Tender For Repairs, Servicing And Periodical Maint Of Package Type And Central Ac Plant At Att And Chilled Water Plant At Cadet Mess Including Allied Wks Under Ge Nda Khadakwasla, khadakwasla-Maharashtra

Military Engineer Services-MES has published Tender For Repairs, Servicing And Periodical Maint Of Package Type And Central Ac Plant At Att And Chilled Water Plant At Cadet Mess Including Allied Wks Under Ge Nda Khadakwasla. Submission Date for this Tender is 18-03-2024. HVAC Tenders in khadakwasla Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

42373886
Corrigendum : Tender For Repairs, Servicing And Periodical Maint Of Package Type And Central Ac Plant At Att And Chilled Water Plant At Cadet Mess Including Allied Wks Under Ge Nda Khadakwasla
Open Tender
Indian
Maharashtra
khadakwasla
18-03-2024

Tender Details

Repairs, Servicing And Periodical Maint Of Package Type And Central Ac Plant At Att And Chilled Water Plant At Cadet Mess Including Allied Wks Under Ge Nda Khadakwasla

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 11-Mar-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 18-03-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 20000.0 /-
Tender Value
INR 10 Lakhs /-

BOQ Items

Name of Work: REPAIRS, SERVICING AND PERIODICAL MAINT OF PACKAGE TYPE AND CENTRAL AC PLANT AT ATT AND CHILLED WATER PLANT AT CADET MESS INCLUDING ALLIED WKS UNDER GE NDA KHADAKWASLA
Sl. No. Item Description
1M & L for prepartion of old painted metal surfaces of any description, with scrapping removing, dusting, and applying one coat red oxide primer and two coats synthetic enamel paint as per existing colour with spray gun of different tint as appoved by Engr-in-Charge (External surfaces of pipe, shell, tube type condensser any size,Cooling water pump/condenser water pump sets up to 10 HP including base frame and condenser water pipe line from condenser to cooling tower including cooling tower frame ) complete all as specified and directed.
2Preparation of Old Painted metal surfaces of any description for applying Primer/Zinc Chrome.
3Material and Labour in Painting of metal surfaces of any description over 10cm in width or girth With One Coating of Priming with red oxide zinc crome (Per Coat - Rs 32.00 per Sqm SSR 17029)
4Material and Labour in Painting ofmetal surfaces of any description With Two Coating of Glossy paint as per Standard colour code(Per Coat - Rs 45.60 per Sqm SSR 17029)
5Taking out existing unserviceable "V" belt of compressor and supply and fix in replacement new "V" belt Make Fenner type C-3000/ 116 or equivalent make as approved.
6Taking out existing unserviceable "V" belt of AHU blower and supply and fix in replacement new "V" belt Make Fenner type B- 1882/LP/B70 or equivalent make as approved.
7Dismantling of compressor of Central type Air conditioner of capacity upto40TR installed at ATT Plant(Make :ACCEL , Model : SMC 4 100S) and over hauling the same by replacing unserviceable / worn out parts including necessory machine work to the crank shaft, discharge valve plate etc for proper repair.Servicing of Oil pump by replacing oil pump repair kit. Reassembling the compressor unit with existing serviceable parts and new parts given here in after(as supply and fix only), rectifying other deffects if any, Charging of Refrigerant gas (R-22) and Compressor Oil upto the required level to achive desired cooling effect,Connecting the compressor with thelines and testing commissioning complete all as directed by Engr- in Charge.
8Note for Ser. Item No. 4 above: i) Parts required for replacement shall be measured and paid seperately under respective items ii)Unit rate includes retrieving - after Pumping down - of existing refrigerant & drain off Compressor oil from the plant, preserve carefully and re-use the same after overhauling of Compressor. iii)Additional quantity of Refrigerant Gas & compressor oil required for the job for satisfactoryrunning of plant shall bemeasured and paid seperately under respective items iv)Any Minor repair or small parts (costing up to Rs 1000/-) those are not covered in itemabove shall to be borne by the contractor and rate for the same should be included with the quoted unit rate.
9Cleaning of shell and tube type condenser of Central type Air conditioner 40 TR Capacity ( Installed at ATT Plant ) with dilute hydrochloric acidand brushing in to internal portion of condenser including replacement of gasket,testing after cleaning complete all as directed by Engineer - in - Charge.
10Supplyand fix in replacement ofPiston assy cast Aluminium including Piston rings, scraper rings & Seeger ringscomplete of compressor (Make :ACCEL , Model : SMC 4 100S) and all as directed.
11Supply and fix in replacement ofinletValve set suitablefor exisitng liquid pipe line as directed (Make : ACCEL , Model : SMC 4 100S).
12Supply and fix in replacement of springs for inlet and outlet valve suitable for existing type as directed (Make : ACCEL , Model : SMC 4 100S).
13Supply and fix in replacement of Hygrometer temperature indicator suitable for existing type as directed (Make : ACCEL , Model : SMC 4 100S).
14Supplyand fix in replacement of Piston sleeves of compressor (Make : ACCEL , Model : SMC 4 100S) complete all as directed.
15Supplyand fix in replacement of Plunger for unloading mechanism of compressor (Make :ACCEL , Model : SMC 4 100S) complete all as directed.
16Supplyand fix in replacement of Piston pin of compressor (Make : ACCEL , Model : SMC 4 100S) complete all as directed.
17Supplyand fix in replacement of bush for Piston pin of compressor (Make : ACCEL , Model : SMC 4 100S) complete all as directed.
18Supplyand fix in replacement of Half section of bearing of compressor (Make : ACCEL , Model : SMC 4 100S) complete all as directed.
19Supplyand fix in replacement of Suction and discharge reed with valve plate of compressor (Make : ACCEL , Model : SMC 4 100S) complete all as directed.
20Supplyand fix in replacement of set of shaft seal complete of compressor (Make : ACCEL , Model : SMC 4 100S) complete all as directed.
21Supplyand fix in replacement of Gasket setcomplete of compressor (Make : ACCEL , Model : SMC 4 100S) complete all as directed.
22Supplyand fix in replacement of oil heater complete of compressor (Make : ACCEL , Model : SMC 4 100S) complete all as directed.
23Supplyand fix in replacement of oil pumprepair kit complete of compressor (Make : ACCEL , Model : SMC 4 100S) complete all as directed.
24Supplyand fix in replacement of connecting rod of compressor (Make : ACCEL , Model : SMC 4 100S) complete all as directed.
25M&L for Refrigerant Gas Leakage Testing with Nitrogen Gas Leak test including all equipmentand necessary brazing and replacement arrengement for arresting leakage and Charging the required quantity of similar Gas as per existing refrigerant and reconfirmation of leakage removal for various cooling appliences at different placesall as directed.
26Supplyand fill compressor oil of suitable grade POE complete all as directed. Make : Seetal/ Gulf/Veedal/Waxpal
27Taking out existing unserviceable "V" belt of compressor and supply and fix in replacement new "V" belt. Make : Fenner type SPC-4000 or equivalent make as approved.
28Taking out existing unserviceable Pressure control device and supply and fix in replacement new Pressure control device(High pressure cut off with indicator) type MP-5 complete all as directed.Make : Danfoss /Indfoss
29Taking out existing unserviceable Pressure control device and supply and fix in replacement new Pressure control device (low pressure cut off with indicator) type MP-1,complete all as directed. Make : Danfoss /Indfoss
30Taking out existing unserviceable Pressure control device and supply and fix in replacement new Pressure control device(High pressure cut off with indicator) type MP-15 complete all as directed.Make : Danfoss /Indfoss+E116
31Taking out existing unserviceable Oil Pressure control device and supply and fix in replacementnew Oil Pressure control device (Oil pressure cut off with indicator) type MP-35 complete all as directed. Make : Danfoss /Indfoss
32Taking out existing unserviceable Oil Pressure control device and supply and fix in replacement new Oil Pressure control device (Oil pressure cut off with indicator) type MP-55 complete all as directed. Make : Danfoss /Indfoss
33Taking out existing unserviceable Loading/unloading solenoid Valve three way 1/4BSP, 22 bar pressure, 100 degree C, 230 Voltand supply and fix and fix in repairs new Loading/unpoading soloniod Valve three way 1/4BSP, 22 bar pressure, 100 degree C, 230 Volt complete all as directed. Make : Danfoss /Indfoss
34Taking out existing unserviceable High Pressure gauge and supply and fix in replacement new highPressure gauge 0-25 Kg/cm square as per existing size complete all as directed. Make : AE/Conserve/HP/Electron/Febic
35Taking out existing unserviceable Low Pressure gauge and supply and fix in replacement new Low Pressure compound gauge 0-16/0-(-760) Kg/cm square suitable for R-22 as per existing size complete all as directed. Make : AE/Conserve/HP/Electron
36Taking out existing unserviceable monometergauge and supply and fixin replacement new Monometer water suction gauge 0-10.6 Kg/cm squareas per existing size complete all as directed. Make : AE/Conserve/HP/Electron/Fiebig
37Taking out existing unserviceable monometergauge and supply and fixin replacment new Monometer water Discharge gauge 0-21 Kg/cm squareas per existing size complete all as directed. Make : AE/Conserve/HP/Electron/Fiebig
38Taking out existing unserviceable water pressure switch and supply and fix in replacement new water pressure switch (IPS) for oil air water stemas per existing size complete all as directed. Make :Danfoss /Indfoss
39Taking out existing unserviceable liquid solenoid valve and supply and fix in replacement new liquid solenoid valve/pilot solenoid valve MAG-2, 208-240V, 50-60 Cy, 15W as per existing size complete all as directed. Make : Danfoss /Indfoss
40Taking out existing unserviceable filter dryer 1/4 inch outer thread, C-032F and supply and fix in replacement new filter dryer 1/4 inch outer thread, C-032F as per existing size complete all as directed. Make : Danfoss /Indfoss
41Dismantiling carefully all water connections, decoping of pumps from electric motor taking out from foundation and transporting pump body to workshop for necessary machining works as directed and reqd and reinstalling the pump to its original position and commissioning etc instaled at Habbibullah hall/ATT Plant for different capacity.
42Supply and fix in replacement coupling made of MS cast block/ Rubber Muff Coupling with suitable accessories for existing pump & motor of make Kirloskar model suitable for 15HP/10 HP including nut, bolts & rubber bushings etc complete.
43Repair and rewinding of electric induction motor by using super enamelled copper wire (Class-F) as per existing gauge, heating and varnishing complete. The repair work involves taking out burntout winding coiles from stator, cleaning of slots throughly , removing all dirt grease an other unwanted particle, replacmement of UNSV parts where reqd (as directed) capacity of motor 50 HP complete all as direced by Engr-in -charge NOTE : (i)Unit rate is deemed to be included for taking out motor from its position, shifting of motor from pump house to workshop, getting back to plant house, reinstalling at site, connecting up, couple and aligning with the pump and testing complete, retrieved winding wire will be the contractor"s property and necessary credit amount is deemed to be included in the quoted rate, hence no credit has been considered in credit schedule. (ii)Spare parts other than rewinding job required for replacement shall be measured and paid separately as supply and fix only.
44Repair and rewinding of electric induction motor by using super enamelled copper wire (Class-F) as per existing gauge, heating and varnishing complete. The repair work involves taking out burntout winding coiles from stator, cleaning of slots throughly , removing all dirt grease an other unwanted particle, replacmement of UNSV parts where reqd (as directed) capacity of motor 20/15/10 HP complete all as direced by Engr-in -charge NOTE : (i)Unit rate is deemed to be included for taking out motor from its position, shifting of motor from pump house to workshop, getting back to plant house, reinstalling at site, connecting up, couple and aligning with the pump and testing complete, retrieved winding wire will be the contractor"s property and necessary credit amount is deemed to be included in the quoted rate, hence no credit has been considered in credit schedule. (ii) Spare parts other than rewinding job required for replacement shall be measured and paid separately as supply and fix only.
45Dismantling/opening the pump part by part without damaging any other parts , descaling and cleaning of all parts for inspection and finding serviceability/unserviceability of the parts and carefully assembling of pumps by using existing serviceable parts including replacement of PTFE gasket packing greasingall bearings, bushing,etc and replaement of unserviceable parts as directed installed at Habbiullah Hall/ATT Plant 10/15/20 HP ( Cooling water pump/ Blower motor of AC plant ),thoroughly,complete refix at their existing positionreinstall the pumpr at existing position, complete all electric connections and testing complete all as directed. .
46Preventive maintenance of AC, 3 Phase induction motor of capacity 20/15 HP by dismanteling the motor completely without damaging any parts and applying air dry insulating varnish, of appropriate grade (make doctor bake/appex), cleaning bearing refix at their existing position with bearing grease, checking terminals and thimbles tighting the all terminal joints replace terminal plates where necessary/reinstall the motor at existing position, connecting electric connections and testing complete all as directed by Engr-in-Charge.
47Preventive maintenance of AC, 3 Phase induction motor of capacity 7.5/10 HP by dismanteling the motor completely without damaging any parts and applying air dry insulating varnish, of appropriate grade (make doctor bake/appex), cleaning bearing refix at their existing position with bearing grease, checking terminals and thimbles tighting the all terminal joints replace terminal plates where necessary/reinstall the motor at existing position, connecting electric connections and testing complete all as directed by Engr-in-Charge.
48Taking out existing burnt contactor from panel and supply and fix in replacement new connecting 3 Pole power contactor, 415 Volt, AC 3 Phase,AC3 rating 80 Amps, AC 3 Phase,AC1 rating 100 Amps,with 400/230 Volt coil,(as per existing ) Conforms to IS / IEC 60947-4-1 & IEC 60947-4-1. MakeL&T /C &S/BCH/Schneider.( Power contactors may be of different make as fitted in existing pannel so that the contactors have to be accommodated in its position) complete all as directed.
49Taking out existing burnt contactor from panel and supply and fix in replacement new connecting 3 Pole power contactor, 415 Volt, AC 3 Phase,AC3 rating 40 Amps, AC 3 Phase,AC1 rating 55 Amps,with 400/230 Volt coil,(as per existing ) Conforms to IS / IEC 60947-4-1 & IEC 60947-4-1. Make L&T /C &S/BCH/Schneider.( Power contactors may be of different make as fitted in existing pannel so that the contactors have to be accommodated in its position) complete all as directed.
50Taking out existing burnt contactor from panel and supply and fix in replacement new connecting 3 Pole power contactor, 415 Volt, AC 3 Phase,AC3 rating 25 Amps, AC 3 Phase,AC1 rating 45 Amps,with 400/230 Volt coil,(as per existing ) Conforms to IS / IEC 60947-4-1 & IEC 60947-4-1.Make L&T /C &S/BCH/Schneider.( Power contactors may be of different make as fitted in existing pannel so that the contactors have to be accommodated in its position) complete all as directed.
51Taking out defective burnt contactor from panel and supply and fix in replacement new connecting 3 Pole power contactor, 415 Volt, AC 3 Phase, AC3 rating 18 Amps AC1 rating 20 to 32 Amps,with 400/230 Volt coil,(as per existing ) Conforms to IS / IEC 60947-4-1 & IEC 60947-4-1 Make L&T /C &S/BCH/Schneider.( Power contactors may be of different make as fitted in existing pannel so that the contactors have to be accommodated in its position) complete all as directed.
52Taking out defective Thermal over load relay and supply and fix in replacement new relay type AUR1 make Schneider or equivalent of L&T /C &S/BCH/Schneider.( Relays may be of different make as fitted in existing pannel so that the relays have to be accommodated in its position) complete all as directed.
53Taking out defective burnt out MCCB 200A, 3 Pole and supply and fix in replacement new MCCB 200A, 3 Pole, 36kA,Conforms to IS/IEC 60947-2 & IEC 60947-2 make Schneider or equivalent of L&T /C &S/BCH/Schneider.( MCCBs may be of different make as fitted in existing pannel so that the MCCBs have to be accommodated in its position) complete all as directed.
54Taking out defective burnt out MCCB 310A, 4 Pole and supply and fix in replacement new MCCB 310A, 4 Pole, 36 kA Conforms to IS/IEC 60947-2 & IEC 60947-2 make Schneider or equivalent of L&T /C &S/BCH/Schneider.( MCCBs may be of different make as fitted in existing pannel so that the MCCBs have to be accommodated in its position) complete all as directed.
55Taking out existing burnt Add on auxilary contact blockfrom panel and supply and fix in replacement new connecting Add on auxilary contact block with 2 NO + 2NC, front mounted ,415 Volt,Make L&T / C &S/BCH/Schneider.( Add on block may be of different make as fitted in existingso that the blocks have to be accommodated in its position) complete all as directed.
56Taking out existing burnt timerfrom panel and supply and fix in replacement new Timer 0-30/60Sec pluse time 50-100 msec, 800 SD 2-230 selce,415 Volt, reqd for star deltaMake L&T /C &S /BCH / Schneider.(Timer may be of different make as fitted in existingso that the timer have to be accommodated in its position) complete all as directed.
57Supply and fix in replacment ofof Miniature circuit breaker triple pole 415 volt, 25-63 Amps having rupturing capacity 10kA "C" Series complete all as directed.Make : Havells/ C&S/ L&T/ Legrand.
58M&L for servicing the Air handling units for compressor of capacity 40/55 TR, with and including cleaning complete units, sheet metal parts, blowing out the dust, chemical cleaning by spraying the organic based scale removing agent Vaniklin at the appropriate ratio till removal of complete dust & scale deposits in the fin area of evaporator coil, flushing through for proper air flow across the coil, cleaning of expansion valve; greasing of blower motor, checking of electrical connection, cleaning of air filters,prefilters & fine filters box type with washable nylon filters media having 90% efficiency to control dust particles up to 10 microns fitted in aluminum framed with both side wire mesh of size 610x610x50mmof class EU-4 and for fine filters 99% efficiency to control dust particles up to 10 microns 610x610x500 mm EU-7 as per samplesuitable for 40 TR AHU plant,greasing of blower motor,replacement of unserviceable bearings,water drain lines, renewal of rusted sheet metal screws, and testing & commissioning the unit all as specified and as directed by Engineer-in-Charge.
59Material and Labour for cleaning and servicing of Cooling Tower at ATT (100 TR ) including changing of defective deflectors, Sprinklers, Fan Blade, Rotor etc.
60Material and Labour for cleaning and servicing of Cooling Tower at Habibullah Hall (150 TR) including changing of defective deflectors, Sprinklers, Fan Blade, Rotor etc.
61Material and Labour for supply, install PVC Corrugated honey comb type of size each 600mm x 300mm x 150mm Cooling Tower Fins/ Fills in Cooling towers of 150.0 TR and 100.0 TR
62Material and Labour for cleaning and servicing of Package Type AC at Habibullah Hall of 8.50 TR -Cleaning the Indoor and Out Door units, Checking for any leakges in the gas copper pipelines and charging with refrigeration gas as required after rectification of faults/ Leakages
63Supply and fix in replacement ofconnectingIntegrated circuit board with all electronic components suitable for 8.5 TR capacity Carrier Pakage type Air conditioner complete all as directed.
64Supply and fix in replacement ofconnecting in replacement high pressure cut off valve 275 lbs suitable for 8.5TR capacity package AC of make Carrier complete all as directed.
65Supply and fix in repairs connecting in replacement low pressure cut off valve 25 lbs suitable for 8.5TR capacity package AC of make Carrier complete all as directed.
66Supply and fix in repairsconnecting in replacement SPPR Circuit board suitable for 8.5TR capacity Package type AC complete all as directed. Make : Carrier.
67Supply and fix in replacement of only electronic sensor unit (PCB) suitable for 8.5 TR Package type AC of any make as ordered.
68Supply and fix 10A Digital thermostat of dual mode,Temperature Regulating device of range from -50 degreesto 999 degree Centigradeof K type thermocouple,and alarm mode type required if it exceeds the set temperature value as specified.Model:ZFX-7016K
69Material & Labour in charging refrigerant gas R-22 to AC Plant Compressor equipments complete all as directed by Engineer-in-charge.
70Supply and fix in replacement of Pre-filter made up of GI sheet frame size 65x 25cmwith Nylon wire mesh 10 Micron grade with efficiency morethan 90% suitable of AHU of 2x40 TR Cap Central AC Plant
71Material and Labour in repair Ducting (supply and Return) : Ducting made out of GI sheet with proper gasketing, supports, Consumables rods, incl all accessories such as Corner, Cleat, Carriage bolt, Gasket etc and fabricated as per standards. All flange joints shall be sealed with RTV Sealent to make it air tight. As per SMACNA Standard along with 25 mm accoustic insulation inside the duct.
7222 Gauge
7320 Gauge
74Material and Labour for Duct insulation with resin bonded fibre glass wool roll of density 24 kg/Cum, with factory laminated aluminium vapour barrier, thickness of insulation 25 mm as specified and including the following:- (a) Cleaning the duct surface (to be insulated ) by scrapping carefully with wire brush etc. to make the surface completely free of millscale, dirt, dust, grease and other foreign materials, taking special care so that all duct joints are sealed against any leakage. (b) Applying rubber based adhesive CPRX compound. (c) Sealing of all longitudinal joints and circular overlaps with and including Aluminium cladding with 26 G sheet with and including Aluminium foil tape 50 mm wide, to make the insulation leakproof.
75Servicing & maintenance (as and when directed) of Chilled water storage unit outer and inner side cleaning of condensing unit/all filters, dryers completewith vaccum clenear, soap water, castic soda, colin etc of capacity4.5 HP of any make and any type in situ including, leak testing, brazing the suction / discharge tubes checking electric connection from DBs to machine , sensor unit/cooling effect of airconditioner etc any time during period of the contract for proper functioning complete all as specified and as directed.
76Taking down burnt compressor from chilled water plant and supply and fix in replacement, install connecting and testing of hermetically sealed compressure of capacity 4.5 HP, suitable for R-22 refrigerant, AC 3 phase, 415 volt, 50 Hz, having capacity of cooling 4 C suitable for chilled water plant installed at cadet mess. Model: KCG554HAE, Make: Emerson Copeland or Equivalent
77Taking down burnt fan motorfrom Water chiller plant and supply and fix in replacement new Fan Motor with blade, 415 V, 50 Hz, Three Phasesuitable for chilled water plant installed at cadet Mess
78Taking down burnt chiller tank Automatic water level controller with float controller and motor , Single phase, 240 V, 50 Hz with delay (ON-OFF) - 0.1 sec to 10 sec and indicator with three float level sensor probe from Water chiller plant and supply and fix in replacement new chiller tank water level controller with motor along with three float level sensor probe as per sample/ site requirement and as directed by Engineer - in - Chargesuitable for chilled water plant installed at cadet Mess
79Supply and fix in replacement of float valve 40mm dia high Pressure with Polythene float and flynut complete screwed for iron pipe or brass ferrule, rod of suitable length PVC ball with all connecting items as in repair complete suitable for chilled water plant installed at cadet Mess all as directed. Make : Aurum/zolota/Prayag/leader
80Supply and fix in replacement of solenoid valve- Type HM2 suitable for chilled water plant installed at cadet Mess. Make : Castle/Danfos/Indfos
81Supply and fix in replacement of relay -Type LR1-D12316 suitable for chilled water plant installed at cadet Mess. Make : Castle/Danfos/Indfos
82Supply and fix in replacement of temperature indicator sub-O SZ 7510P suitable for chilled water plant installed at cadet Mess. Make : Castle/Danfoss/Indfoss
83Supply and fix in replacement of temperature indicator sub-T-72 suitable for chilled water plant installed at cadet Mess. Make : Castle/Danfoss/Indfoss
84Supply and fix in replacement of relay MNX-12 suitable for chilled water plant installed at cadet Mess. Make : Castle/Danfoss/Indfoss
85Supply and fix in replacement of relay MNX-A18 suitable for chilled water plant installed at cadet Mess. Make : Castle/Danfoss/Indfoss
86Material and labour for earthing complete with 60cm x 60cm x 6mm thick GI plate electrode buried in ground vertically not less than 2.25mtrs deep below ground level with top edge of the plate not less than 1.5mtrs below ground level with GI strip of size 32 x 6mm as earthing lead with bolts, nuts, checknuts and washers of galvanised iron or steel all as shown in Electrical plate No. 3 connected to earthing test point all as specified including testing on completion including necessary excavation and earth work (in any of strata) providing charcoal dust, salt mixed with fine sand in continuous layers, PCC (1:3:6 ) type C1 in chamber, Precast 50 mm thick in cement (1: 2:4) type B.1 with CI frame with cover, 20mm dia bore light grade GI watering pipe furnel etc fixing of GI Pipe 40 mm bore protection for earthing strip from earth pit to test point complete & making connection all as directed. NOTE: (i) Item includes the cost of 7.5 metre GI pipe for protection of earth lead. Any additional length shall be adjusted through deviation order. (ii)Item includes trhe cost of 7.5 metre GI earth lead. Any additional in length shall be adjusted through deviation order.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail