Tender For Repair/Maintenance Of Medical Gas Pipe Line And Connected Items At Mh Jaipur Under Age E/M Of Ge Jaipur, jaipur-Rajasthan

Military Engineer Services-MES has published Tender For Repair/Maintenance Of Medical Gas Pipe Line And Connected Items At Mh Jaipur Under Age E/M Of Ge Jaipur. Submission Date for this Tender is 20-03-2024. Medical Gas Tenders in jaipur Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

42427339
Corrigendum : Tender For Repair/Maintenance Of Medical Gas Pipe Line And Connected Items At Mh Jaipur Under Age E/M Of Ge Jaipur
Open Tender
Indian
Rajasthan
jaipur
20-03-2024

Tender Details

Tender For Repair / Maintenance Of Medical Gas Pipe Line And Connected Items At Mh Jaipur Under Age E / M Of Ge Jaipur

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 13-Mar-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 20-03-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 24000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work : REPAIR/MAINT OF MEDICAL GAS PPE LINE AND CONNECTED ITEMS AT MH JAIPUR UNDER AGE E/M OF GE JAIPUR
Sl. No. Item Description
1Material and labour for opening of semi-automatic control panel servicing of control panel at OT Building , NICU, Surgical ward & Family II building complete by leak detection, checking of all parts and clening the inner body, valveetc by removing sludge etc and reassemblingafter repair and replacement of unserviceable parts of the same and testing complete
2All as per item no 1 here in before but for oxygen mainford system complete.
3All as per item no 1 here in before but for emergency oxygen regulater system complete.
4All as per item no 1 here in before but for oxygen gas outlet system complete.
5S & F in repair emergency oxygen regulater complete all as specified and directed. Make GHL / M.R. Engg Works Pvt Ltd / Aktive or equivelent as approved by GE
6Supply and fix in repair Copper tail pipe of system complete all as specified and directed. Make GHL / M.R. Engg Works Pvt Ltd / Aktive or equivelent as approved by GE
7Supply and fix in repair NRV of dia 22mm made up of brass complete all as specified and directed. Make GHL / M.R. Engg Works Pvt Ltd / Aktive or equivelent as approved by GE
8Supply and fix in repair Oxygen Gas outlet with polycarbonate outer cover, front plate of aluminium, internal mechanism of brass complete all as specified and directed. Make GHL / M.R. Engg Works Pvt Ltd / Aktive or equivelent as approved by GE
9Supply fixing, testing and commissioning, painting with colour code and errection of DHP medical grade pipe solid drawn, semless, dioxidised, non-arsenical, half hard tempered and degreased,materials confirming to BS: 6017/1981 Table -2 (Cu-DHP) manufactured as per BS"2871/1971 part 1 Table X and dimension tolerance confirming to BS-EN 1057. pipe fitting confirm to BS -EN 12543: 1998ofsize 12 X 0.7 MMOD complete all as specified and directed. Make for item No. 9 to 12 :Janaya / Mexflow / Helix or eqvt as approved by GE
10All as per srl item No. 09 above but size 15 X 0.9 MM OD complete all as specified and directed.
11All as per srl item No. 09 above but size 22 X 0.9 MM OD complete all as specified and directed.
12All as per srl item No. 09 above but size 28 X 0.9 MM OD complete all as specified and directed.
13Material and labour for leak detection and rectifying the same by cutting existing DHP Medical line for inserting new medical pipeline including brazing / welding and other connected item as required on site complete all as specified and directed. Note: The cost of piece of pipe and necessary fitting used in leakage rectification is deemed to be included in the quoted rates.
14Repair /servicing ofGas outlet points with probe parkodex typefor Vacuum, copper stubs around 175 mm long, 12 mm OD copper pipe complete all as specified and directed.
15Supply and fix in repair of isolation valve with adapter ball valve type working tempeturer (-30 degree to 180 degree) For 12 MM OD pipe complete all as specified and directed
16All as per srl item No. 15 above but for 15 MM OD pipe complete all as specified and directed
17All as per srl item No. 15 above but for 22 MM OD pipe complete all as specified and directed
18All as per srl item No. 15 above but for 28 MM OD pipe complete all as specified and directed
19Repair and servicing of Oxygen manifold main with middle frames 2x4 cylinder Oxygen manifold including checking of NRV, rectification of leakage (if any), PVC sheets and tail pipe servicing complete all as specified and directed.
20Repair and servicing of Oxygen manifold main with middle frames 2x2 cylinder Oxygen manifold including checking of NRV, rectification of leakage (if any), PVC sheets and tailpipe servicing complete all as specified and directed
21Supply and fix in repair Two Gas Area Alarm System Digital display with sensor, digital display of gas pressure, high and low setting of audio-visual alarm complete all as specified and directed.Make : GHL / M.R. Engg Works Pvt Ltd / Aktive or equivelent as approved by GE
22All as per srl item No. 21 above Three Gas Alarm system complete complete all as specified and directed
23All as per srl item No. 21 above Four Gas Alarm system complete all as specified and directed
24Supply and fix in repair ofTwo Gas Valve box with regulator with bypass system complete all as specified and directed. Make GHL / M.R. Engg Works Pvt Ltd / Aktive or equivelent as approved by GE
25All as per srl item No. 24 above but Three Gas Valve box complete all as specified and directed.
26All as per srl item No. 24 above but Four Gas Valve box complete all as specified and directed.
27Supply and fix in repair BPC Flow meter with humidifier bottle and capacity 1 to 12 lpm with inlet pressure of 50 to 60 psi, humid fire 250 CC polycarbonate body complete all as specified and directed. Make : GHL / M.R. Engg Works Pvt Ltd / Aktive or equivelent as approved by GE
28Supply and fix in repair Wall mounted Bed Head Panel - 900 MM Long forof 02 nos oxygen outlet , 01 no medical vacuum outlet and 02 nos BS 15 Amp standard electric switch and socketwith double rail (Vertical) as per sample approvedcomplete all as specified and directed. Make GHL/M.R. Engg Works Pvt Ltd / Aktive or equivalent as approved by GE.
29M&L for reapair /maintenance of Wall mounted Bed Head Panel - 900 MM Long for 02 nos oxygen outlet , 01 no medical vacuum outlet and 02 nos BS 15 Amp standard electric switch and socketwith double rail (Vertical) as per sample approved complete all as specified and directed. Make GHL/M.R. Engg Works Pvt Ltd / Aktive or equivalent as approved by GE.
30Supply and fix in repair DOL starter, 5HP(MU1) suitable for upto 5HP 3 phase, 415 volts AC supply motor complete all as specified and directed. Make:- L&T Cat part No SS-95647 or equivalent in siemens, schneider as approved by GE.
31Opening of vacum pump and servicing of vaccum pump at Oxygen building complete by replacement of oil, coolent, V belts, greasing and oiling of parts and clening the inner body, tank, radiator etc by removing sludge etc and reassembling the vaccum after repair and replacement of unserviceable parts of vaccum pump and testing complete all as specified and directed. Note : Oil, coolent, v belts etc shall be inclusive in quoted rates.
32All as per item No. 31 above but for suction trolly system complete all as specified and directed.
33All as per item No. 31 above but for vaccum gas outlet system complete all as specified and directed.
34Supply and fix in repair suction trolly suitable for 5 HP vacuum pump with 2*2000 ml polycarbonate jar, regulator with aluminium body and platform made of iron complete all as specified and directed. Make GHL/M.R. Engg Works Pvt Ltd / Aktive or equivalent as approved by GE.
35Supply and fix in repair ward vaccum unit having 1 * 2000 ml polycarbonate jar and regulator made of aliuminium compatible with the existing system complete all as specified and directed. Make GHL/M.R. Engg Works Pvt Ltd / Aktive or equivalent as approved by GE.
36Supply and fix in repair vaccum gas outlet with polycarbonate outer cover, front plate of aluminium, internal mechanism of brass complete all as specified and directed. Make GHL/M.R. Engg Works Pvt Ltd / Aktive or equivalent as approved by GE.
37Note:- The contract sum shall be calculated by deducting the amount shown in Credit Schedule attached to this tender, from total amount of Schedule "A"/BOQ