square 96mm x 96mm multi functional digital meter6 Nos NO/NC contacts for remote open & closeRed/Green ON/OFF indicating lampsTerminals to receive XLPE aluminium cables240 V AC shunt trip coil |
| 442 | AHU Panel: 1 No. 630 Amps 50 kA 415 volt TPN MCCB with in built Microprocessor based release with protection for short circuit and over load & each equipped with followings3 Nos Cast Resin 630/5 Class 10, 15 VA burden CT\"s for metering1-square 96mm x 96mm multi functional digital meter6 Nos NO/NC contacts for remote open & closeRed/Green ON/OFF indicating lampsTerminals to receive XLPE aluminium cables240 V AC shunt trip coil |
| 443 | Hot Water Generator Panel 1 No 630 Amps 50 kA 415 volt TPN MCCB with in built Microprocessor based release with protection for short circuit and over load & each equipped with followings3 Nos Cast Resin 630/5 Class 10, 15 VA burden CT\"s for metering1-square 96mm x 96mm multi functional digital meter6 Nos NO/NC contacts for remote open & closeRed/Green ON/OFF indicating lampsTerminals to receive XLPE aluminium cables240 V AC shunt trip coil |
| 444 | Scrubber/ RO/ Compressed Air Plumbing Panel 100 Amps 25 KA 415 volt TPN MCCB with Thermal Magnetic Based Release for O/C S/C 04 Sets & each equipped with followings (3W+1SB)3 Nos Cast Resin 100/5 Class 10, 15 VA burden CT\"s for metering1-square 96mm x 96mm multi functional digital meter6 Nos NO/NC contacts for remote open & closeRed/Green ON/OFF indicating lampsTerminals to receive XLPE aluminium cables240 V AC shunt trip coil |
| 445 | Clean Room Sitting PDB Panel 100 Amps 25 kA 415 volt 4P MCCB with in built Microprocessor based release with protection for short circuit and over load 02 Sets & each equipped with followings (2W+1SB)3 Nos Cast Resin 100/5 Class 10, 15 VA burden CT\"s for metering1-square 96mm x 96mm multi functional digital meter6 Nos NO/NC contacts for remote open & closeRed/Green ON/OFF indicating lampsTerminals to receive XLPE aluminium cables240 V AC shunt trip coil |
| 446 | Clean Room Sitting Plant Room LDB Panel 40 Amps 25 KA 415 volt 4P MCCB with in built Microprocessor based release with protection for short circuit and over load 02 Sets & each equipped3 Nos Cast Resin 40/5 Class 10, 15 VA burden CT\"s for metering1-square 96mm x 96mm multi functional digital meter6 Nos NO/NC contacts for remote open & closeRed/Green ON/OFF indicating lampsTerminals to receive XLPE aluminium cables240 V AC shunt trip coil |
| 447 | Main AC Panel P.1(Location: Existing AC Room)INCOMMER 1 NO-1250A 50KA 4 Pole Electrically Operated Drawout type Air Circuit Breaker with safety shutter afc s/c eff release with all other standard accessones as per specifications1 Set indicating lamps RYB ON/OFF/TRIP1No- breaker control switch1No control fuse with base1No Volt meter 0-500V with selector switch1No Ammeter 0-1250A with selector switch3Nos CT 1250/5A 15VA CL-1BUSBARElectrolytic high conductivity aluminium three phase and neutral busbars rated at 1250 Amp having a maximum current density of 0 8 amp per sq mm suitable to withstand symmetrical fault level of 25 MVA at 415 volts. The neutral busbar is to be of 100% capacity |
| 448 | OUTGOING(i) 2 Nos 800 Amps 35KA TPN MCCB with rotary operated handle outgoing for chillers (1 standby)ii) 2 Nos 63 Amps MCB TPN outgoing for Secondry Chilled Water Pumps with 25 KW motor (1 standby)iii) 2 Nos 160 Amps MCB TPN outgoing for Primary Chilled Water Pumps with 25 KW motor (1 standby)iv) 2 Nos 16 Amps MCB TPN outgoing for spareAll starter shall have following accessories1 No overload relay1 No Ammeter with ASS & CTs1 No single phase preventer MPRO-2 Type3 Nos ON/OFF/TRIP indicating lights2 Nos ON/OFF push buttons |
| 449 | AHU SWITCHBOARD(Location Plant Room Mezzanine Floor) INCOMING1 Nos 400 Amp TPN MCCB 35 KA 415 volt 4P MCCB with in built Microprocessor based release with protection for short circuit and over load1. No 0-500 voltmeter with selector switch1 No 0-400 Amp ammeter with selector switch and CTs1 set of phase indicating lamps with MCBBUSBARElectrolytic high conductivity aluminium three phase and neutral busbars rated at 400 amps having a maximum current density of 0.8 amp per sq mm suitable to with stand symmetrical fault level of 25 KA at 415V. The neutral busbar is to be of 100% capacity. |
| 450 | OUTGOINGSi) 11 Nos 40 Amps TPN MCB outgoing for AHUSii) 5 Nos 25 Amps TPN MCB outgoing for AHUSiii) 14 Nos 10 Amps TPN MCB outgoing for De Humidifiers iv) 11 Nos automatic Star Delta starter for 15 KW motor of AHUSiv) 11 Nos automatic Star-Delta starter for 15 KW motor of AHUS v) 5 Nos automatic DOL starter for 5 KW motor of AHUS All starter shall have following accessories1 No overload relay1 No Ammeter with ASS & CTS1 No single phase preventer MPRO 2 Type3 Nos ON/OFF/TRIP indicating lights2 Nos ON/OFF push buttons2 Nos 16 Amp TPN MCCB3 Nos 40 Amp TPN 16KA ELCBThe switchboard shall be complete with all interconnections, risers wiring tables etc complete as required |
| 451 | Hot Water Generator Panel(Location Plant Room Ground Floor)INCOMING1 Nos 630 Amp TPN MCCB 25 KA 415 volt 4P MCCB with in built Microprocessor based release with protection for short circuit and over load 1 No. 0-500 voltmeter with selector switch1 No 0-600 Amp ammeter with selector switch and CTs1 set of phase indicating lamps with MCBBUSBARElectrolytic high conductivity aluminium three phase and neutral busbars rated at 630 amps having a maximum current density of 0.8 amp per sq mm suitable to with stand symmetrical fault level of 25KA at 415volts. The neutral busbar is to be of 100% capacity |
| 452 | OUTGOINGSi) 02 Nos 500 Amps TPN MCCB outgoing for HWGii) 03 Nos 63 Amps TPN MCCB outgoing for HWPAll starter shall have following accessories1 No overload relay1 No Ammeter with ASS & CTs1 No single phase preventer MPRO-2 Type 3 Nos ON/OFF/TRIP indicating lights2 Nos ON/OFF push buttons2 Nos 16 Amp TPN MCCB3 Nos 40 Amp TPN 16KA ELCBThe switchboard shall be complete with all interconnections risers, wiring lables etc complete as required. |
| 453 | UPS SWITCHBOARD(Location Plant Room Ground Floor)UPS INPUTS03 Nos 630 Amp TPN MCCB 35 KA 415 volt 4P MCCB with in built Microprocessor based release with protection for short circuit and over load & each eqquiped with followingsPower quality analyzer with display and event recording facility suitable for interface with BMS - 03 Nos1 No. 0-500 voltmeter with selector switch1 No 0-400 Amp ammeter with selector switch and CT1 set of phase indicating lamps with MCBUPS OUTPUT02 Nos 400 Amp TPN MCCB 35 KA 415 volt 4P MCCB with in built Microprocessor based release with protection for short circuit and over load & each eqquiped with followings 1 No 0-500 voltmeter with selector switch1 No 0-800 Amp ammeter with selector switch and CTs1 set of phase indicating lamps with MCBBUSBARElectrolytic high conductivity aluminium three phase and neutral busbars rated at 630 amps having a maximum current density of 0.8 amp per sq.mm suitable to with stand symmetrical fault level of 25 KA at 415volts. The neutral busbar is to be of 100% capacity |
| 454 | OUTGOINGS(i) 02 Nos 250 Amps 4P MCCB outgoing for Clean Room PDBs Panel (3W+158)(ii) 02 Nos 150 Amps 4P MCCB outgoing for Clean Room LDBS Panel (3W+1SB)(iii) 02 Nos 100 Amps 4P MCCB outgoing for Clean Room PDBs Panel (3W+1SB)(iv) 04 Nos 63 Amps 4P MCCB outgoing for Clean Room LDBs Panel (3W+1SB)(v) 04 Nos 40 Amps 4P MCCB outgoing for Clean Room LDBS Panel (3W+1SB) |
| 455 | SCRUBBER SWITCHBOARD(Location Plant Room Ground Floor)INCOMING1 Nos 100 Amp TPN MCCB 25 KA 415 volt TPN MCCB with in built Microprocessor based release with protection for short circuit and over load1 No. 0-500 voltmeter with selector switch1 No 0-100 Amp ammeter with selector switch and CTs1 set of phase indicating lamps with MCBBUSBARElectrolytic high conductivity aluminium three phase and neutral busbars rated at 100 amps having a maximum current density of 0.8 amp per sq.mm suitable to with stand symmetrical fault level of 25 KA at 415volts. The neutral busbar is to be of 100% capacity |
| 456 | OUTGOINGSi) 02 Nos 40 Amps MCB TPN outgoing for Wet Scrubber Fan (1W+1SB)ii) 02 Nos 40 Amps MCB TPN outgoing for Dry Scrubber Fan (1W+1SB)iii) 02 Nos 10 Amps MCB TPN outgoing for water Sprinkler Pumps (1W+1SB)iv) 04 Nos automatic Star Delta starter for 15 KW motor of Scrubber Fan (2W+2SB)v) 02 Nos automatic DOL starter for 1.5 KW motor of water Sprinkler Pumps (1W158)All starter shall have following accessories 1 No overload relay1 No overload relay1 No Ammeter with ASS & CTs1 No single phase preventer MPRO-2 Type2 Nos ON/OFF indicating lights 2 Nos ON/OFF push buttonsThe switchboard shall be complete with all interconnections, risers wiring lables etc complete as required |
| 457 | CDA SWITCHBOARD(Location Plant Room Ground Floor)INCOMING1 Nos 100 Amp TPN MCCB 25 KA 415 volt 4P MCCB with in built Microprocessor based release with protection for short circuit and over load1 No. 0-500 voltmeter with selector switch1 No 0-100 Amp ammeter with selector switch and CTs1 set of phase indicating lamps with MCBBUSBARElectrolytic high conductivity aluminium three phase and neutral busbars rated at 100 amps having a maximum current density of 0.8 amp per sq.mm suitable to with stand symmetrical fault level of 25 KA at 415volts. The neutral busbar is to be of 100% capacityOUTGOINGSi) 02 Nos 80 Amps MCB TP+NL outgoing for CDA (1W+1SB)The switchboard shall be complete with all interconnections, risers wiring lables etc complete as required |
| 458 | PLUMBING SWITCHBOARD(Location Plant Room Ground Floor)INCOMING1 Nos 100 Amp TPN MCCB 25 KA 415 volt, 4P MCCB with in built Microprocessor based release with protection for short circuit and over load1 No. 0-500 voltmeter with selector switch1 No 0-100 Amp ammeter with selector switch and CTs1 set of phase indicating lamps with MCBBUSBARElectrolytic high conductivity aluminium three phase and neutral busbars rated at 100 amps having a maximum current density of 0.8 amp per sq.mm suitable to with stand symmetrical fault level of 25 KA at 415volts. The neutral busbar is to be of 100% capacity |
| 459 | OUTGOINGSi) 04 Nos 10 Amps MCB TP+NL outgoing for Feed Pumps (2W+2SB)ii) 02 Nos 16 Amps MCB TP+NL outgoing for Feed Pumps (1W+1SB)iii) 02 Nos 10 Amps MCB TP+NL outgoing forDrainage Pumps (1W+1SB)iv) 04 Nos automatic DOL starter for 1.5 KW motor of Feed Pumps (2W+2SB)v) 02 Nos automatic DOL starter for 5 KW motor of Domestic Water Pumps (1W158)vi) 02 Nos automatic DOL starter for 0.75 KW motor of Water Drainage Pumps (1W158)All starter shall have following accessories 1 No overload relay1 No overload relay1 No Ammeter with ASS & CTs1 No single phase preventer MPRO-2 Type2 Nos ON/OFF indicating lights 2 Nos ON/OFF push buttonsThe switchboard shall be complete with all interconnections, risers wiring lables etc complete as required |
| 460 | Distribution BoardsSupply, receiving, handling, erecting, testing and commissioning of cabinet type of original factory fabricated vertical double door distribution board 18 gauge rust inhibited and baced enamel painted sheet steel and comprising of incoming MCB, outgoing MCBs. |
| 461 | (a) PDB |
| 462 | 08 way TPN DB with 24 nos. SP MCB of 16-32A rating & controlled by 1 no. 63A TPN MCCB |
| 463 | (b) LDB |
| 464 | 04 way TPN DB with 12 nos. SP MCB of 6-20A rating & controlled by 1 no. 40A TPN MCCB |
| 465 | MV Cables |
| 466 | Supply, laying and commissioning of following size 1.1 KV grade XLPE insulated armoured aluminium conductor underground cable, in built up cable trench / alredy laid RCC hume pipe or on cable tray with all installation materials. When the cable is to be laid in ground, the same shall be laid at a depth of 750mm below ground level including excavation in any type of soil including SDR & Hard rock and refilling of earth after cables are laid providing protection with sand and bricks at sides and top and cable route markers at every 15mtr. interval and also at the turnings. The cable shall conform to IS:7098/Part 1 |
| 467 | 3.5C X 300 Sq.mm |
| 468 | 3.5C X240 Sq.mm |
| 469 | 3.5 C X185 Sq.mm |
| 470 | 3.5 C X120Sq.mm |
| 471 | 3.5 C X 95 Sqmm |
| 472 | 3.5 C X 70 Sqmm |
| 473 | 3.5 C X 50 Sqmm |
| 474 | 3.5 C X 35 Sqmm |
| 475 | 3.5 C X 25 Sqmm |
| 476 | 4C X 16 Sqmm |
| 477 | 4C X 10 Sqmm |
| 478 | Cable End Termination |
| 479 | Providing Double Compression and terminations for the cable specified above with compression type gland, lugs using crimping tool, Insulation tape, Identification tags, etc. including end termination and earthing of gland. |
| 480 | 3.5C X300 Sq.mm |
| 481 | 3.5C X240 Sq.mm |
| 482 | 3.5C X185 Sq.mm |
| 483 | 3.5 C X120Sq.mm |
| 484 | 3.5 C X 95Sq.mm |
| 485 | 3.5 C X 70 Sqmm |
| 486 | 3.5 C X 50 Sqmm |
| 487 | 3.5 C X 35 Sqmm |
| 488 | 3.5 C X 25 Sqmm |
| 489 | 4 C X 16 Sqmm |
| 490 | 4 C X 10 Sqmm |
| 491 | Control Cable |
| 492 | Supply, laying and commissioning of following size 1.1KV grade PVC insulated armoured copper conductor underground cable, in built up cable trench / alredy laid RCC hume pipe or on cable tray with all installation materials. The cable shall conform to IS:1554/Part 1 |
| 493 | 4 core 2.5 Sq.mm |
| 494 | 6 core 2.5 Sq.mm |
| 495 | 3 core 2.5 Sq.mm |
| 496 | 19 core 2.5 Sq.mm |
| 497 | 3 core 6.0 Sq.mm |
| 498 | Cable End Termination |
| 499 | Providing Double Compression and terminations for the cable specified above with compression type gland, lugs using crimping tool, Insulation tape, Identification tags, etc. including end termination and earthing of gland. |
| 500 | 4 core 2.5 Sq.mm |
| 501 | 6 core 2.5 Sq.mm |
| 502 | 3 core 2.5 Sq.mm |
| 503 | 19 core 2.5 Sq.mm |
| 504 | 3 core 6.0 Sq.mm |
| 505 | Earth Stations |
| 506 | Supply, installation, and testing of Earthing with Copper plate 600 mm x 600 mm x 3mm thick at minimum 2500 mm depth including fixing hardware brasss nut bolts other accessories 20 mm dia GI Pipe including construction of brick pedestal providing meshed funnel Ci cover and other civd Engineering works spreading a homogenous mixture of salt char coal or bentonite around the plate etc including earth work excavation in all types of sail SDR & HR, Back filling etc complete as per IS 3043 or latest revision and as directed by engineer in charge |
| 507 | Supply, installation and testing of Earthing with GI plate 600 mm x 600 mm x 6mm thick at minimum 2500 mm depth including fixing hardware, brasss nut bolts, other accessories 20 mm dia GI Pipe including construction of brick pedestal providing meshed funnel Ci cover and other civil Engineering works. spreading a homogenous mixture of salt char coal or bentonite around the plate etc including earth work excavation in all types of soil, SDR & HR Back filling etc, complete as per IS 3043 or latest revision and as directed by engineer in charge |
| 508 | Providing maintenance free Earth station consisting of - 40min dia 3 Mtr length G.I.electrode capsule, filled with earth enhancing compound, sealed at both ends and brazed lead for connection at one end, suitable for direct installation at site at a depth of 3.0 Mtrs- Earth Enhanced compound, Conditioning Gel & Moisture Retaining Compound upto a depth of 2.0 Meters around the electrode capsule-Brick chamber & CI Cover complete |
| 509 | Providing maintenance free Earth station consisting of- 40min dia 3 Mtr length Copper electrode capsule, filled with earth enhancing compound, sealed at both ends and brazed lead for connection at one end, suitable for direct installation at site at a depth of 3.0 Mtrs- Earth Enhanced compound, Conditioning Gel & Moisture Retaining Compound upto a depth of 2.0 Meters around the electrode capsule-Brick chamber & CI Cover complete |
| 510 | Earth Strips |
| 511 | Supply and laying of the following size earth strips at 0.5 Mtr. below ground including excavation and refilling of earth when laid in ground and with all fixing accessories when laid in trench with including connection / terminating to Earth Station with brass / GI nut-bolts, spring, washer, bi-metalic strips etc. complete as required(Jointing shall be done by overlapping and with 2 sets of brass / GI nut-bolts & spring washer spaced at 50mm) |
| 512 | 50 x 6mm hot dip GI strip (Galvanisation as per IS 4759 : 1996) with heat shrinkable sleeves laid ground/ on wall including all necessary fixing materials and accessories complete as required. |
| 513 | 25 x 6mm hot dip GI strip (Galvanisation as per IS 4759 : 1996) with heat shrinkable sleeves laid ground/ on wall including all necessary fixing materials and accessories complete as required. |
| 514 | 50 x 6mm hot dip Copper strip (Galvanisation as per IS 4759 : 1996) with heat shrinkable sleeves laid ground/ on wall including all necessary fixing materials and accessories complete as required. |
| 515 | 25 x 6mm hot dip Copper strip (Galvanisation as per IS 4759 : 1996) with heat shrinkable sleeves laid ground/ on wall including all necessary fixing materials and accessories complete as required. |
| 516 | CHEMICAL EARTHING SYSTEM |
| 517 | Supply installation testing and commissioning of Earth Pits for rocky/sandy/ normal soil with 3000mm long x 14 2 mm dia copper coated (0 254mm) steel earthing rod surrounded by ground enhancement material (s 12 Ohm Cms Resistivity Value) compound slurry 50 mm all around the earthing rod in 120mm dia hole made in 300 mm dia and 6000mm deep hole pit duly filled with black cotton soil including accessories complete in all repects and as per the drawing attached |
| 518 | Supply installation testing and commissioning of UL listed 143000 CCER 14 2mm dia 3000mm length Copper bonded Corbon steel core electrode tested according to IEC 62561-2 with universal clamp Equivalent to OBO along with making of 300mm dia 6000mm deep earthing pit in Rocky/Sandy bed with drill machine and removing the malba as required and Supply and Filling the 300mm x 6000mm earth pit hole with a black cotton soil and compactising the same @0 4247cu mtr per pit. Drilling of 120mm dia. 3000 mm deep earthing pit hole in in black cotton soil with machine/by hand drilling process and finally Supply and filling ground enhancement material after drilling the filled black cotton soil with 50mm thick GEM compound all around upto top of the pit |
| 519 | Making of Width 100mm x Depth 150mm on Rocky/Sandy/Normal Soil Bed on ground spreading 50mm Soil top up with 25mm thick GEM compound in and then placing 50x5mm ground mat copper conductor and covering it with GEM compound 25mm all around topping the dug out with 50mm soil (without GEM Compound and copper strip) and and pouring of GEM Bags needed for floor strip in above trench @ 11Kg / 3 RM |
| 520 | Supply Installation Commissioning of heavy duty earthpit cover made out of poly ethyelyne material of approved size and as directed by engineer incharge |
| 521 | EARTH STRIPS AND WIRES |
| 522 | Supply and laying of following size earth strips/wires of approved size and as directed by engineer incharge |
| 523 | Supply and laying of 16mm dia Copper Wire |
| 524 | Supply Installation Testing and commissioning of Earthing Grid Copper Plate of 1200mm x 100mm x 8mm thick duly supported on insulated studs with anti-vibration Rubber Bushes with 12 Nos 6mm dia hole with 12 Nos copper nut and bolts |
| 525 | Supply, laing and commissioning of 1C x 70Sq.mm, 1.1KV grade PVC sheathed, XLPE insulated copper conductor unarmoured cable. |
| 526 | EARTH STRIPS |
| 527 | Supplying, laying and fixing of 25x6mm copper flat / strip laid for raft earthing duly affixed with stainless steel clampd to the steel structure of floor slab and side walls along with exothermic type copper jointingfor a4/3/2 way joint as required. |
| 528 | Substation Accessories |
| 529 | Supply and laying of 3mm thick 11KV grade Rubber Mat as per IS : 15652 of size 1000mm x 2000mm |
| 530 | Providing printed instruction chart both in English, Hindi and local language and duly framed with front glasses for treatment of person suffering from electric shock. |
| 531 | Supplying and fixing of 4.5 Kgs. Carbon Dioxide(CO2) Fire Extinguisher with necessary clamps made from 50 x 6mm M.S.Flat with Nut & Bolts growted in wall complete. |
| 532 | Supply and fixing of floor mounting stand for keeping 4No of fire bucket 1500mm length, 900mm height made out of 40x40x6mm angle iron welded with 4 hooks and duly painted with one coat of red lead and two coats of enamel paint as per direction of Engineer-in-Charge. |
| 533 | Supply and fixing of laminated SLD-A 1 size |
| 534 | Providing pair of rubber hand gloves suitable for working on 11KV |
| 535 | Supply and fixing of NO SMOKING & DANGER ZONE sign boards |
| 536 | Supplying First Aid Box for HV complete as approved by St. Jones ambulance or Indian Red Cross. |
| 537 | Cable Route Marker |
| 538 | Supplying and fixing of cable route marker with route indicating on 150mm dia cast iron disc bolted to 40x40x3mm angle iron grouted in 1:3:6 concrete block 150x150x300mmdeep including two coats of aluminium paint on the metal works. |
| 539 | RCC Hume Pipe |
| 540 | Supply and laying of 450mm dia RCC hume pipes with collars for road crossings, laid 1250/1000mm below groung level indicating excavation of earth in any type of soilincluding SDR & hard rock and refilling and other civil engineering works. |
| 541 | Perforated Tray |
| 542 | Supply and fixing of the following power coated perforated type cable tray system including fittings and accessories on existing structural supports, fabricated from minimum 2mm thick CRCA MS sheets including the cost of power coating of armoured shade of minimum 50 microns film thickness on MS surface cleaned and prepared with 7 tank process and including the cost of providing loop earthing with 2 Nos. 25x6mm GI earth strips complete as per specifications as required and as below. |
| 543 | 900 mm x 75mm x 2.0mm trays |
| 544 | 600 mm x 75mm x 2.0mm trays |
| 545 | 450 mm x 62.5mm x 75mm trays |
| 546 | 300 mm x 62.5mm x 2.0mm trays |
| 547 | 150 mm x 50mm x 1.6mm trays |
| 548 | Circuit Wiring |
| 549 | Supplying and Drawing 1.1 KV single core stranded \"FRLS\" PVC insulated& unsheathed single core stranded copper wire (approved make) of the following sizes in PVC conduit \"FRLS\", of approved make incl. necessary fittings by the GI fish wire and making necy. connection with lugs complete as required. |
| 550 | 2x2.5 sqmm + 1x2.5 sqmm as ECC |
| 551 | 2x4 sqmm + 1x4 sqmm as ECC |
| 552 | 2x6 sqmm + 1x6 sqmm as ECC |
| 553 | 4x6sqmm + 2x6sqmm as ECC |
| 554 | 4x10sqmm + 2x6sqmm as ECC |
| 555 | Supplying and fixing of following sizes medium class PVC conduit along withaccessories in surface /recess including cutting the wall and making good the same as required. |
| 556 | 25 mm |
| 557 | 32 mm |
| 558 | Distribution BoardsSupply, installation, testing and commissioning of TPN MCB double door Distribution Boards dust and vermin protected and rated for 415V Three Phase ACsupply, operation including incoming MCB/ELCB/RCCB as per specifications and required capacity , Neutral Bar and Earthterminal complete as required and installed in flush with wall including all fixing materials required. MCBs shall conform : 8828 and ELCB/RCCB shall conform ti IS : 12640 |
| 559 | (a) PDB |
| 560 | 08 way TPN MCB DB vertical type with 250A, 100mA, 4P RCCB as incomer and 2 Nos. 32A TP MCB + 3nos. 63A TPMCB as outgoings. |
| 561 | 08 way TPN MCB DB vertical type with 100A, 100mA, 4P RCCB as incomer and 10 Nos. 16A DP MCB + 2nos. 32A DPMCBs as outgoings. |
| 562 | (a) LDB |
| 563 | 04 way TPN MCB DB vertical type with 63A, 100mA, 4P RCCB as incomer and 12 Nos. 6-32A SP MCBs as outgoings. |
| 564 | MV Cables |
| 565 | Supply, laying and commissioning of following size 1.1 KV grade XLPE insulated armoured copper conductor underground cable, in built up cable trench / alredy laid RCC hume pipe or on cable tray with all installation materials. When the cable is to be laid in ground, the same shall be laid at a depth of 750mm below ground level including excavation in any type of soil including SDR & Hard rock and refilling of earth after cables are laid providing protection with sand and bricks at sides and top and cable route markers at every 15mtr. interval and also at the turnings. The cable shall conform to IS:1554/Part 1 |
| 566 | 1C X 95 Sq.mm(copper) |
| 567 | 4C X 10 Sq.mm(copper) |
| 568 | Cable End Termination |
| 569 | Providing Double Compression and terminations for the cable specified above with compression type steel gland, Bi-metalic lugs using crimping tool, Insulation tape, Identification tags, etc. including end termination and earthing of gland with 8 SWG GI wire. |
| 570 | 1C X 95 Sq.mm |
| 571 | 4C X 10 Sq.mm |
| 572 | Aluminium Raceways |
| 573 | Supplly and fixing of 2mm thick Aluminium Raceways with clamping as per standards including chipping where over necessary finishing complete as required. Line and level should match with finished floor level after finishing the raceways |
| 574 | 150mm wide x 50mm depth |
| 575 | Earthing |
| 576 | Providing maintenance free Earth station consisting of - 40min dia 3 Mtr length Copper electrode capsule, filled with earth enhancing compound, sealed at both ends and brazed lead for connection at one end, suitable for direct installation at site at a depth of 3.0 Mtrs- -Earth Enhanced compound, Conditioning Gel & Moisture Retaining Compound upto a depth of 2.0 Meters around the electrode capsule-Brick chamber & CI Cover complete |
| 577 | Supply and laying of following size single core copper cable of following size in 32mm B-class GI Pipe including all necessry interconnections with earth station and equipments including excavation and back filling etc. complete. |
| 578 | 35 Sqm |
| 579 | FIRE ALARM AND GAS SUPRESSION SYSTEM |
| 580 | Fire Detection System for LAB |
| 581 | Fire Alarm PanelSupply, installation, testing and commissioning of micro processor based1 loop analogue addressable type fire alarm control panel with 80 character LCD display with battery backup of 1 1/2 hours four access level 500 event historical logging(UL approved) which consists of 125 detectors & 125 devices with building in 1 loop card & exp upto 6 loops etc all complete. |
| 582 | Aspiration Detector |
| 583 | Supply, installation, testing and commissioning of Laser based absolute smoke detection system with single pipe inlet aspiration detector for up to 250 m2(2500 Sq.ft.) coverage programmable alarm thresholds offline / online configuration capability, instant fault finder, auto learn smoke, auto learn flow, multiple event log up to 18000 events. Alarm threshold setting Range : 0.025-20.00%obs/m(0.008- 6.25% obs/ft) : (UL approved) |
| 584 | Supply, installation, testing and commissioning of Power Supply Unit for above detector 230V AC to 24V DC, 3 Amps. Power Supply should be with 24 Hrs. etc.all complete. |
| 585 | Supply, installation, testing and commissioning of Aspirating tube, capilary tube, Nozzles, accessories etc. all complete. |
| 586 | Supply and fixing of 25mm dia. 16 SWG MS conduit and necessary flexible MS conduits concealed / surface in walls/ceiling/above false ceiling including painting with 2 coats of Red color paint for exposed part and with all necessary accessories like tee/elbow/junction box/saddle/screws etc. as complete. |
| 587 | Photoelectric Smoke Detector |
| 588 | Supplying, installation, testing & commissioning of Analoge addressable Photoelectric Smoke detector with mounting based LED, address switch to programme the dectors from 01-99, with BASE complete as required. |
| 589 | Gas Release Panel |
| 590 | Supplying, installation, testing & commissioning ofGas Release Panel / Built in Module with 2-zone fire detection and 1-zone gas discharge module with binary switch timer for release delay and potential free contact to relay \"Gas Release\" signal to main panel. The panel should also have LCD display for the different functions. |
| 591 | Cable |
| 592 | Supplying, installation, testing & commissioning of 2C x 1.5 Sq.mm. armoured cable |
| 593 | Manual Call Point |
| 594 | Supplying, installation, testing & commissioning of addressable manual call point (break glass) complete as required and as per specifications. |
| 595 | Hooter cum Flasher |
| 596 | Supplying, installation, testing & commissioning o f Hooter cum Flashercomplete as required and as per specifications. |
| 597 | Manual Abort Station |
| 598 | Supplying, installation, testing & commissioning of Manual Abort Station (pull type) complete as required and as per specifications. |
| 599 | Addressable Module for Hooter |
| 600 | Supplying, installation, testing & commissioning of Addressable Module for Hooter complete as required and as per specifications. |
| 601 | Addressable Module for Hooter Cross-zoning |
| 602 | Supplying, installation, testing & commissioning of Addressable Module for Hooter Cross-zoning complete as required and as per specifications. |
| 603 | Addressable Module for Abort & Release Station |
| 604 | Supplying, installation, testing & commissioning of Addressable Module for Abort & Release Station address switch to programme the modules form 01-99, complete as required and as per specifications. |
| 605 | Photoluminiscent Sign Board |
| 606 | Supplying, installation, testing & commissioning of Photoluminiscent Gas Release caution Sign Board complete with fixing arrangements as required and as per specifications. |
| 607 | 24V DC Electric Photoluminiscent Sign Board |
| 608 | Supplying, installation, testing & commissioning of Electric Photoluminiscent Sign Board(24V DC) for approved locations complete as required and as per specifications. |
| 609 | Repeater Panel |
| 610 | Supplying, installation, testing & commissioning of Intellegent addressable network control repeater panel with network communication module on FACP network communication to monitor and control all local fire alarm control panels located in building built in buzzer and RS-485 port on CPU board with optional network software connectivity, fire / fault locations, audio visual signals, battery, battery charger, central processing unit 80 characters display unit complete in all respects complete as required and as per specifications. |
| 611 | Fire Detection System for Other Area |
| 612 | Networkable Fire Control Panel with Loop Cards |
| 613 | Supply, installation, testing and commissioning of the following number of loops Micro processor based analogue addressable type (UL approved) intrinsically safe networkable fire control panel with zonal indications, Zener barriers, Signal booster for network connectivity modules with optic media converters for both sides of the panels along with speech dialer facility and where is requiested and with battery power pack as per specification. All panels shall be fixed away from the wall & the same shall be fixed at MS angle with required accessories. |
| 614 | Single loop with loop cards |
| 615 | Two loop with loop cards |
| 616 | Fire Alarm Management Software |
| 617 | Supply, Installation, Testing and Commissioning of Fire Alarm Management Software System and maximum networking upto 9 panels and the following shall be pre equipped with preparation of graphic compatibilty to the firm alarm monitoring software of building and connected with slave panels including layout of the building and wiring diagram of the fire alarm system.Interconnecting the same with thefire alarm software located at the master panel testing the parameters and operation of individual detectors and slsve panel. Establishing two way communication with the master panel and slave panel. |
| 618 | Work Station |
| 619 | Supply, Installation, Testing and Commissioning of Desktop computer Dual core processor with 32\" LCD monitors with 16GB RAM loaded, 1 TB hard disk and A3 size inkjet printer with all pre required software to work with the fire alarm. The System shall be compatible/communicable for IBMS system. |
| 620 | FRLS Twisted Pair Cable |
| 621 | Supply and laying of twisted pair 1.5Sq.mm. shilded FRLS insulated copper conductor flexible wire through existing MS conduit. |
| 622 | MS Conduit |
| 623 | Supply and fixing of 25mm dia 16 SWG, MS conduit and necessary flexible MS conduitsconcealed / surface in wall / ceiling / above false ceiling including painting with two coats of Red colour paint for exposed part and with all necessay accessories like bends, tees, junction boxes, clamps, screw, etc.as complete |
| 624 | Multi Sensor Detector |
| 625 | Supplying, installation, testing & commissioning of analogue addressable type Multi Sensor(smoke/heat) Photoelectric detectors with base and LED indication lamp along with all fixing accessories. |
| 626 | Heat Detectors |
| 627 | Supplying, installation, testing & commissioning of analogue addressable type rate of rise heat detectorswithLED indication lamps. |
| 628 | Response Indicators |
| 629 | Supplying, installation, testing & commissioning of Response Indicators with LED indication lamps along with all fixing accessories. |
| 630 | Sounder /Flasher |
| 631 | Supplying, installation, testing & commissioning of analogue addressable loop powered Sounder /Flasher with all necessary fittings and accessories. |
| 632 | Manual Call Point |
| 633 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 634 | Fault Isolator |
| 635 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 636 | Control Module |
| 637 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. |
| 638 | Smoke Detector(Duct type) |
| 639 | Supplying, installation, testing & commissioning of addressable analogue type duct-able smoke detectors i/n Duct Detector Accessory, 18 in, Sampling Tube for AHU rooms with dual chamber with all fixing accessories complete as required. |
| 640 | Manual Call Points with Glass and Hammer(Weather Proof type) |
| 641 | Supplying, installation, testing & commissioning of weather proof type, analogue addressable manual call points with glass and hammer on stand post made out of 1500mm long 50 x 50 x 6mm Galvanised channel fixed in ground with concrete coping as required. |
| 642 | 8 Way Wago/ Phonix terminal connector |
| 643 | Supply, installation, testing and commissioning of 8 Way Wago/ Phonix terminal connector in MS Junction box including painting and all installation materials etc as required. |
| 644 | Siren |
| 645 | Supply, installation, testing and commissioning of 2.5 Km range Siren with Weather proof motor with 220V 50HZ AC Supply operation with required power contactor, MPCB for control all in a weather proof enclosure near motor including all installation materials as required. |
| 646 | Control Cable |
| 647 | Supply, laying, terminations and commissioning of following size 1.1KV grade PVC insulated armoured copper conductor underground cable 750mm depth, in built up cable trench / alredy laid RCC hume pipe or on cable tray with all installation materials. The cable shall conform to IS:1554/Part 1 |
| 648 | 3 core 2.5 Sq.mm |
| 649 | GI Pipe |
| 650 | Supply and laying of 50mm dia.Class \"B\" GI pipe for cable wire protection below ground works. |
| 651 | Gas Suppression System for LAB and UPS Room |
| 652 | Gas Suppression System for LAB |
| 653 | Supply, installation, testing and commissioning of the following capacity cylinderfilled with suitable for Clean Room application gasses (i.e. HFC, NOVEC, INRERGEN)Location- as per schedule4 Nos. 55Ltr. Seamless Cylinder with Syphon Tube4 Nos- Valve LPG -190-00 with pressure Gauge1 No. Centralised - Solinoid Valve 13W/24V Outlet 1/8\" Inox(High pressure)1 No. Centralised - Pneumatic Manual Release Lever (High pressure)4 Nos- Non Return Valve-1 1/2\" - 2\"4 No. Centralised - Rigid Hose 1 1/2\"(HG)- 1 1/2\"(HG)1 No. Pressure Switch with Locking Device on Manifold1 No Pneumatic Cone 1-way(High Pressure) with Tee & Decompression Screw 1 No Pneumatic 2-way(High Pressure)1 No. TF Female 1/8\"- Make 1/8\" NPT 180mm Hose4 Nos.- TF Hose 1/4\" MG/MG 580 Cones180 Kgs NOVEC Gas |
| 654 | Gas Suppression System for UPS Room |
| 655 | Supply, installation, testing and commissioning of the following capacity cylinderfilled with suitable for Clean Room application gasses (i.e. HFC, NOVEC, INRERGEN)Location- as per schedule5 Nos. 55Ltr. Seamless Cylinder with Syphon Tube5 Nos- Valve LPG -190-00 with pressure Gauge1 No. Centralised - Solinoid Valve 13W/24V Outlet 1/8\" Inox(High pressure)1 No. Centralised - Pneumatic Manual Release Lever (High pressure)5 Nos- Non Return Valve-1 1/2\" - 2\"5 No. Centralised - Rigid Hose 1 1/2\"(HG)- 1 1/2\"(HG)1 No. Pressure Switch with Locking Device on Manifold1 No Pneumatic Cone 1-way(High Pressure) with Tee & Decompression Screw 1 No Pneumatic 2-way(High Pressure)1 No. TF Female 1/8\"- Make 1/8\" NPT 180mm Hose5 Nos.- TF Hose 1/4\" MG/MG 580 Cones218 Kgs NOVEC Gas |
| 656 | Discharge Nozzle |
| 657 | Supply, installation, testing and commissioning of Discharge Nozzle(UL Listed) calibrated as per computer generated results. |
| 658 | Manifold |
| 659 | Supply, installation, testing and commissioning of Seamless Manifold and Cylinder Rack with Strip. |
| 660 | Stainless Steel PipeStainless Steel SS-304 grade and schedule 40 with necessary fittings like elbow, tees, bends, union, flanges etc. all complete. |
| 661 | 80mm dia. |
| 662 | 65mm dia. |
| 663 | 50mm dia. |
| 664 | 40mm dia. |
| 665 | 32mm dia. |
| 666 | 25mm dia. |
| 667 | 20mm dia. |
| 668 | Gas Suppression System as described above |
| 669 | CIVIL WORKS |
| 670 | Earth Work & Dismantling |
| 671 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. :All kinds of Soil ( For Foundation) |
| 672 | Demolishing lime concrete manually/ by mechanical means and disposal of material within 50 metres lead as per direction of Engineer in- charge. |
| 673 | Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer - in- charge. |
| 674 | Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. |
| 675 | In cement mortar |
| 676 | Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead : |
| 677 | Of area 3 sq. metres and below |
| 678 | Dismantling stone slab flooring laid in cement mortar including stacking of serviceable material and disposal of unserviceable materialwithin 50 metres lead. |
| 679 | Dismantling G.I. pipes (external work) including excavation and refilling trenches after taking out the pipes, manually/ by mechanical means including stacking of pipes within 50 metres lead as per direction of Engineer-in-charge : |
| 680 | 15 mm to 40 mm nominal bore |
| 681 | Dismantling old plaster or skirting raking out joints and cleaning the surface for plaster including disposal of rubbish to the dumping ground within 50 metres lead. |
| 682 | Dismantling aluminium/ Gypsum partitions, doors, windows, fixedglazing and false ceiling including disposal of unserviceable material and stacking of serviceable material with in 50 meters lead as directed by Engineer-in-charge. |
| 683 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. |
| 684 | All kinds of soil |
| 685 | Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m : |
| 686 | All kinds of soil |
| 687 | Pipes, cables etc, not exceeding 80 mm dia. |
| 688 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m. |
| 689 | Anti Termite Treatment |
| 690 | Supplying and filling in plinth withsand under floors, including watering, ramming, consolidating and dressing complete. |
| 691 | Supplying chemical emulsion in sealed containers including delivery as specified. Chlorpyriphos/ Lindane emulsifiable concentrate of 20% |
| 692 | Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) : Along the external wall below concrete or masonry apron using chemical emulsion @ 2.25 litres per linear metre including drilling and plugging holes etc.: With Chlorpyriphos/ Lindane E.C. 20% with 1% concentration |
| 693 | Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor: With Chlorpyriphos/Lindane E.C. 20% with 1% concentration |
| 694 | Concrete Work |
| 695 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : |
| 696 | 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 697 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). |
| 698 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level & above plinth |
| 699 | Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 700 | Centering and shuttering including strutting, propping etc. and removal of form for |
| 701 | Foundations, footings, bases of columns, etc. for mass concrete |
| 702 | Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 703 | Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5mm nominal size derived from natural sources) including mixing waterproofing material in cement concrete work @ 1kg per 50kg of cement and a coat of residual petroleum bitumen of penetration 80/100 of approved quality using 1.7kg per sqm on dmp proof course after cleaning the surface with brushes and finally with a piece of cloth lightly soaked in kerosine oil. |
| 704 | Brick Work |
| 705 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 706 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 707 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. |
| 708 | Cement mortar 1:3 (1 cement :3 coarse sand) |
| 709 | Flooring |
| 710 | 52 mm thick cement concrete flooring with concrete hardener topping, under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6 mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacturer\"s specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete. |
| 711 | Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : |
| 712 | 25 mm thick |
| 713 | Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete. |
| 714 | Plastering & Finishing |
| 715 | Cement Plaster (In Coarse Sand) : 12mm cement plaster of mix : 1:6 (1 cement: 6 coarse sand) |
| 716 | 18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster 1:6 (1 cement : 6 fine sand). |
| 717 | 6 mm plaster on cement concrete or reinforced cement concrete work with white cement based polymer modified self curing mortar of approved make as per the direction of Engineer-In-Charge. |
| 718 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 719 | Distempring with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of approved manufacturer and of required shade and colour all complete to achieve even shade and colour :New work (two or more coats) over and including water thinnable priming coat with cement primer having VOC content less than 50 gram/litre |
| 720 | Finishing walls with Acrylic Smooth exterior paint of required shade : New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm) |
| 721 | Joinery Work |
| 722 | Providing and fixing fire resistant door frame of section 143 x 57 mm having built in rebate made out of 16 SWG G.I. sheet (zinc coating not less than 120 gm/sqm) duly filled with vermuculite based concrete mix, suitable for mounting 60 minutes fire rated door shutters. The frame is fitted with intumuscent fire seal strip of size 10x4 mm (minimum) alround the frame and fixing with dash fastener of approved size and make, including applying a coat of approved brand fire resistant primer etc. complete as per direction of Engineer-in-charge (Dash fastener to be paid for separately). |
| 723 | Providing and fixing 50 mm thick glazed fire resistant door shutters of 60 minutes fire rating conforming to IS:3614 (Part-II), tested and certified as per laboratory approved by Engineer-in-charge, with suitable mounting on door frame, consisting of vertical styles, lock rail, top rail 100 mm wide, bottom rail 200 mm wide, made out of 16 SWG G.I.sheet (zinc coating not less than 120 gm/m2) duly filled FR insulation material and fixing with necessary stainless steel ball bearing hinges of approved make, including applying a coat of approved fire resistant primer etc. all complete as per direction of Engineer-in-charge |
| 724 | Providing and fixing carbon steel galvanised ( minimum coating 5 micron) dash fastener of 10 mm dia double threaded 6.8 grade (yield strength 480 N/mm2), counter sunk head, comprising of 10 mm dia polyamide PA 6 grade sleeve, including drilling of hole in frame , concrete/ masonry, etc. as per direction of Engineer-in-charge. |
| 725 | 10 x 80 mm |
| 726 | Providing and fixing tiled false ceiling of specified materials of size 595x595 mm in true horizontal level, suspended on inter locking metal grid of hot dippedgalvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive)onsisting of main \"T\" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross \"T\" of size 24x25 mm made of 0.30 mm thick inimum) sheet, 1200 mm long spaced between main \"T\" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross \"T\" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main \"T\" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of allT-sections shall be pre-painted with polyester paint, all complete for all heights as perspecifications, drawings and as directed by Engineer-in-charge. |
| 727 | GI Metal Ceiling Lay in plain Tegular edge Global white color tiles of size 595x595 mm, and 0.5 mm thick with 8 mm drop; made of G I sheet having galvanizing of 100 gms/sqm (both sides inclusive) and electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending. |
| 728 | Steel Work |
| 729 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. |
| 730 | In stringers, treads, landings etc. of stair cases, including use of chequered plate wherever required, all complete |
| 731 | In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 732 | Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying priming coat of approved steel primer. |
| 733 | M.S. tube |
| 734 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item) |
| 735 | With float glass panes of 5 mm thickness (weight not less than 12.50 kg/sqm) |
| 736 | Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters. |
| 737 | 80x1.25 mm M.S. laths with 1.25 mm thick top cover |
| 738 | Roofing |
| 739 | Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations:(a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment.(b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conformingto IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs. |
| 740 | (c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineer- in-charge.(d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer- in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. |
| 741 | (e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge :With average thickness of 120 mm and minimum thickness at khurra as 65 mm. |
| 742 | Providing and fixing G.I. chain link fabric fencing of required width in mesh size 25x25 mm made of G.I. wire of dia 3 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. |
| 743 | Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 744 | Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a priming coat of approved steel primer. |
| 745 | Using M.S. angels 40x40x6 mm for diagonal braces |
| 746 | Providing and fixing to existing door frames.30 mm thick Glass Fibre Reinforced Plastic (FRP) panelled door shutter of required colour and approved brand and manufacture, made with fire - retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate for forming hollow rails and styles, with wooden frame and suitable blocks of seasoned wood inside at required places for fixing of fittings, cast monolithically with 5 mm thick FRP laminate for panels conforming to IS: 14856, including fixing to frames. |
| 747 | Providing and fixing of PVDF Pipe for Chemical Handling, Size/Diameter: 4 inch with 60°C to 150°C temperature range, UV resistant, Flame retardant & self-extinguishing, Very low water absorption, High tensile and impact strength including all necessary fittings complete as per the direction of Engineer-in-charge |
| 748 | Providing and laying Non Pressure NP-3 class (Medium duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete |
| 749 | 450 mm dia RCC pipes. |
| 750 | MISCELLANEOUS ITEMS |
| 751 | Acidic & Normal Exhaust SystemExhaust Air Fans & Scrubbers |
| 752 | Wet ScrubberSupply, Erection, Testing and Commissioning of ERP WET Scrubber comprising of 3 stage (a ) Standard Activated charcoal. (b) Alcoholic scrubbing. ( c ) Acidic Scrubbing , the scrubber shall be suitable for chemicala like HCL, HNO3, HF, HSO Bromine and organic fumes , the scrubber made out of MS plates, duly epoxy painted, packed with polypropylene rings of size 50mm diameter for scrubbing with inlet water distributer , moisture diffuser etc. complete and of following capacities and sizes along with multiple inlet connections minimum 4 Nos. of dia. 600mm with FRP / PP dampers, interconnecting piping alongwith valves and safeties asdeemed necessary also being included for the complete unit with plug out / bypass arrangement complete in all respects. The units shall be supplied along with control panel having suitable outgoing along with startes for fans, pumps, and controlsand level switches and all the safety features.Flow rate - 4500 CFMBottom dia.- 1200mmShall dia. - 800mm.Height - 3000mm |
| 753 | Dry Type ScrubberSupply, Installation, Testing and Commissioning of dry type scrubber, IP-65, comprising of electrostatic section with auto wash with multiple cells to suit total volume, the housing shall be 16 gauge zinc coated steel sheet with gasketed access door, electrical interlocked, and bottom drain pan shall have integral washing system. The unit can be floor mounted or ceiling suspended. The cell wash module shall have a set of metal mesh filters. The electronic air cleaner shall be the two- stage dual voltage plate type cellsand efficiency of 90% as per ASHRAE test Standard for dry particulate. Ionizing- collecting cell shall be of one-piece construction . Power supply shall be 100% solid state. on 200 to 240 VAC, 50HZ, 1Phase input with an LED light indicating the performance status. Quoted rate shall be including of vibration isolators, foundation, electrical panel, cabling, earthing etc as required to commissioning the Dry type Scrubber. |
| 754 | 4500 cfm capacity |
| 755 | Supply, Erection, Testing and commissioning of centrifugal single inlet single width type of ID Fan of MS with FRP lined, directly coupled with suitable 3 phase, 415 volts, IP65 protected class \"F\" insulated, TEFC motors having a speed of around 1440 RPM, with necessary pedestals, foundation bolts & nuts etc. complete with following capacities and head complete in all respects. |
| 756 | 4500 CFM 8\" static |
| 757 | 3000 CFM 3\" static |
| 758 | Supply and Erection of self supporting stack made out of minimum 4mm sheet of MS construction with necessary branch off and isolation damper along with necessary provision for monitoring the quality of air duty epoxy paintedwith foundation bolts and nuts, rain roof etc., complete and of following sizes complete in all respects. |
| 759 | 600mm x 400mm dia. X 3m height |
| 760 | Supply, Erection, Testing and commissioning of centrifugal pumps with casing , inpeller of polypropylene materials with mechanical seal coupled to suitable motor of TEFC,AC 3 phase , 415V with IP65 protection, class\"F\" insulated having a speed of 1440 RPM, comlete with foundation bolts& nuts coupling, coupling guard, base plate, etc and of following capacities complete in all respects. |
| 761 | 20l/sec against a head of 05mWC |
| 762 | Supply, Erection, Testing and commissioning of Scrubber Round ducting using polypropylene with glass lining sheets with fusion welding joints completed with flanges, bends, transition pieces , brach entries, SS supports, SS 316 L hardware etc. The polypropylene ducting shall be lined with FRP lining of specified thickness & complete as per specifications. All supports used shall be of SS. |
| 763 | 3mm PP + 3mm FRP |
| 764 | Supply, Erection, Testing and commissioning of manual slide gate valve of PP construction with PP gate complete with bolts, nuts & rubber insertions and of following sizes: |
| 765 | 300mm NB |
| 766 | 250mm NB |
| 767 | 200mm NB |
| 768 | Supply, Erection, Testing and commissioning of polypropylene pipes of 16 Kg/cm pressure rating, including fittings etc., complete and of following sizes |
| 769 | 50mm NB |
| 770 | 25mm NB |
| 771 | Supply, Erection, Testing and commissioning of PVC pipes conforming to IS 4985 , 16 Kg/cm pressure rating, including fittings etc., complete and of following sizes |
| 772 | 25mm NB |
| 773 | 20mm NB |
| 774 | Steel Structural Work |
| 775 | Supply, Fabrication, transportating and erection in position in proper allignment at all height MS structural steel support in angles/iron/plates/ channels/beam etc. including premier coat of anti corrosive red oxide paint and two coats of approved shade of epoxy paint (structural steel shall be measured based on actual diemension. |
| 776 | Supply, Erection, Testing and commissioning of manual slide gate valve of ms construction with SS 316 L gate, complete with SS bolts, nuts, rubber insertions and following sizes: |
| 777 | 65mm NB |
| 778 | 50mm NB |
| 779 | Supply, Erection, Testing and commissioning of manual ball valve with body and fittings of MS, ball- SS316 L , PTFE seats, screwed and complete and of following size: |
| 780 | 25mm NB |
| 781 | Supply, Erection, Testing and commissioning of manually operated control valve of polypropylene, 3 piece construction full port and lever operated ball valve with body polypropylene, seat- PTFE, screwed ends, complete and of the following sizes: |
| 782 | 65mm NB |
| 783 | 50mm NB |
| 784 | Supply, Erection, Testing and commissioning of tubular level indicator with MS isolation valves, C/C distance of 1300mm for scrubber liquid holder complete in all respects. |
| 785 | Supply, Erection, Testing and commissioning of pressure gauge, Bourdon with chemical seal Diaphragm type sensor dial size of 6 inches for local measurement in circulation pumps with following ranges complete in all respects. |
| 786 | 0 to 200Kpa |
| 787 | 0 to 100Kpa |
| 788 | Supply, Erection, Testing and commissioning of pressure gauge, Bourdon with chemical seal Diaphragm type sensor dial size of 6 inches for local measurement in Dosing pumps with following ranges of (-100 to 350) complete in all respects. |
| 789 | Air ShowerSupply and Installation of Air Shower working space(inside diemension) should not be less than 800mm(W) x 900mm(D) x 2000mm(H) made out of SS 316 material with adjustable type SS 304 Nozzles, have high static Air Handling System. The Air Shower shall be provided with per filter of HDPE, Washable type with efficiency 90% down to 10 micron and HEPA filter with efficiency of 99.97% down to 0.3 microns etc. complete as required. |
| 790 | Effluent Treatment PlantDesign, Supply, install and testing of Package Type 2 KL ETP Plant with FRP lining having the following equipment but not limited to below equipment to achieve outlet parameters as directed by Engineer-in-charge including civil work:-i) S S Bar Screen - 01 No. ii) Equalized Effluent Transfer Pump - 2 Nosiii) Lime Dosing Tanks - 1 Noiv) Acid Dosing Tank - 1 Nov) Agitator for Lime Dosing - 1 Novi) PAC Dosing Tanks - 1 Novii) Agitator for PAC Dosing - 1 Noviii) Poly Dosing Tanks - 1 Noix) Reaction cum Settling Tank - 1 Nox) Floucalotor for Reactor Tank - 1 Noxi) Filter Feed Tank - 1 Noxii) Filter Feed Pump - 1 Noxiii) Pressure Sand Filter with UF system - 1 Noxiv) Instruments like Ph controller and recorder to monitor outlet qualityxv) Panel with automation cabling, cable tray etcxvi) Complete interconnecting pipe work and valves to complete ETPxvii) Civil work like underground effluent collection tank, platform for equipment, shed, chain link fencing etc |
| 791 | Design, Supply, install and testing of Organic solvent handling and disposal system for organics like acetone, Benzene and Alcohol. The system will be collected in three Nos 500 Ltr tank and disposal will be done by external agency:- i) 500 Ltr Tank with lifting arrangement Instruments - 3 Nosii) Level Switch - 3 Nosiii) With actuator valves for auto operation in sequence - 3 Nosiv) Panel with automation cabling, cable tray etcv) Complete interconnecting pipe work and valves to complete disposal of organic solventvi) Civil work like underground effluent collection tank, platform for equipment, shed, chain link fencing as directed by Engineer-in-Charge. |
| 792 | Testing & Report Generation of Clean RoomThe testing shall be as per specifications. Rate to include all formalities, submission of forms, follow up , submitting a time line to client, etc. for completion of testing etc. all complete. |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy