Municipal Copr Of Greater Mumbai-MCGM has published Tender For Refurbishment And Supply Installation Testing And Commissioning Work Of Fire Alarm System Alongwith Allied Works At Mcgm Ctc, Pho And Bmt Center Borivali (E).. Submission Date for this Tender is 09-02-2024. Alarm Systems Tenders in borivali Maharashtra. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Supply, Installation, Testing & Commissioning of conventional optical type smoke detector complete on box as per Specification |
2 | Supply, Installation, testing & commissioning of conventional Manual Call Point (Pill box) with break glass push button in metal enclosure complete with back mounting box. |
3 | Supply, Installation, testing & commissioning of conventional Hooters with CRCA enclosure complete with external power supply & junction boxes |
4 | Supply, Installation, testing & commissioning of expandable Loop card for main fire alarm electronic control panel, shall support 254devices bothdetectorsand modulesandshall support both class "A" & class "B" wiring. |
5 | Supplying and erecting FRLS armoured cable 4 core 1.5 sq.mm. copper complete erected on wall/ceiling/trusses as per specification |
6 | 75mm x 75mm x 75mm size GI Junction box with kNosck out & 1 Nos. 5Amp. SP switch for local ON, OFF operation |
7 | Cable End Termination For Copper Cables – 4C x 2.5 Sq.mm |
8 | Supply, Installation, testing & commissioning of remote response indicator |
9 | Supplying and erecting ABC powder type fire extinguisher as per IS : 13849 /15683 of 9 kg capacity with necessary clamp for erection on Wall. |
10 | Providing Floor mounting stand for keeping 4 Nos. of FIRE buckets 1500mm in length, 900mm in height frame made out of 30x30x4 mm angle iron with cross supports for legs, welded with 4 hooks and duly painted with one coat of red lead and two coats of silver Paint. |
11 | Providing Round bottom FIRE Bucket of 9 Litres capacity as per IS : 2546 made out of 24 gauge G.I. sheet with extra handle at bottom duly painted white inside and red outside with FIRE Mark, on provided stand/ wall hook. |
12 | SITC of Auto glow signage for Emergency Fire Exit |
13 | SITC of Auto glow signage for Do not use lift in case of Fire etc |
14 | SITC of Auto glow signage for Staircase direction |
15 | 2/3 Independent Plug (IP) |
16 | Supply and installation of 250 watts amplifier with USB |
17 | Supply & installation of 6W/100V wall mounting box speakers. |
18 | Supply & installation of Unidirectional Dynamic Vocal & Speech Microphone |
19 | Supply & installation of Microphone floor stand |
20 | Wiring for speakers with 24/0.2 multi core twin twisted flexible copper. |
21 | 25 mm.- Only PVC Conduits |
22 | SITC of 9 inch Rack |
23 | Solar street light of 24 Watt LED |
24 | Outdoor LED Street Light fittings – 130-150 W |
25 | Swan neck type bracket for fixing HPMV / HPSV lamp fixtures mounting on wall / shed etc. 0.5 to 1.2 Mtrs |
26 | IP 42 Wall/column Mounted distribution board with one Nos of 32A DP MCB as incomer and 2 Noss 16A DP MCB as outgoing (8way SPN DB) |
27 | 1 st category Al armoured cables FRLS outer sheathed- 2C x 6.0 Sq.mm |
28 | Cable End Termination For Aluminium Cables – 2C x 6 Sq.mm |
29 | Earthing Continuity Conductors -Bare G.I. Conductor size 8 SWG |
30 | Earthing station with 600 mm x 600 mm x 6 mm galvanised iron plate & 50 mm dia. G.I. pipe, 3000mm long GI pipe (Class B or better) earth pit as per IS 3043. The earth pit shall be provided with watering pipe (Class B) with wire messed funnel, 25x3 GI strip/ / 2X8SWG G.I. wire up to chamber (wire or strip size as per fault level), disconnecting links with 600 x 600 mm (clear) RCC chamber & heavy duty 3mm thick CI chequered plate cover with hinge & stainless steel bolts. Bentonite/ Charcol & Salt shall be provided for earth pits. Excavation, back filling, removal of excess soil is included in the scop |
31 | S.S. mosquito net |
32 | Providing, detailing, composite fabricating members like Trusses, N-girders, girders, bracings, supports, purlins, runners, and similar structural steel members fabricated using M.S. hollow tubular steel sections (circular & rectangular pipes), of TATA Structura Make or equivalent conforming to IS 1239 part 1 and 2 and of grade Fe 250 as per specifications and approved fabrication drawings (which are to be prepared y Contractor and got approved from Engineer), including transportion of the same to site, erection of structural steel members for all heights & at all levels, provision of necessary erection bolts, fixing bolts, nuts, washers, cleats, stiffeners, gussets, base plate, and all necessary operations like preheating as per specifications, straightening, bending, cutting, drilling, grinding, machining if specified, welding,grinding, removing the welding burr and preparing surface for painting with wire brush cleaning and applying two coats of epoxy red oxide zinc phosphate primer of 30 microns each and two coats of Epoxy Corrosion Resistant Enamel paint of 30 microns after fabrication including touching up with spray painting after erection etc complete as directed by Engineer In Charge. |
33 | Bare Galvalume /zincalume sheet for roofing |
34 | Excavation for foundation, substructures, basements, tanks, sumps, walls, chambers, manholes, trenches, poles, pits & general building works in soft/ disintegrated rock, sand stone, stiff clay, gravel, cobblestone, hard laterite, water bound macadam, wet mix macadam, asphalt mix carpet of any type, pitching, soling, paths and hardcore, lime concrete, plain cement concrete, stone masonry and all types of brick/ block masonry below ground level, rock boulders, etc. for depths/ lifts upto 1.5M measured from the ground level, including dressing/ trimming the sides, leveling of bottoms, manual dewatering, removing rank vegetation, backfilling in layers not more than 200mm thickness, watering, consolidating, compacting to achieve not less then 97% Modified Proctor density conforming to relevant IS, stacking in measurable heaps for future use within owners space or disposing within an initial lead of 150m as directed, loading, unloading, leveling excluding shoring, strutting etc. complete as directed by Engineer-inCharge. Note: 1) The rate includes the handling/supporting the existing utilities such as cables, drains, pipes, water mains etc. 2) It also includes the royalty and other taxes if any |
35 | Filling in plinth, floors, trenches, pits with approved excavated materials, murum / good earth in layers not exceeding 200mm including breaking of clods, watering, consolidating each layer in filled up area by rolling and compacting with roller/ plate compactor as required to achieve not less than 97% modified proctor density conforming to relevant IS etc. complete as directed by Engineer In charge. Note: 1) The rate includes the royalty and other taxes if any |
36 | HYSD steel bars (Fe 415) |
37 | Nominal Mix of 1:3:6 (1 Cement OPC: 3 coarse sand : 6 graded stone aggregate 20 mm nominal size). |
38 | Cement mortar 1:4 (1 cement : 4 coarse sand) |
39 | By using acrylic based exterior paint |
40 | CSMC for 3 years after 1 year DLP. |