Tender For Supply, Installation, Testing, Commissioning Of Hvac Work At Regional Cancer Institute (Phase-Ii), Jodhpur, jodhpur-Rajasthan

Rajasthan State Road Development And Construction Corporation Limited has published Tender For Supply, Installation, Testing, Commissioning Of Hvac Work At Regional Cancer Institute (Phase-Ii), Jodhpur. Submission Date for this Tender is 12-03-2024. HVAC Tenders in jodhpur Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

42427147
Corrigendum : Tender For Supply, Installation, Testing, Commissioning Of Hvac Work At Regional Cancer Institute (Phase-Ii), Jodhpur
Open Tender
Indian
Rajasthan
jodhpur
12-03-2024

Tender Details

Tender For Supply, Installation, Testing, Commissioning Of Hvac Work At Regional Cancer Institute ( Phase-Ii ) , Jodhpur

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 05-Mar-2024 Corrigendum Other 12-03-2024

Key Value

Document Fees
INR 2360 /-
EMD
INR 560000.0 /-
Tender Value
INR 2.80 Crore /-

BOQ Items

Name of Work: SITC of HVAC work at Regional Cancer Institute (Phase II), Jodhpur.
Sl. No. Item Description
1Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia
2150 mm dia per running inch length
3Supply, Fabricating & installing following sizes of perforated Powder coated MS cable tray with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
4150mm x 50mm x 1.6mm
5450mm x 50mm x 2.0mm
6300mm x 50mm x 1.6mm
7Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as requiredcomplete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
8Supply,Installation, Testing & Commissioning of modular type VariableRefrigerantFlow/VariableRefrigerantVolumeaircooled Outdoorunitssuitable for cooling and heating,having100% hermetically sealed inverter type Scroll Compressor(s) withand minimum two compressors along with two Condensing fan,above 14/18 HPmodules,microprocessorbased Controller, Side / top discharge type condensing unit(s), with R-410 A Refrigerant,vibrationisolators,withsuitablefoundationetc. completeasrequired.Theunitshalldelivertheratedcapacityat AHRIConditions andwork evenat 50°C ambient temperature without tripping.The unit shall be suitable to work on 400V +/- 10%, 3Phase,50HzACpowersupply.Theunit shallbefilledwithfirst charge of the refrigerant and ready for use as required. The EER at 100% load with AHRI conditions shall not be less than 3.5 andIncluding OEM supplied Piping connection Kit etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Make :- HITACHI /MISTUBHISHI /DAIKIN /OGENERAL . THE COMPLETE AC SYSTEMSHALL BE IN THE COMPREHENSIVE MAINTANANCE PERIOD OF FIVE YEARS AND SHALL BE MAINTANED BY THE OEM OR ITS AUTHORISED DISTRIBUTOR.
9Supply,installation,testingandcommissioningoffollowing minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor,coilsection with DXCoppercoil,electronicexpansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation,Cordedremotecontroletc., suitableforoperationon single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down valve in case of fire on receivingsignalfromBMSSystem. Thecoolingcapacityofindoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
10Ceiling Mounted4 Way Cassette type Units with Remote Control
111.6 TR
122 TR
132.4 TR
14Supply, installation, testing & commissioning of Group controller for monitoring the status and working condition of all indoor and outdoor units, The controller shall act as an advanced air conditioning management system to given complete control of VRV/VRF air conditioning equipment with Starting/stopping of air-conditioning as a zone or group of individual units. Temperature setting for each Indoor units of zone, Switching between temperature control modes, switching of the fan speed and direction of airflow, enabling/disabling of individual remote controller operation, Alarm code display in case of any problem. It shall be able to control up to 64 (max. 512 if required) number of Indoor units. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
15Supplying and installation of high-pressure grade required size OEM make copper connectionY or T Joints / refnet for liquid and suction line complete erected on wall/ceiling with supports/raceways, Nitrile rubber insulation, painting etc. with brazing and testing for leakages confirming the normal operation of the VRV / VRF air conditioning system. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
16Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping withfittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing,support with MS hanger on ceiling or recessed in wallwith chasing & plastering with 6 mmthickclosedcellelastomeric nitrile rubberinsulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1725 mm
1832 mm
1940 mm
20Supplying and drawing Fire Resistant flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existingsurface or recessed PVC/ MS conduit/casing capping/ Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
212 x 1.5 Sq.mm Unarmoured With Outer Sheath in Red Color
22Supply , Installation, Testing and Comissioning of site fabricated ducting made from GI sheet metal conforming to IS:277 with a zinc coating grade not less than 120 GSM (both side inclusive)& fabricated as perIS:655 and as per approved drawings & designs including the cost of hangers, supports, angle, expansion fasteners , closed cell neoprene gasket T&P etc. as required of following thickness. Test Certificate for Galavanizing with lot no. to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
230.60 mm
240.80mm
25Supply & fixing of external thermal closed-cell Nitrile rubber Insulation material FM/UL approved with high water vapor diffusion resistance and low thermal conductivity should be certified "Class O" in Fire Propagationas per BS 476 Part 6 in form of sheet on duct including cost of adhesive (CPRX Compound) complete as required.All as per pre approved by Engineer in charge.Make:- Aflex, kflex, supreme, Armacell
2613mm thick for indoor Application
27Supply and fixing of acoustic lining of ducts withchemically cross link Oxide accetate foam open cell structure Acoustic Insulation with density 30 Kg / Sqm, UV protected and Class O Fire propperty Water Vapour absorption 0.002 gm / Sqcm,including cost of adhesive etc. complete in all respect.All as per pre approved by Engineer in charge.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
2815 mm thick
29SITC of Interconnecting refrigerantcopper pipe forsplit/Ductable/ Casseette AC of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink MarkBrand Printing on Hard Tubes should be present. Piping between each set of indoor & outdoor units of different sizesas per OEM requirement & specifications including class "O" Nitrile rubber sleeves, chase cutting, supports, making good the same with sand cement plaster etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
30Supplying, installing, testing and balancing of extruded Aluminium powder coated Air Diffuser and complete with Flush, 20mm flanges with PVC/neoprene gasket, anti – smudge frame and removable inner core to facilitate the adjustable of air control damper, square/round/ rectangular as required.including fixing with steel screws etc. complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
31Supply Air Diffuser with Volume Control damper
32Return Air Diffuser without Volume Control damper
33P & F of Fire retardent flexible canvass connection made of fibreglass weave having silver grey silicon rubber coating, of height 200 mm with sufficient fold to avoid transmission of vibrationwith GI frame ,Gasket Nut Bolts for air cooling Plants/AHU/FCU etcas required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
34Gas charging of VRF/VRV system with R410A refrigerant gas. Before gas charging system shall be flushed with high purity Nitrogen Gas to remove carbon content, dirt particles to make sure that there is no chance of mixing any impurity with Refrigerant Gas. Thereafter System shall be tested with Nitrogen Gas at 1.5 Times of working pressure of R410 Refrigerant Gas to ensure leakproof system. Whole system shall be Vacuumed up to 500-micron level which ensures the zero-moisture content level in piping to ensure better cooling efficiency and long life of the system. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .