Tender For Repair/Replacement And Servicing Parts Of Ac Plants ,Vrv And North Side Of Runway And Allied Works At Af Station Jodhpur, jodhpur-Rajasthan

Military Engineer Services-MES has published Tender For Repair/Replacement And Servicing Parts Of Ac Plants ,Vrv And North Side Of Runway And Allied Works At Af Station Jodhpur. Submission Date for this Tender is 19-02-2024. HVAC Tenders in jodhpur Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

41800900
Corrigendum : Tender For Repair/Replacement And Servicing Parts Of Ac Plants ,Vrv And North Side Of Runway And Allied Works At Af Station Jodhpur
Open Tender
Indian
Rajasthan
jodhpur
19-02-2024

Tender Details

Repair / Replacement And Servicing Parts Of Ac Plants , Vrv And North Side Of Runway And Allied Works At Af Station Jodhpur

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 12-Feb-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 19-02-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 29000.0 /-
Tender Value
INR 14.50 Lakhs /-

BOQ Items

Name of Work:Commander Works Engineers, Air Force, Jodhpur
Sl. No. Item Description
1Material & Labour for finding out the leakage with the pressure test of water chiller scroll type capacityup to11 TR plant ,identifing gas and oil leakage and removing the same andLeak repairing by brazing/flaring andflushing the sysytem by nitrogen gasandpressure testing for leakage and rectifiedand after rectification vacumacation, pressuretesting,andgas charging R-407c for achieve desire pressure and testing complete to the entire satisfaction of Engineer-in-Charge NOTE :- Gas charging requiredshall be measured and paidseparatelyas supply only. note -all three units will be checked for leakage and rectified in each job.
2Ditto all as per Ser item No 1.00 above but capacityup to11 TR to 25 TR,
3Ditto all as per Ser item No 1.00 above but capacityup to 25 TR to 50 TR,
4M&L for charging of refrigerant R-407c Gas. (Make:- Mafron/ Feron/floron/du point) complete all as specified and directed
5M&L for replacement ofthermostatic expansion valve suitable for water cooled scroll chiller unit cap 25/37/50 TR all as per sample, including brazing at both ends all as required and directed.
6M&L for replacement of Drier filter suitable for Package type AC Plant size 5/8" Make: Catch All Model : C-165
7M & L for Descaling the chiller and compressser unit by descaling compound / hydrochloric acid by soaking method,disconnecting chiller unit from the system by taking out nuts, bolts, studs, valves and MS/GI pipe line from both side cover, cleaning each tube with nylon brush,flushing with alkaline solution,connecting back both side cover including replacingleather gasket 4 mm thick for following capacities of condensers suitable for AC Plant installed as indicated below complete all as specified and directed and all as per manufacturers instruction and to the entire satisfaction of Engineer-in-charge. (a) chiller unit cap 60 TR
8b)Ditto all as per Ser item No 7.00 above but chiller unit cap 50 TR
9c)Ditto all as per Ser item No 7.00 above but chiller unit cap 37 TR
10d)Ditto all as per Ser item No 7.00 above but chiller unit cap 30 TR
11e)Ditto all as per Ser item No 7.00 above but chiller unit cap 12.5 TR/11.5 TR/10TR
12M&L for disconnecting electrical connections motor located at the top of cooling tower,keep cables at safe custody for reconnection and dismantling and taking out fan blade assembly along with motor mounted on base frame at the top of cooling tower after cutting/dismentalingall nuts, bolts and fixtures from the mounting frame and removing wholeassembly including motor and base frame from the top of cooling tower with the help of T&P for servicing of cooling tower suitable for 100-120 TR capcity including following complete:- (i) Cleaning /scrapping of inner& outer surface of FRP basin, repair of damaged portion if any incuding FRP lining of all surfaces joints to avoid leakage including replacement of all nuts and bolts joining all parts of Basin complete. (ii) servicing coolingtower plant through cleaning re-agent complete pipe line, including servicing of cooling tower motor and fan and make the necessary alignment with motor. (iii) replacement of bearing if any of suitable cap if any after necessory work including gressing and replacement of nut bolts and preventing leakage if any by means of suitable adetives etc all as directed and specified. (iv)taking out PVC fills blocks, cleaning and refixing as per existing location and channel direction if pvc fills vintage then replace with new one measure seprately . (v)servicing of spray header and sprinkler assy complete. (vi) repair of water strainer complete.
13Ditto all as per Ser item No 12.00 above but cooling tower suitable for 25- 60 TR capcity
14Supply and fixing Pressure switch0-30 BAR AKS 3000(060G1081) suction/discharge/oil pressure as directed
15Supply and filling of compressor oil (mineral) suitable for voltas water cooled recirocating chillers model 5H 60/5 H 66
16Supply and chargingfor refrigerant R-22 Gas (Make:- Mafron/ Feron/floron ) complete all as specified and directed.
17M&L for replacement of micro processor controller panel, suitaable for voltas water cooled recirocating chillers model 5H 60/5 H 66 Digital display of all vital parameter for water cooled reciprocating pkg chiller plant 60 TR as per sample Model No-VLRP SINGLE V2A,Type -DELUX Range-6/5/4 ,Aux supply-8v &12 V, Make-SOFTHARD or equivalent complete all as specified and directed.
18M & L for replacement of microcomputer voltage protection device(MVPD) with display complete model-EC, Type-MVPD, Range 30-220 Amps,Aux supply-230V,Special -5 sec Curve MPD make -SOFTHARD.
19M&L for taking out unserviceable sealed unit (compressor) as existing and replacing the same with new packaged type sealed unit (compressor)12.5 ton capacity ,model-SZ185S4RC , three phase, 415 volt of modelsDanfoss make including necessary modification of the foundation as required to suit the compressor, flushing the sysytem by nitrogen gasandpressure testing for leakage and rectified (bybrazing) and after rectification vacumacation, pressuretesting,andgas charging R-407c for achieve desire pressure and testing complete to the entire satisfaction of Engineer-in-ChargeNOTE :- Gas charging requiredshall be measured and paidseparatelyas supply only.
20M&L for replacement of chilled water sensorcomplete all as specified and directed
21M&L for replacement of micro processor controller panel, Digital display of all vital parameter for water cooled scroll type chiller plant as per sample Model No-SCR44TR(MPD) ,Type -DELUX Range-5-30 Amp , Make-SOFTHARD or equivalent complete all as specified and directed
22M & L for replacement of microcomputer voltage protection device(MVPD) with display complete model-EC, Type-MVPD, Range 5-30 Amps,Aux supply-230V,Special -5 sec Curve MPD for 37.5 TR/50TR/25TR CHILLER make -SOFTHARD or equivalent complete all as specified and directed
23M&L for repairs ofcondenser/chiller pumps from 2HPUpto 7.5 HP including dismantling ofPumpof following capacity and segregating to its parts for repairs and maintenance, replacement onlyofshaft bearing, impeller key, shaft sleeve, impeller and grinding / polishing, bend removing etc complete including painting by two coats of synthetic enamel paint reassembling of pump after completion of work & testing complete all as per direction and satisfaction of Engineer in charge. Note:-Supply only of bearing and sleeve, impellerwill be measured and paid under relevent item of work.
24Supply and fix in replacementof spare parts of pumps sets (To be incorporated under respective item above ) :- (a) Shaft bearing as per existing specifications.
25(b) Shaft sleeveas per existing specifications.
26(c) Impellerwith keyas per existing specifications.
27(d) Mechanical Couplings as per existing specifications.
28(e) rubber type coupling as per existing specifications.
29M & L for repairing /Disconnecting the electrical and mechanical connection of burnt electrical motors from the site / location, transporting to and from to work shop.Rewinding of electrical motors/ pump motorsby dismantling and removing the burnt cut copper winding wire cleaning the slots of stator with petrol and brushes winding polyster based super enamelledcopper wire of same gauge of original one with proper class of insulation including varnishing and heating the coil and remove air bubbles complete stator / roter after rewinding reassembling all parts including reinstalling connection to original position and testing on full load all as directed by Engineer in charge for different capacity of motor as per following :- (a) 1 to 2 HP
30(b) Ditto as per item No. 29.00 above but for 3 to 5 HP
31(c) Ditto as per item No. 29.00 above but for 7.5to 10 HP
32M&L for replacement of Thermostat Honey well 0-30 degree C
33M & L for Descaling the Condenser by descaling compound / hydrochloric acid by soaking method,disconnecting Condenser from the system by taking out nuts, bolts, studs, valves and MS/GI pipe line from both side cover, cleaning each tube with nylon brush,flushing with alkaline solution,connecting back both side cover including replacingleather gasket 4 mm thick for following capacities of condensers suitable for AC Plant installed as indicated below complete all as specified and directed and all as per manufacturers instruction and to the entire satisfaction of Engineer-in-charge. (a) chiller unit cap 60 TR
34b)Ditto all as per Ser item No 33.00 above but chiller unit cap 50 TR
35c)Ditto all as per Ser item No 33.00 above but chiller unit cap 37 TR
36d)Ditto all as per Ser item No 33.00 above but chiller unit cap 30 TR
37e)Ditto all as per Ser item No 33.00 above but chiller unit cap 12.5 TR/11.5 TR/10TR
38supply and fix in replacement of Cooling Tower Sprinkler Assembly such as Sprinkler, Sprinkler Pipe, Elimentor, Tension bar and Turn buckle for Cooling Tower capacity 160/120/100 TR as existing on site make :-MIHIR or equivalent suitable as per existing and ali as perdirected by engg in charge.
39S&F in replacement of of PN 1.6 butterfly valves size 125 mmduly insulated with companion flanges,nuts,bolts,gaskets etc.as specified . butterfly valves with cast iron body, seat of black nitrile rubber ,nylon coated S.G.iron disc,epoxy powder coated shaft AISI 410 etc.complete all as specified and directed. Make Audco/castel/kirloskar
40Ditto all as per Ser item No 39.00 above but size 100mm.
41Ditto all as per Ser item No 39.00 above but size 80mm.
42Ditto all as per Ser item No 39.00 above but size 65mm.
43S&F in replacement of air filter for AHU, Filter section consists of50 mm thick washable HDPE 90% down 10 micron Pre-Filters, AHU prefilter having HDPE media with aluminium / GI frame & filter as per the existing size of600mmX600mmX50/40 mm mm complete all as specified and directed.(Make :- Supreme/Athlete or equivalent
44M&L for replacement of" V Belt ofA & B Series any sizesfor AHU "s as per site requiement complete all as specified and directed
45Supply and fix in replacement of water presuure gauge 0-7 kg / cm2 including Female Stainless Steel Gauge Fittings INCLUDING ball valve 5/8", type MakeFebig or equivant suitable makes as per appx "B" complete all as specified and directed
46S&F in replacement ofthermometerto condenser/chiller, inlet or outlet water pipes including addition alteration to pipe line for fixing thermometer Range 0-100 degreeF / degree centigrade complete all as specified and directed
47Supply and fix in replacement of PVC insulated 4 Core copper Cable of size 6 Sqmm complete all as specified and directed
48Supply and Fixing in replacement of MCCB 400 Amp 4Pole 36 KA thermal megnatic complete all as specified and directed
49Supply and Fixing in replacement of MCCB 250 Amp 4 Pole 36 KA thermal megnatic typecomplete all as specified and directed
50Supply and Fixing in replacement of MCCB 160 Amp 4 Pole 25 KA thermal megnatic typecomplete all as specified and directed
51Supply and Fixing in replacement of MCCB 100 Amp 4 Pole 16 KA thermal megnatictypecomplete all as specified and directed
52Supply and Fixing in replacement of MCB TP C63 Amp415 Volt complete all as specified and directed
53Supply and Fixing in replacement of MCB TP C40/32 Amp 415 Volt complete all as specified and directed
54M&L for taking out unserviceable sealed unit (compressor) scroll type for CASSETEAC 5.5 ton capacity , SINGLEphase, 415 volt of models as existing and replacing the same with new packaged type sealed unit (compressor) of Hitachi/Danfoss/daikin/copeland make including necessary modification of the foundation as required to suit the compressor, vacumacation, pressure , testing, leaking, rectification includinggas charging R-22/407/410 for achieve desire pressure and testing complete to the entire satisfaction of Engineer-in-Charge
55M&L for taking out unserviceable sealed unit (compressor) scroll type for CASSETEAC 2.8 ton capacity , three phase, 415 volt of models as existing and replacing the same with new packaged type sealed unit (compressor) of Hitachi/Danfoss/daikin/copeland make including necessary modification of the foundation as required to suit the compressor, vacumacation, pressure , testing, leaking, rectification includinggas charging R-22/407/410 for achieve desire pressure and testing complete to the entire satisfaction of Engineer-in-Charge
56M&L for replacement of Al Fan blade for out door Fan motor assembly suitable for ductable AC 5.5/8.5 ton capacityMake - Hitachi/Danfoss/Tecumesh
57M&L for replacement ofPCB control card set complete suitable for Tower AC of any capacity 4.0 TRrequirement complete and testing the AC after the replacement of PCB as specified
58M&L for replacement ofPCB control card set complete suitable for CASSETE AC of any capacity 4.0 TRrequirement complete and testing the AC after the replacement of PCB as specified
59M&L for replacement ofPCB control card set complete suitable for VRV CASSETE AC INDOR UNIT CAPACITY UPTO 4.0 TRrequirement complete and testing the AC after the replacement of PCB as specified
60Supply and fix thermometer humidity meter clock with sensor cable Temperature and Humidity Functions: With temperature range from -10 degC to +50 degC and humidity 10 % sim 99 % RH, temperature and humidity readings show directly all as per directed
61S &F in replacement of humidistat H6000to control humidity range 15 to 80 % RH all as per specified and directed .
62Supply and fixof cooling tower PVC honey comb fillsin colums of size 600mm x 300mm x 150mm size and min wt 600 gram of capacity 15 TR to 150 TR for the following Make : Kool Drop / MIHIR / ADVANCE / HIMGIRI per existing specification and requirement.
63Supply and fix of multifunction meter voltage, ampere, power,power factor measureable accuracy class 1 for 3 phase panel including setting the parameter with CT as directed
64M&L in replacement for duct insulation highly flexible closed cell thermal insulation of 19mm thickness of elastomeric foam based on synthetic rubber laminated with 12 micron aluminium foil fencing with reinforced glass scrim and addehessive rubber coating class BS 476 as directed by engineer in charge
65M& L for repair for humidifier including cleaning of tank ,replacement of heater of 2KW ,painting of tank with corrosion less paint ,rewiring of electrical panel as directed by engineer in charge
66Supply and fix in repair Y staineer filter as per existing size and make as directed
67M&Lfor replacement of electrical strip heater ,finned type ,capacity 2 kwconsisting of stainess steel sheathing having heatresistent chrome -nickel 80/20 element protectedunder best insulation to avoid the leakage of current and with screwed type terminal at one end, 240 volts, AC, 50Hz ,single phase completeall as specified and as directed.
68Providing and fixing in repair FRP lining of 6 mm thickness on cooling water piping near cooling towers to minimize corrosion of MS piping of 65mm diameter as directed
69Providing and fixing in repair FRP lining of 6 mm thickness on cooling water piping near cooling towers to minimize corrosion of MS piping of 80mm diameter as directed
70Providing and fixing in repair FRP lining of 6 mm thickness on cooling water piping near cooling towers to minimize corrosion of MS piping of 100mm diameter as directed
71Providing and fixingin repair FRP lining of 6 mm thickness on cooling water piping near cooling towers to minimize corrosion of MS piping of 125mm diameter as directed
72M&L for WATER JET servicing ofVRV (complete indoor and outdoor unitby using service bag cover & cooling coil rinse solution for cleaning of coils),cassette type AC of 2.5/3.0/4.0/5.0 HPcapacitytaking out the indoor top coveroutdoor top cover from existing location, cleaning of cooling coil , condenser coil,and other components usingclean water greasing of fan, motor, blower etc without damage any part and reinstall at the same location all as directed by the Engineer-in-charge.
73M &L for WATER JET servicing of package type AC "s cap 7.5/5.5/11TR complete indoor and out door unit from existing location for servicing inner and outer filter complete with T&P and other accessories as directed.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail