Tender For 32 Hostels/Barracks And Investigation Work Of Electrical Work Of Kutch At Mailani Police Station In District Lakhimpur Kheri., lakhimpur-Uttar Pradesh

Public Works Department-PWD has published Tender For 32 Hostels/Barracks And Investigation Work Of Electrical Work Of Kutch At Mailani Police Station In District Lakhimpur Kheri.. Submission Date for this Tender is 05-03-2024. Barrack Tenders in lakhimpur Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

42550451
Corrigendum : Tender For 32 Hostels/Barracks And Investigation Work Of Electrical Work Of Kutch At Mailani Police Station In District Lakhimpur Kheri.
Open Tender
Indian
Uttar Pradesh
lakhimpur
05-03-2024

Tender Details

Tender For 32 Hostels / Barracks And Investigation Work Of Electrical Work Of Kutch At Mailani Police Station In District Lakhimpur Kheri.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 29-Feb-2024 Date Date 05-03-2024

Key Value

Document Fees
INR 766 /-
EMD
INR 100000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: tuin y[kheiqj [khjh ds Fkkuk flaxkgh esa 01 foospuk d{k ds fo|qrhdj.k dk dk;ZA
Sl. No. Item Description
1WIRING POINTS
2Wiring point for light with 1.5 sq.mm.FRLSHPVCinsulated multistrand single core copper conductor cable in PVC conduitpartly concealed in the wall and partly laid in slab alongwith the reinforcement before concreting, complete. and1.5 sq. mm.PVC insulatedcore copper conductor cable as earthwire drawn inside the conduit.,GP Box, piano type switch & ceiling rose/angle/batten holder on 3mm thickphenolic paminated backalite sheet etc complete in all respect as directed including matching colour wash.
3Wiring point for fan / fresh air fan (light duty exhaust fan) with 1.5 sq.mm.FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduitpartly concealed in the wall and partly laid in slab alongwith the reinforcement before concreting, complete. and1.5 sq. mm.PVC insulatedcore copper conductor cable as earthwire drawn inside the conduit.,,GP Box, piano type switch & ceiling rose on 3 mm. thick backelite sheet etc., complete in all respect including matching colour wash.
4Wiringpointforplugwith 1.5 sq. mm.FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduitpartly concealed in the wall and partly laid in slab alongwith the reinforcement before concreting, complete. and1.5 sq. mm.PVC insulatedcore copper conductor cable as earthwire drawn inside the conduit., and piano typeswitch and socket etc., complete in all respect including matching colour wash.
5Wiringpointfor2 way lightwith 1.5 sq. mm. FRPVC insulated multistrand single core copper conductor cable in PVC conduitpartly concealed in the wall and partly laid in slabwith piano type switch& ceiling rose/angle/batten holderetc. FRLSH PVC insulatedmultistand copper conductor cable as earthwire drawinside the conduit
6Add for Invertor Wiring in wiring Point for light/ Fan/ Plug with 1.5 mm Cu Wire
7SUBMAIN
8Supply and wiring of submain 2.5 Sqmm with two number 20mm dia. heavy duty (2mm thick) PVC conduit with one number 1.5 sq. mm. FRLSH PVC insulated 1100 V grade multistrand copper conductor cable as earth continuity wire drawn inside the conduit.
9S/wiring of sub main with 2 no 4 sq.mm FRLSH PVC insulated 1100 Volt Grade multi strand single core copper conductor cable in 20 mm dia heavy dutyPVC conduit concealded in wall withone no 2.5 sq.mm FRLSH PVC insulated 1100 Volt Grade multi strand single core copper conductor cableas earth complete in all respect
10S/wiring of sub main with 2 no 10 sq.mm FRLSH PVC insulated 1100 Volt Grade multi strand single core copper conductor cable in 25 mm dia heavy dutyPVC conduit concealded in wall withone no 6.0 sq.mm FRLSH PVC insulated 1100 Volt Grade multi strand single core copper conductor cableas earth complete in all respect
11FITTINGS
12Supply and fixing ofLED Tube Light with batten suitable for up to 1 X 22 watt LED tube light fittingincluding tube on Surface complete in all respect. {2420 system lumens 110 Lm/w PF>0.95, THD<10%, CRI>80, Sheet thickness 0.8mm, Tube with aluminium heat with 5 year warrantee}
13Supply and fixing of 2" x 2" 36 Watt to 46 Wattindoor Recess/Surface mountingLED Square Fitting for Armstrong CeilingPowder coatedCRCA housing body diffuser ofSpecial Polycarbonate meterial and driver set complete in all respect. {3960-5060 system lumens, 70mm height with fully covered diffuser type, 110 Lm/w PF>0.95, THD<10% at full load, CRI>80 with 5 year warrantee}
14Supply and fixing ofLED Street light Fitting with mandatory driver set having die cast aluminium body and lenses suitable for 75 to 90 Watt. And Confirming to IP 66 Protection having company logo Engraved complete in all respect including labour. {8250-9900 system lumens high power LED with lenses, >110 Lm/w PF>0.95, THD<10% at full load, CRI>70, poated driver set (Not Circuitory) phase to phase protection at 440V and >300 V auto cut and restart feature with 5 year warrantee}
15Supply and fixing of power plug with 15A/250 voltflush type switch and 5 pin 15A/250V flush type universal socket in suitable M.S. box of 175mm x 100mm x 50mm size with phenolic laminated bakelite sheet cover 3mm thick fixed with brass machine screw and cup washer.
16S/O LED Bulb 15 Watt
17S & F surface/Flush mounting 4ways V TPN distribution board without additional Door without DPX3 160 MCCB complete in all respect, as directed at site byEngineer in charge.
18Supply and fixing of M.S. box of size 480mm x 480mm x 200mm deep in sunk for housing BDB/TPN fabricated from 16 gauge M.S. Sheet and 13mm x 2.5mm flat iron etc. painted outside with red oxide primer and inside with synthetic enamel paint complete in all respect.
19S/F Surface/Flush mounting 8 way SPN Distribution board witout MCB with additional metel door complete in all respect
20S&F of 40Amp. DP MCB (10 KA) C Curve
21S&F of40Amp.SPMCB(10KA)C Curve
22S&F of 125Amp4 pole MCCB (16 KA)Thermal Magnetic release
23S/F 6 Amp to 32 Amp SPMCB (10 KA)
24S&F of 200 A. 415 VMetal clad TPN CFS complete with HRC fuse etc. on angle iron frame complete in all respect.
25Supplyandlayingof aluminiumconductorPVCinsulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.
26A- 10 sq.mm x 2 core cable
27B- 70 sq.mm x 3½ core cable
28Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring ofthe cable shall be properly connected with the earth as per direction of Engineer-Incharge.
29A- 10 sq.mm x 2 core
30B- 70 sq.mm x 3½ core
31Supply and fixing of plain or pin type copper tin plated cable socket ( lug ) to the cable leads, insulating with tape and making connection etc. complete in all respect as per direction of the Engineer-Incharge.
32A- 6 sq.mm
33B- 10 sq.mm
34C- 35 sq.mm
35D- 70 sq.mm
36EARTHING
37Supply and burying of 600mm x 600mm x 6mm G.I. plate vertically for earthing with its top at least 3 metres below ground level complete with 20mm dia G.I. pipe and funnel for watering and one earthing lead oftwo no. 8 to 10 SWG GI wire in 15mm dia G.I. pipe up to switch board (from appron to switch board the cost of G.I. pipe and G.I. wire will be extra) 30cm square C.I. frame with hinged cover masonry housing alternate layers of charcoal/coke and salt at least 150mm thick alround etc. as per directions of Engineer-in-charge complete in all respect.
38Supply and laying of 25mm x 3mm G.I. strip from earth electrode directly in the ground as required complete in all respect.
39MISCELLANEOUS
40Supply and laying of 1800mm x 900mm x 12mm thick chequered rubbbber matting of tested quality.
41Supply and fixing of shock treatment chart (prescribed under I.E. rules) duly framed with glass and supported from back with hard board or soft board with supply of all material labour T&P for proper completion of work.
42Erection and testing of ceiling fan and regulatoretc. excluding supply of down rod, complete in all respect.
43Supply and fixing of fire extinguisher, ABC Type 4.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work.
44Supply and fixing of fire bucket, round bottom made of G.I. sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand,water as per directions of Engineer-in-Charge.
45Supply and fixing of electronic fan regulator 120-280 V. ISI marked, on the existing switch board including making connections, required material, labour T&P etc. for proper completion of work to the satisfaction of Engineer in charge of work.
46Supply and fixing of switch box 200 x 250 x 65 mm size of approved make made up of 1.0 mm thickISI Marked G.P.sheet All 4 corners folded & spot welded for screw and holes plugged with PVC Nylon Caps . Two or more holes for pipe entryof 25.4 mm on upper and lower sides of the box. Holes shuld be semi-shuttered type and fitted with heavy brass Earth Piller duly screwed & brand name should be embossed. Box flushed in wall including cutting of brick work, fixing it to the level with cement sand mortar, including matching colour wash with s/o all materials, labour and T&P required for proper completion of work as directed at site by the Engineer in charge.
47Supply of Ceiling fan with fan motor of AC permanent installation , capacitor, rating, conforming BEE 5 star rating and IS: 374/79 and also comply with IS:1709/1984 with latestammandment. The rated voltage 220/240 Volts, 50Hz, 1-ph AC the fan assemble should consists of down rod blades, shackle canopies etc and with double ball bearing system BEE 5 star rated 1200mm sweep size
48Wiring point for light with 1.5 sq.mm.FRLSHPVCinsulated multistrand single core copper conductor cable in PVC conduitpartly concealed in the wall and partly laid in slab alongwith the reinforcement before concreting, complete. and1.5 sq. mm.PVC insulatedcore copper conductor cable as earthwire drawn inside the conduit.,GP Box, piano type switch & ceiling rose/angle/batten holder on 3mm thickphenolic paminated backalite sheet etc complete in all respect as directed including matching colour wash.
49Vivechana
50Wiring point for light with 1.5 sq.mm.FRLSHPVCinsulated multistrand single core copper conductor cable in PVC conduitpartly concealed in the wall and partly laid in slab alongwith the reinforcement before concreting, complete. and1.5 sq. mm.PVC insulatedcore copper conductor cable as earthwire drawn inside the conduit.,GP Box, piano type switch & ceiling rose/angle/batten holder on 3mm thickphenolic paminated backalite sheet etc complete in all respect as directed including matching colour wash.
51Wiring point for fan / fresh air fan (light duty exhaust fan) with 1.5 sq.mm.FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduitpartly concealed in the wall and partly laid in slab alongwith the reinforcement before concreting, complete. and1.5 sq. mm.PVC insulatedcore copper conductor cable as earthwire drawn inside the conduit.,,GP Box, piano type switch & ceiling rose on 3 mm. thick backelite sheet etc., complete in all respect including matching colour wash.
52Wiringpointforplugwith 1.5 sq. mm.FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduitpartly concealed in the wall and partly laid in slab alongwith the reinforcement before concreting, complete. and1.5 sq. mm.PVC insulatedcore copper conductor cable as earthwire drawn inside the conduit., and piano typeswitch and socket etc., complete in all respect including matching colour wash.
53Add for Invertor Wiring in wiring Point for light/ Fan/ Plug with 1.5 mm Cu Wire
54S/F ofComputer board with 6 Amp. 3 Nos. switch & 6Amp. 5 pin 3 Nos. socket & 16 Amp. Swicth and Socket 1 No.
55S/wiring of sub main with 2 no 10 sq.mm FRLSH PVC insulated 1100 Volt Grade multi strand single core copper conductor cable in 25 mm dia heavy dutyPVC conduit concealded in wall withone no 6.0 sq.mm FRLSH PVC insulated 1100 Volt Grade multi strand single core copper conductor cableas earth complete in all respect
56S/wiring of sub main with 2 no 6 sq.mm FR PVC insulated 1100 Volt Grade multi strand single core copper conductor cable in 25 mm dia heavy dutyPVC conduit concealded in wall withone no 4.0 sq.mm FR PVC insulated 1100 Volt Grade multi strand single core copper conductor cable as earth complete in all respect
57S & F surface/Flush mounting 12ways SPN distribution board without additional metaldoor without MCB complete in all respect, asdirect by Engineer in Charge.
58Supply and fixing ofLED Tube Light with batten suitable for up to 1 X 22 watt LED tube light fittingincluding tube on Surface complete in all respect. {2420 system lumens 110 Lm/w PF>0.95, THD<10%, CRI>80, Sheet thickness 0.8mm, Tube with aluminium heat with 5 year warrantee}
59Supply and fixing ofLED Street light Fitting with mandatory driver set having die cast aluminium body and lenses suitable for 75 to 90 Watt. And Confirming to IP 66 Protection having company logo Engraved complete in all respect including labour. {8250-9900 system lumens high power LED with lenses, >110 Lm/w PF>0.95, THD<10% at full load, CRI>70, poated driver set (Not Circuitory) phase to phase protection at 440V and >300 V auto cut and restart feature with 5 year warrantee}
60Supply and fixing of power plug with 15A/250 voltflush type switch and 5 pin 15A/250V flush type universal socket in suitable M.S. box of 175mm x 100mm x 50mm size with phenolic laminated bakelite sheet cover 3mm thick fixed with brass machine screw and cup washer.
61S/O LED Bulb 15 Watt
62S/F 6 Amp to 32 Amp SPMCB (10 KA)
63S&F of 63Amp. DP MCB (10 KA)
64S&Fof 63Amp. 415 V metal clad T.P. rewireable type switch fuse unit on angle iron bracket complete
65Supplyandlayingof aluminiumconductorPVCinsulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.
66A- 10 sq.mm x 4 core cable
67Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring ofthe cable shall be properly connected with the earth as per direction of Engineer-Incharge.
68A- 10 sq.mm x 4 core cable
69Supply and fixing of plain or pin type copper tin plated cable socket ( lug ) to the cable leads, insulating with tape and making connection etc. complete in all respect as per direction of the Engineer-Incharge.
70A- 6 sq.mm
71B- 10 sq.mm
72Supply and burying of 600mm x 600mm x 6mm G.I. plate vertically for earthing with its top at least 3 metres below ground level complete with 20mm dia G.I. pipe and funnel for watering and one earthing lead oftwo no. 8 to 10 SWG GI wire in 15mm dia G.I. pipe up to switch board (from appron to switch board the cost of G.I. pipe and G.I. wire will be extra) 30cm square C.I. frame with hinged cover masonry housing alternate layers of charcoal/coke and salt at least 150mm thick alround etc. as per directions of Engineer-in-charge complete in all respect.
73Supply and laying of 25mm x 3mm G.I. strip from earth electrode directly in the ground as required complete in all respect.
74Supply and laying of 1800mm x 900mm x 12mm thick chequered rubbbber matting of tested quality.
75Supply and fixing of shock treatment chart (prescribed under I.E. rules) duly framed with glass and supported from back with hard board or soft board with supply of all material labour T&P for proper completion of work.
76Erection and testing of ceiling fan and regulatoretc. excluding supply of down rod, complete in all respect.
77Supply and fixing of fire extinguisher, ABC Type 4.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work.
78Supply and fixing of fire bucket, round bottom made of G.I. sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand,water as per directions of Engineer-in-Charge.
79Supply and fixing of electronic fan regulator 120-280 V. ISI marked, on the existing switch board including making connections, required material, labour T&P etc. for proper completion of work to the satisfaction of Engineer in charge of work.
80Supply and fixing of switch box 200 x 250 x 65 mm size of approved make made up of 1.0 mm thickISI Marked G.P.sheet All 4 corners folded & spot welded for screw and holes plugged with PVC Nylon Caps . Two or more holes for pipe entryof 25.4 mm on upper and lower sides of the box. Holes shuld be semi-shuttered type and fitted with heavy brass Earth Piller duly screwed & brand name should be embossed. Box flushed in wall including cutting of brick work, fixing it to the level with cement sand mortar, including matching colour wash with s/o all materials, labour and T&P required for proper completion of work as directed at site by the Engineer in charge.
81Supply of Ceiling fan with fan motor of AC permanent installation , capacitor, rating, conforming BEE 5 star rating and IS: 374/79 and also comply with IS:1709/1984 with latestammandment. The rated voltage 220/240 Volts, 50Hz, 1-ph AC the fan assemble should consists of down rod blades, shackle canopies etc and with double ball bearing system BEE 4 star rated 1200mm sweep size
82S/F of Air Fresh Fan 300mm
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail