Tender For Repair Maintenance Of Area Lighting Infrastructure Various Types Of Earthlings Lightening Protection System Fire Alarm System And Other Misc E M Works At Afs Jalahalli, jalahalli-Karnataka

Military Engineer Services-MES has published Tender For Repair Maintenance Of Area Lighting Infrastructure Various Types Of Earthlings Lightening Protection System Fire Alarm System And Other Misc E M Works At Afs Jalahalli. Submission Date for this Tender is 17-02-2024. Alarm Systems Tenders in jalahalli Karnataka. Bidders can get complete Tender details and download the document.




Tender Notice

41762501
Corrigendum : Tender For Repair Maintenance Of Area Lighting Infrastructure Various Types Of Earthlings Lightening Protection System Fire Alarm System And Other Misc E M Works At Afs Jalahalli
Open Tender
Indian
Karnataka
jalahalli
17-02-2024

Tender Details

Tender For Repair Maintenance Of Area Lighting Infrastructure Various Types Of Earthlings Lightening Protection System Fire Alarm System And Other Misc E M Works At Afs Jalahalli

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 02-Feb-2024 corrigendum BOQ 10-02-2024
2 10-Feb-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 17-02-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 100000.0 /-
Tender Value
Refer document

BOQ Items

NAME OF WORK: REPAIR/MAINT OF AREA LIGHTING INFRASTRUCTURE, VARIOUS TYPES OF EARTHINGS, LIGHTENING PROTECTION SYSTEM, FIRE ALARM SYSTEM AND OTHER MISC E/M WORKS AT AFS JALAHALLI
Sl. No. Item Description
1Attending unserviceable/ non functional street light complaints (for street light/perimeter lights/high mast light/flood light etc of any type/size fitted on poles/walls/post/pillers etc)by deploying technically qualified and experienced technicians to find out defective/taking out unserviceable parts such as electronic driver, pvc insulated copper conductor cable for connecting street light fittings etc and repairing by changing the defective parts including minor repair to cable connection/loose connection, screws,nuts & bolts and insulation tap to insulate the LT joint etc and testing complete all as specified and as directed in complete domestic area andtechnical area at AF Station East Jalahalli
2Note : The following items are deemed to be inclusive of quoted rate :-
3(a)The above job shall be carried out by a trained electrician having ITI in electrical, documentary proof of the education of tradesman shall be produced before commencement of work.
4(b)Contractor or his Authorised Representative has to inspect all Street/ Security Lights on Daily basis at their own arrangement between 7.00 PM to 9.00 PM and maintain the record in Register which will be put up to Engineer-in-Charge/ JE on the very regular basis.
5(c) A Joint Inspection for Serviceability of all Street/Security Lights will be carried out from 7.00 PM to 9.00 PM on every MONDAY by Engineer-in-Charge/ JE (E/M)/ User along with Contractor or his authorised Representative.
6(d) Contractor has to arrange own moveable Generatorof suitable capacity for repairing and testing of the Street/ Security Lights, defect rectification of Cables, etc. and to check the serviceability after repair.No Electricity shall be provided by the Department on this account.
7(e) Quoted Unit Rate shall deemed to be inclusive of attending any breakdown of Street/ Security Lights during night. Contractor has to arrange Electrician and Helper and all necessary T&P and Equipment"s to remove the breakdown. Fault will be intimated through Telephone/ SMS.
8(j)Contractor shall provide conveyance to the deployed labour for maintaining the services without any extra cost to department.
9(k)Vehicle mounted ladder for maintaining services shall be provided by the contractor at no extra cost to department.
10(l) Materials requiredfor the repairing of the lights shall be measured and paid separately under respective item(s) as supply and fixing . But labour required for taking down, dismantling, repairing and replacing parts and reinstalling and testing the street lights fittings shall deemed to beincluded in the rate quoted.
11(m)Necessary T&P, Safety Belt, Vehicle, Aluminium Ladder, etc. will be arranged by the Contractor and Cost for the same shall deem to be included in the Quoted Unit Rate.
12(n)All safety measures and provn of all safety devices, first aid box etc shall be provided by the contractor.Contractor will be solely responsible forfull safetyof the persons deployed for providing the services and department will have no liability for any type of accident/injury of any type. Unit rate quoted will be deemed to include the cost of the same and no extra payment shall be made on this part.
13(o)All type of T & P, PVC insulation tapes, minor nuts/ bolts/ washers etc required for maintaining the services shall be provided by the contractor without any extra cost to department.
14(p)Attending and repairing complaint for onelightof any type shall be measured and paid as one Job.
15(p)Earth work (if necessary at Site) for removing of any Cable Fault will be Measured and Paid under respective Items.
16(i) Contractor has to ensure serviceability of all Street/ Security Lights in above mentionedDOMESTIC & TECHNICAL AREA on Daily basis in any Weather Condition at their own arrangement.
17(f)In case of any delay in attending the complaint more than 12 hrs after handing over routine/urgent work, the contractor shall be liable to pay the penalty as described in penalty clause given here as under.
18(g) The penalty shall be applicable to the contractor if the delay is noticed by the Engr-in-Charge more than twelve hrs after handing over works of urgent nature to the contractor. The Engr-in-Chargeshall handover the slip containing specification of work to the contractor by lodging the time and signature of contractor be obtained on slip.The contractor shall attend the complaint immediately and shall report to Engr-in-Charge with in 12 hrs. The contractor will keep his tradesmen in stand by for attending any routine / urgent works from the executive.If the nature of job is such that the work cannot be completed within period of 12hrs then the facts shall be brought to the notice of the GE/Engr-in-Chargeand the period for the working to the complaint shall be decided by the GE/EIC. If the delay is more then twelve hrs period and the GE is not satisfied with the reason for delay then penalty at the rate of Rs 50/- per job shall be deducted from the dues of the contractor. Please note that this penalty is exclusively other then the condition 56 of IAFW - 2249 and shall be treated as interim condition of the contract and shall be enforce above as and when delay in individual job is noticed and no claim whatsoever on this account shall be entertained by the Deptt.
19(h) The decision of the Accepting Officer is this regards shall be final and binding.
20Supply and fixing the electronic controller with accessories (LED outdoor Driver) of 75V to 145V suitable up to 100 wattLED fittings complete all as specified Make - CG/Phillips/Bajaj or equivalent as per site requirement
21Supply and fixing the electronic controller with accessories (LED outdoor Driver) of 75V to 110Vsuitable up to 75 wattLED fittings complete all as specified. Make - CG/Phillips/Bajaj or equivalent as per site requirement
22Supply and fixing the electronic controller with accessories (LED outdoor Driver) of 40V to 75Vsuitable upto 45 wattLED fittings complete all as specified. Make - CG/Phillips/Bajaj or equivalent as per site requirement
23Supply and fixing the electronic controller with accessories (LED outdoor Driver) of 24V to 40Vsuitable upto 30 wattLED fittings complete all as specified. Make - CG/Phillips/Bajajor equivalent as per site requirement
24Supply only porcelain lamp holders pin / screw type suitable for HPSV/MH type fitting 70/ 150/250 Watts.
25Supply only capacitor suitable for HPSV/MH 70/150/250 Watts.
26Supply only igniter suitable for 70 watts to 400 watts HPSV/MH lamp fittings, complete, all as specified and directed.
27Supply only PVC insulated Copper Conductor Cable 1.5 Sqmm, 3 Core Round Flexible for connection of Street Light Fitting, complete all as specified and as directed. Make : Havells/ Plaza/ Finolex
28Supply and fixingthe surge protection device 5KV voltage compatible with industrial and out door type LED fixtures up to rated power of50W complete all as specified. Make - CG/Phillips/Bajaj or equivalent as per site requirement
29Supply and fixingthe surge protection device 5KV voltage compatible with industrial and out door type LED fixtures rated power of above 50W & up to 100W complete all as specified. Make - CG/Phillips/Bajaj or equivalent as per site requirement
30Supply and fix Contactor two pole 25-32 Amps suitable for street light timer switch including taking down the oldfitting unserviceable.Make: Philips/ Bajaj/ CG
31Material and labour for Removing ,errecting steel swagedtubular pole 8.5/9 mtr long,bracket for fixingstreet lightand refixing the sameincluding necessary PCC 1:4:8, type D2 (using 40 mm graded stone aggregate) for foundation of 50 x 50 x 45 cm and coping with 1:2:4, type B1 (using 20 mm graded stone aggregate) complete all as specifiedand directed by Engr-in-chrage.
32Material and Labour for fabricate, supply and fix MS sheet metal enclosure of size 45x30x20cm depth made out of 2 mm thick double door, including provision of opening for cable entry duly painted with two coats of synthetic enamel paint over one coat of red oxide andsuitable fixing MS clamps 40x5mm thick bend to shape drilled with holes suitable for fixing to PCC / Steel tubular pole all as directed and specified :-(a) Aluminium bus bar chambers 4 strip 300 mm long 100 Amps(b) MCB SPN40A 10KA "C" 03 Nos (c) Digital Time switch 3P Module, weekly program with battery bach up 100 hrs Current of capacity 16 Amps with change over - 01 Nos. Make -Indo asian cat part No-.TL032AB0. or equivalent in Schneider/ ABB.
33Supply and fix in repair bracket for street light fitting made out of40 mm dia light grade GI tubing bent to required shape 1.5m long including necessary GI clamps, nuts bolts and washers and fixing to the pole complete including taking down old or Old U/Sbracket from the pole as directed.
34Supply and fixing LED floodlight 150 watt made up of die cast aluminium housing with toughened glass and high power LEDs and secondary lenses with IP 66 protection and system efficiency = 125 LPW with option for 3000K 10 KV SPD includesand corrosion resistant complete with driver and lamp. Protection complete including street light fitting bracket nuts, bolts, washers complete. complete, all as specified and directed. Make - Bajaj/CG/Phillips
35Supply and fix in replacement whether proof PVC junction box approved by CPRI street light control box made out of not less than 2mm thick of size 140mm x 140 mm x 5mm (approx) complete with hinged door locking arrangement and consisting of 2 Nos of suitable size cable glands consisting of 01 No panel mounted connector 4 pole 32A-1 No, MCB SP 6A 10KA-01No, including connecting up with the electrical connections and fixing and clamping complete and all as directed.
36Supply, installation, testing and commissioning of smart street light control system using GSM/Lux based technology having12 KW 3 phase 32 amp load capacity per phase and can be operated by IVRS/SMS/lux based infrared sensor. Nature switch operation should be based on natural light lux level. Require illuminnance level for switching on is = 60 luxand for switching off = 10 lux. The smart unit should have 4 timers that can be set via SMS. Surge protection device (SPD) should provide protection agaist indirect lightning & switching surges. It should conform to IEC61643-11 and should have 40 KA capacity. The sensor & SPD along with suitable power contactors and incoming-outgoing MCCB/MCBs should be enclosed in a enclosure made of rust proof, electric shock proof , metal whether proof conforming to IP65 with angle iron frame of suitable size 04 Nos legs 600 mm long , PCC 1:2:4 typeB1 for grouting of base including taking down unserviceable panel. The scope of work also comprising the following :- The GPRS shall have seven segment display to show voltage, current, network and street light status , it should also have indicator for showing supply status , timer , overload or high low voltage. It should also able to measure voltage, current and automatic set street light overload current. Unit have facility to call back to registered number for power on/off and if any fault occurs at site.in SMS it should also monitor power/on/off time light on off time, ampere, voltage, unit mode, network percentage date and mobile number who called device number. The device should also have battery backup with minimum 24 hours backup capacity.The panel should have three operation mode :-1. GSM mode -in this mode light should be switched as per GSM controller"s preset time by user by sms , 4 clock base timer facility should be availble 2. Nature switch based-in this mode light will be switches as per nature light lux level 3. Bypass mode -in this mode light will switched on directly for testing purpose and emeregncy switching .In GSM controller there should be facility to register 4 user by sms/call and alerts will be sent on all registered number and also call back on power on/off and faults on first registered number.The Gsm controller should also compatible for cloud based data transmission for interfacing with web for future use,Password protection for Accessing the control of device via SMS/IVRS complete all as specified and directed including the following subcomponents & features :-
37(a) MCCB 100 Amps capacity, 10 KA, 415 Volts -01 No (Incoming) with separate SPD of 40 KA capacity. (Make of MCCB- L & T, BCH, Havells) (b)Supply Resign cast CT"S - set of 3 (c)Gsm based smart street light controller. (d) Lux based sensor to operate external as per light intensity. (e)Line Contactor, AC 3duty, 3 phase, 415 volts. 50 Hz , 25 Amps -03 Nos (make - L & T, BCH, Havells) (f)MCB SP 32 Amps- 03 Nos(make -L & T, BCH, Havells) (g)Terminal block suitable for 100 A rating with brass contacts for INPUT/ and 63 A for OUTPUT termination. (h) GSM/Timer/Bypass Mode switch. (j) Panel wiring for control circuit with copper flexible 1.5 sqmm & power wiring 10 sqmm flexible. Make- Tricolite/ Kewintech/HPL
38Excavation in trenches insoft/loose soil not exceeding 1.5 mtr in width and not exceeding 1.5 mtr in depth for laying of cables up to proper level complete all as specified and directed by Engr-in-charge.
39Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cmcomplete all as specified and directed by Engr-in-charge.
40Removing surplus excavated material from excavation not exc 50 meter and depositing where directed at a level not exc 1.5 meter above the starting point complete all as specified and directed by Engr-in-charge.
41Material and labour for Spreading ribbed soil in trenches as in cable cushioning all as per IS 1255-1983and as directed. Note :- Excavated approved soil obtained from excavation under item No 1 shall be ribbed by using sieve to separate composite particles etc as per IS and refilling in trenches before laying of cable 8 CM and 15 CM after laying of cable. This is than gently punned down to a depth of 10 cm above the top of upper most cable(ii) For the purpose of measurement only punned thicknesswill be considered for payment.
42Material and labour for well burnt class ‘B’ bricks as mechanicalprotection to under ground cables laying with length of the bricks equal to the width of the trench complete all as specified and directed by Engr-in-charge.
43Material and labour for Cutting existing road/PCC/Drain for laying of GI or any type of pipe including necessary earthwork, excavation exc 600mm depth but not exc 1mtr depth, wide 800mm including making good existing surface with 150 mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate complete all as specified and directed.
44Note for item No 43:-The tenderer shall take into consideration for following points while quoting rate for this item andthe unit rate is deemed to be inclusive for :-
45(i) Earth work excavation in any type of soil
46(ii) Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick complete all as specified and as directed.
47(iii) Removing excavated material to out side MD land
48(iv)Laying of any type/any bore of pipe in trenches including taking down any description. Supply of pipe will be measured and paid separately
49(v)150 mm thickPCC 1:2:4 type B1 using 20mm graded stone aggregate as inroad to make good existing disturbed surfaces.
50Supply and laying of GI pipe light grade for cable protection of size 40mm bore complete with fitting complete including taking down unserviceable one all as specified and directed by Engr-In-Charge.
51Material and labour for3 ½ core 120 Sqmm XLPEinsulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheather laying in trenches/cable ducts, fixed to wall/pole complete including taking down unserviceable one all as specified and directed by Engr- in -Charge.
52Material and labour for3 ½ core 95 Sqmm XLPEinsulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheather laying in trenches/cable ducts, fixed to wall/pole complete including taking down unserviceable one all as specified and directed by Engr- in -Charge
53Material and labour for3 ½ core 70 Sqmm XLPEinsulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheather laying in trenches/cable ducts, fixed to wall/pole complete including taking down unserviceable one all as specified and directed by Engr- in -Charge
54Supply and laying of GI pipe light grade for cable protection of size 80mm bore complete with fitting complete including taking down unserviceable one all as specified and directed by Engr-In-Charge.
55Supply & Erecting Mild steel tubular swaged pole 8.5 meter long 410, SP-31 complete with cast iron base plate, bracket, final taper plug, bolt, nuts & screws and painted on both side (internally & externally), external surface painted with two coat of aluminum paint over coat of primer and painting with blackup to 1.5 meter from top of PCC 1:2:4 with 20 mm aggregate coping white colour paint as in strips of equal width with marking pole numbers by using one coat of synthetic enamel paint including necessary PCC 1:4:8 with 40 mm aggregate foundation and coping as per TD drawing including dismantling & removeing from the site damaged pole one complete all as specified and as directed.Note (i)Excavation, earth work and PCC work for embedding pole shall be measured and paid seperately.(ii) Pole upto 1.5 m top of copping shall be painted with 2 coats of block and white strips alternate 30cm each over one coat of red oxide primer (iii) Steel tubular pole above 1.5 m shall be painted with 2 coats of alu paint over a coat of red oxide primerthe rate for above items shall be deemed to be inclusive in the quoted rate.
56Supply, installation, testing and commisioning Feeder Pillar Box out door type weather proof, dust & vermine proof CPRIapproved LT panel made out of 3.15 mm thickCRCA sheet front and back door openable type and suitable for operation on 415V, 50Hz, AC supply, conforming to IP-54 and fixed on angle iron frame/chanel of suitable size complete, aluminium bus bar chamber cable alley, cable glands brass crommium plated of diffrent sizes suitable for incoming and out going cable panel, painted with powder coated paint incuding necessary PCC (1:3:6) foundation extending 300mm above GL and 60cm wide platform in front of the panel complete all specified and directed by Engir-in-Charge withthe following accessories :-INCOMING(a) MCCB 400 Amps 4 pole 36 KA with adjustable type - 01 No (b) Aluminiumbusbar of capacity 600 Amps with eppoxy insulated supports 3 phase and neutral -1 set (c ) Volt meter digital type 96 sqmm with in built selector switch - 01 set (d) Amps meter digital type 96 sqmm with CT"s 200/5 -03 Nos and in built selector switch - 01 Set(e) Indicating lamp set LED type - 01 setOUTGOING(a)MCCB 63 Amps, 4 Pole 10 KA adjustable type - 1 Nos(b) MCCB 100 Amps, 4 Pole 16KA adjustable type - 01 Nos (c) MCCB 200 Amps, 4 Pole 25KA adjustable type - 02 Nos (d) MCCB 32 Amps, 4 Pole 10KA adjustable type - 01 Nos For Existing Timer Note (1)Rates deemed to be included for suitable lugs and glands for incoming and out going of LT UG cable.(2) The Contractor Shall submit the drawing with sample of accessories for approval before executing the work. (3) Insulators, wiring, bus bar sleeves, lugs, gland,sheet metal enclosure etc including complete wiring with suitable size of copper wire.
57Material and labour for New Earthing complete with galvanised steel earth plate electrode 60cm×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less"than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 5 connected to earthing test point all as specifiedincluding excavation earth work in any type of strata, removal of surplus excavated material, GI pipe for watering and funnel, PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 in cover slab with GI protection pipe testing on completion including taking down old earthing material complete all as specified and directed by Engineer-in-Charge.
58Boring of holes under road, pavement hard standings by trenches technology using ultra sound technique and necessary machine including HDPE pipes of 30 mm dia suitable for 0.4 Mpa working pressure complete all as specified and directed by Engr-in-charge.
59Material and labour for3 ½ core 35 Sqmm XLPEinsulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheather laying in trenches/cable ducts, fixed to wall/pole complete including taking down unserviceable one all as specified and directed by Engr- in -Charge.
60Material and labour for3 ½ core 50 Sqmm XLPEinsulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheather laying in trenches/cable ducts, fixed to wall/pole complete including taking down unserviceable one all as specified and directed by Engr- in -Charge.
61Material and labour for 4 core 25 Sqmm XLPEinsulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheather laying in trenches/cable ducts, fixed to wall/pole complete including taking down unserviceable one all as specified and directed by Engr- in -Charge.
62Material and labour for4 core 10 Sqmm XLPEinsulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheather laying in trenches/cable ducts, fixed to wall/pole complete including taking down unserviceable one all as specified and directed by Engr- in -Charge.
63Material and labour forEarthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6 mm thick buried directly in ground vertically to a depth not less than 2.25 mtr below ground level with top edge of plate not less than 1.5 m below ground level connected to and including galvanised earth strip of size 32x6 mm (up to 7.5 mtr length) and GI pipe 40 mm light grade for protection of GI earth strip by means of bolts, nuts, check nuts and washers made out of galvanised iron and connected to earth test point as shown in electrical plate No. 3 of SSR Part-1-2009 and as specified or indicated and testing on completion including excavation and earth work any in type of strata available at site, PCC (1:3:6) type C-1 for earth chamber, precast RCC slab 50mm thick in cement concrete (1:2:4) type B-1 reinforced with welded steel wire fabric (xpm) weight not less the (4kg/sqm) funnel with GI watering pipe of 20mm bore medium grade, wire nuts and lugs complete all as specified and directed by Engr-in-charge.
64Note for item No. 63: -(a)All Joints should be joined by Exothermic Welding or Brazing. (b)After completion of work earthing shall be tested by the contractor in presence of Engineer-in-Charge, User and proper record shall be maintained duly signed by all concerned. (c)Earth resistance tester shall be provided by the contractor. It should be caliberated from authorised company/ lab. (d)After testing if desired earth resistance of less than 5 Ohm is not obtained, the earthing will be redone at no extra cost to Govt till desired result is obtained.
65Material and labour for in repairs Galvanised Earth strip of size 32 x 6 mm fixed on proper post insulator at the instrument end complete all as per specified and as directed.
66Supply and fixing in repair test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm longhex. head screw all as specified and directed by Engineer - in - Charge.
67Supply and fix in replacement Aluminium steel strip 25 X 3 mm with saddles and fixing screws etc. for roof conductors and down conductors above ground brazing at each joints between strip including saddle/Ceramic insulator/PCC block where required. all as directed by Engineer-in-Charge.
68Supply and fixing in single pointed copper franklin rod/Air Termination rod of 12mm dia 1000 mm long fixed to copper strip including drilling holes, nuts, bolts washers, Insulating mounting pads for resting/ supporting of air terminals etc. complete all as directed.
69Supply and fixing 40 mm bore galvanised steel water medium grade with all fitting laid in trenches/road cutting including taking down old GI pipe complete all as specified .
70Supply and fixing 20 mm bore galvanised steel water tubing medjum grade with all fitting fixed to wall and ceiling or laid in floors including taking down old GI pipecomplete all as specified.
71Supply and Fix in repairs Bib Tap of 15 mm dia standard of PTMT any colour high pressure screwed for iron pipe(Minimum weight 90 gms ) all as specifed and directed. Make Prayag, Princes, Supreme
72Supply and fixing new generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP OPENING seperate driver compartment with IP66 protection and impact resistance of IK07 with 10KV Built-in Surge Protection Device of 70 watt.Make:Havells/Philips/Wipro
73Disconnecting of burnt/ damaged cables from panels/ junction boxes etc, cutting out the burnt out ends, making new end joints by supply and fixing new aluminium lugs/ insulation tapes etc and reconnecting using new nuts/ bolts/ washer etc and restoring three phase and neutral in the junction box complete all as directed for the 25 - 50 sqmm 3.5 core size of LT underground armoured cables. Note :- Earth work required for extending the incoming/ outgoing cable in junction box/ panel board etc shall be deemed to be included in the unit rate quoted.
74Supply and fix LEDfloodlight fitting 200Wintegral type light fixture, cast aluminum body, reflector, drivers, LEDsand accessories with system wattage 200W.including taking down oldfitting unserviceable.Make: Philips/ Bajaj/ CG
75Fabricate supply install test and commissioning of Bus bar box out door typetotally enclosed dust and vermin proof floor mounting with hinged doors and locking arrangement front and back fabricated out of 3.15 mm thick CRCA sheetincluding powder coated paint finish including all accessories, provision independent removevable MS plates for fixing cable glands for all sutable for 300sqmm X3.5 core UG cable incomming and out going cables and complete control wiring with 2.5 sqmm copper conductor incuding necessary PCC foundation complete all specified and directed by Engineer-in-Charge. Note:- (1)Rates deemed to be included for suitable lugs and glands for incoming and out going of LT UG cable. (2) The Contractor Shall submit the drawing with sample of accessories for approval before executing the work. INCOMING (a) MCCB 200 Amps 4 pole 36 KA with adjustable type - 01 No(b) Aluminiumbusbar of capacity 400 Amps with eppoxy insulated supports 3 phase and neutral -1 set
76Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc.removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc.complete all as specified.
77Material and labour for point wiring for one Light pointusing approved colour code as per IS (Red, Black and Green for single phase circuits)with multistrand copper conductor 1.5 sq mm nominal cross-sectional area, single core,PVC insulated and unsheathed FRLS cable 1100 Volts grade ISI-694 marked with valid CM/L No. drawn in Conduit pipe 20mm PVC rigid non metalic conduit, including mild steel Modular sunken box including inner/outer sheet/cover plate and fixed covered etc including PVC insulated multi-stranded copper conductor 1.5 sqmm nominal cross sectional area single core FRLS cable as earth continiuty conductor to common earth and connecting to earth dolly complete for one light/fan point controlled by one 5/6 amps one way switch. (Note: switch,socket , and fan regulator itemto be measured and paid seperatly)
78All as per item No here -in- before but for OneExhaust Fan pointwith Cable 1.5 Sqmm Size complete all as specified anddirected.
79All as per item Nohere -in- beforebut for one celing/wall mounted fan point with Cable 1.5 Sqmm Size complete all as specified anddirected.
80All as per item No here -in- before but for One Light point for building security light with Cable 1.5 Sqmm Size complete all as specified anddirected.
81All as per item No here -in- before but for One pointfor 3 pin modular socket outlet 5/6 Amps2-in-1, on independent board.
82All as per item No here -in- before but for Onepointfor 3 pin modular socket outlet 5/6 Amps 2-in-1, on the same board with other switch.
83All as per item no 77herein before but for above but one point for 5/6 pin modular socket outlet 15/16 Amps2-in-1, independent board with cable 4sq mm size.
84All as per item No 77herein before but for one pointfor 5/6 pin modular socket outlet 15/16 Amps2-in-1, Same board with cable 2.5 sq mm size and other switch.
85All as per item No 77here -in- before but for One bell point controlled by one bell push onindependent board.
86All as per item No-77 here in before but for One Light pointfor controlled by two 2-way switches , with cables 1.5 sq. mm size.
87All as per item No-77here-in-before but for One 3 pin modular socket combination 15/16Amps Independent board for AC point/power equipment with cable 4 Sq mm size complete all as specified.
88Supply and fixing Modular Switch 1 way 6 A, 1 Module all as specified and directed. Make: Legrand/Indo Asian/Crab tree
89Supply and fixing Modular Switch 1 way 16 A, 1 Module all as specified and directed. Make: Legrand/Indo Asian/Crab tree
90Supply and fixing Modular bell push 6 A, 1 Module all as specified and directed. Make: Legrand/Indo Asian/Crab tree
91Supply and fixing Modular socket 6 A, - 2/3 pin combined 2 module all as specified and directed. Make: Legrand/Indo Asian/Crab tree
92Supply and fixing Modular socket 6/16 A, - 2 / 3 pin comb 2 module all as specified and directed. Make: Legrand/Indo Asian/Crab tree
93Supply and fixing Modular fan regulator 120W, 2 Module for Ceiling fan complete all as specified and directed. Make: Legrand/Indo Asian/Crab tree
94Supply and fixing Bell Ding-Dong AC 230 V AC complete all as specified and directed. Make: Anchor/Havells/Cona
95Supply and fixing ceiling rose surface bakelite3 terminals 65x50mmcomplete all as specified and directed.
96Supply and fixing Lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings with Ledz inverter Lamp 9 watts with suitable back plate angle type complete all as specified and directed. Make :Bajaj / Anchor / cona
97Material and labour for sub main wiring withtwo single core stranded copper conductor unsheathed PVC insulated cable 1100V grade, 4 sq mm drawn throughand including 20MM size of non-metallic PVC rigid conduit with 4 sqmm copper conductor cable as earth conductor and conduit accessories fixed up in surface/ recessed as required, including connecting up completeall as specified and directed including taking down old U/S wiring.Note:-Two run of cable and one run of earth continuity copper conductor and non metalic PVC conduit shall be measured as one unit length. Make: Havells/Plaza/Finolex
98Supply and fixingin repair MCBTPN/FP 40 to 100 AMP 10 KA, Triple pole415 volts, 50 HZcomplete all as specified and as directed.Make: L&T/Indo Asian/Legrand
99Supply and fixingin repair MCB SP5 to 32 AMP 240V, 10 KA "B" curve miniature circuit breaker (MCB) of single poles and current carrying capacity 5 to 32 AMP, in the MCB DB Complete with connection, testing and commissioning complete all as specified and as directed.Make: L&T/Indo Asian/Legrand
100Supply & Fixingin repair Single pole and neutral enclosure with a two pin and earth plug & socket Modular type with one sigle pole MCB 20 Amps, fixed forAC/ other Equipmenton wall and making all connections all as directed.Make: L&T/Indo Asian/Legrand
101Supply and fixing in repair VTPNMCCB DB(distibution board) 125A Double Door8 Way, IP:54 protection,isolated neutral bar,Mechanical impect strength IK 09three phase, cement spill protector, 415volts including one new mccb 125A 4pole16kAand fixing at site,electric connection complete all as specified and as directed.Make: L&T/Indo Asian/Legrand
102Supply and fixing LED light fitting,4 feet ,1x20 watt 230 Volt,PC body. Compact appearance, simple and versatile in nature makes it as long lasting, efficient solution for offices and other commercial spaces. Efficacy : 100 lumen/watt with all accessories including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and directed including taking down old fitting . Make: Philips/Bajaj/CG
103Supply and fixingin repair MCB DB(distibution board)8 Way SPN(single pole and neutral) single phase made sheet steel cement spill protector , isolated neutral bar,IP:54 protection door earthing Mechanical impect strength IK 09,240 volts and connection complete all as specified. Make: L&T/Indo Asian/Legrand
104Supply and fixingin repair 32 ampMCB SPN rating 240V, 10KA "B" curve miniature circuit breaker (MCB) of following poles and current carrying capacity 32 amps,in the MCB DB complete with connection testing and commissioning complete all as specified and as directed.Make: L&T/Indo Asian/Legrand
105Supply and fixing LED Building security light fitting 60 wattswith cast aluminium housing, toughened glass diffuser, IP 65 and wired includingall accessories , suitablesize GI bracket made with light grade pipe& clamps-02 Nos with bolts & nuts. and fixed at siteand eletric connection complete all specified and as directed. Make: Philips/Bajaj/CG
106Material and labour for sub main wiring withtwo single core stranded copper conductor unsheathed PVC insulated cable 1100V grade, 6 sq mm drawn throughand including 20MM size of non-metallic PVC rigid conduit with 6 sqmm copper conductor cable as earth conductor and conduit accessories fixed up in surface/ recessed as required, including connecting up completeall as specified and directed including taking down old U/S wiring. Note:-Two run of cable and one run of earth continuity copper conductor and non metalic PVC conduit shall be measured as one unit length. Make: Havells/Plaza/Finolex
107Supply and fixing LED light fitting, 2 feet ,1x10 watt230 Volt,PC body. Compact appearance, simple and versatile in nature makes it as long lasting, efficient solution for offices and other commercial spaces. Efficacy : 100 lumen/watt with all accessories including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and directed including taking down old fitting .Make: Philips/Bajaj/CG
108Supply and fixingin repair TPNMCB DB(distibution board) Double Door 12 Way, TPN (triple pole neutra)IP:54 protection,isolated neutral bar,Mechanical impect strengththree phase, cement spill protector, 415volts and connection complete all as specified and as directed. Make: L&T/Indo Asian/Legrand
109Supply and fixing in repair VTPNMCCB DB(distibution board) 250A Double Door12Way, IP:54 protection,isolated neutral bar,Mechanical impect strength IK 09three phase, cement spill protector, 415volts, including one new mccb 250A 4pole 25kA fixing at site and electric connection complete all as specified and as directed.Make: Havells/Indo Asian/Legrand
110Supply and Fixing surface mounted 36 Watt LED Surface full lit luminaire with glare free uniform illumination with longer life and less maintenance 36 wattages in 2 ft x 2 ft (>100 Lumen/Watt) and electric connection completeall as specified and directed. Make: Philips/Bajaj/CG
111Supply and fixing in repair MCCB125 Amps 16 KA, Four Pole 415 volts, 50 HZcomplete all as specified and as directed. Make: L&T/Indo Asian/Legrand
112Material and labour for sub main wiring withtwo single core stranded copper conductor unsheathed PVC insulated cable 1100V grade, 10 sq mm drawn throughand including 20MM size of non-metallic PVC rigid conduit with 10 sqmm copper conductor cable as earth conductor and conduit accessories fixed up in surface/ recessed as required, including connecting up completeall as specified and directed including taking down old U/S wiring. Note:-Two run of cable and one run of earth continuity copper conductor and non metalic PVC conduit shall be measured as one unit length. Make: Havells/Plaza/Finolex
113Supply, installation, testing and commissioning Feeder Pillar Box out door type weather proof, dust & vermin proof CPRIapproved LT panel made out of 3.15 mm thick CRCA sheet front and back door operable type and suitable for operation on 415V, 50Hz, AC supply, conforming to IP-54 and fixed on angle iron frame/channel of suitable size complete, aluminium bus bar chamber cable alley, cable glands brass chromium plated of different sizes suitable for incoming and out going cable panel, painted with powder coated paint including necessary PCC (1:3:6) foundation extending 300mm above GL and 60cm wide platform in front of the panel complete all specified and directed by Engir-in-Charge withthe following accessories :-INCOMING(a) Aluminiumbus bar of capacity 400 Amps with epoxy insulated supports 3 phase and neutral -1 set (b) MCCB 250 Amps 4 pole 36 KA with adjustable type - 01 No (c ) Volt meter digital type 96 sqmm with in built selector switch - 01 set (d) Amps meter digital type 96 sqmm with CT"s 200/5 -03 Nos and in built selector switch - 01 Set(e) Indicating lamp set LED type - 01 set OUTGOING(a) MCCB 63 Amps, 4 Pole 16 KA adjustable type - 2 Nos (b) MCCB 100 Amps, 4 Pole 16KA adjustable type - 3 NosNote (1)Rates deemed to be included for suitable lugs and glands for incoming and out going of LT UG cable. (2) The Contractor Shall submit the drawing with sample of accessories for approval before executing the work.(3) Insulators, wiring, bus bar sleeves, lugs, gland,sheet metal enclosure etc including complete wiring with suitable size of copper wire
114Supply, installation, testing & commissioning of maintenance free chemicalearthing system comprising 17mm dia copper bondedrod 3 mtr long horizontally pre welded T-terminal rod with provision for connection size of 50 x 150mm long, 6mm thickness with equal space either side, with 12mm dia hole of 02 numbers each on either side of the terminal clamp with 250 microns (average) coating thickness, tested and certified by CPRI India alongwith 50 Kg earth energizer compound and 10 litres earth resistance reducingliquid. The earthing energizer compound and resistance reducing earthing liquid shall be tested as per IEC-62561-7 read with ASTM G57-06, CI 3.4 A by any NABL accredited lab. The above mentioned rod shall be installed in 4-6 inch bore, 12 feet depth with a distance of minimum 3 meters between each installation including taking down existing one all as directed. Make : Model HTSP 317 of safeTrode or equivalent in OBO Betterman/ FURSE/ERICO.
115The quoted rate is deemed to be included the following :- (i)Prior toinstallation of maintenance free chemicalearthing, soil resistivity test to be carried out at the location where earthingwork to be donein presence of Engr-in- Charge/JE (E/M),user and the report has tosubmitto Garrison Engineer with recommendation of manufacturer, if required additional interconnection ofearthing (not more than 04 number of earthing) to achive earth result less then 1 Ohms. The arrangement done for soil resistivity testingandsubmission of report with recommendationdeemed to be included in the quoted rate.
116(ii) The description/ size/ qty of items mentioned in above are for indicating only however qty/ size may vary at site condition to maintain the earth resistance 1 ohm. The contractor shall quote rate by considering all factors.
117(iii) Rateofearth energizer compound of 25 Kg of 02 bags and earthresistance reducingliquid 10 litre per cane for each pit deemed to be included in the quoted rate.
118(iv)Resistivity of earth energizer compound and resistance reducing earthing liquid shall be certified by any NABL accredited lab carried out as per IEC-62561-7 read with ASTMG57-06, CI-3.4A and the certificate of same shall be submitted by the contractor before commencement of work.
119(v) Earth enhancing material should not leach into the adjacent soil or underground water channels and its PH valve should be in neutral range complete all as specified and as directed. It should solidify when mixed with water and set like concrete.
120(vi) Copper strip of size 20 x 3 mm shouldbe fixed on proper post insulator at the instrument end ( copper strip will be measured and paid separately).
121(vii)Testing of earth shall be carriedout in presence ofdepartmental and user representativeand report shall be submitted to Garrison Engineer duly signed by all concern.
122(ix)Earthing shall be tested after completion of work by the contractor in presence of Engr-in-charge, user and proper record shall be maintened duly signed by all concerned.After testing if the desired earth resistance of less than 1 Ohm is not obtained, the earthing will be redone at no extra cost to Govt. till desired result is obtained.
123(viii)Earth resistance tester will be provided by the contractor.Tester should be calibrated from authorised company/ lab.
124(x) The contractor shall given a written guarantee of minimum three years for maintaining the earth resistance less than 1 Ohm after certified date of completion.
125(xiii) A security deposit of value equal to 2.5 % of the rate quoted for chemical earthing per each earthing shall be retained from payment due to the contractor for the guarantee period.
126(xii) During the guarantee period, if earth resistance is not maintained less than 1 ohm the contractor has to redo or rectify at no extra cost to Govt till desired result is mainained.
127(xi) No further maintenance or periodic watering or recharge shall be required in earthing during its guarantee period of over 03 years in all type of soil including soft/ disintegrated or hard rock.
128(xv) The connection clamp shall be permanentlly welded to the copper boundedrodto avoid any kind of connectivity loss,.The pre-welded copper bounded rod shall not need any additional clamp for termination.
129(xvi) The acceptable earth resistance at earth busbar/ test point shall not be more than 0.1 ohm.
130(xvii)The contractor shall submit CPRI India certified document for copper bonded rod to ensure genuity of material.
131(xviii) Sign boardof mild steel 2 mm thick duly painted with two coats of synthetic enamel paint over a coat of red oxideZinc chrome primer showing result of earthing should be fixed near the earth pit after completion as directed by engr -in- charge.
132(xix)Earth work such as auguring andmaking good the surrounding area shall carried out in any type of soil.
133Material and labour for Copper strip 20 x 3mm thick as earthing lead fixed to wall/roofs etc including taking down existing one all as directed. NOTE : All Joints should be joined by Exothermic Welding or Brazing.
134Material and labour forEarth pit cover madeof heavy duty poly plastic of high grade polypropylene tested and certified by any NABL accredited lab for load bearing capacity not less than 9.2 tonnes with top dia not less than 250mm, bottom dia not less than 330 mm and height not less than 260 mm dia for each electrode pit complete including taking down all as specified and directed. Make : Model SEPC 250 of SAFE TRODE/ Electrogrip Model/ EGTEK3LC of ISG Global or equivalent in OBO Betterman/ ERICO. Note :- The contractor shall submit load bearing capacity certificate from the manufacturer.
135Supply and Fixing Recess mounted 36 Watt LED Surface full lit luminaire with glare free uniform illumination with longer life and less maintenance 36 wattages in 2 ft x 2 ft (>100 Lumen/Watt) and electric connection completeall as specified and directed. Make: Philips/Bajaj/CG
136Supply and fix in replacement microprocessor based automatic fire alarm control panel complying with BSEN 54 single loop panel input voltage 230 V AC (+-10% to 15%) 50 HZ, output 21.5 -28.5 V DC, with battery microprocessor based automatic fire alarm control panel complying with BSEN 54 single pole panel provide battery with box breakup up to 24 hrs in standby mode and 15 min in alarmcondition complete all as specified and directed. Make: Honeywell/ Cease fire/Universal (Ravel)
137Supply and fixing Fire Alarm Sounders / Sirens Electronic type horizontal single stage continous normal operation for atleast 50 minutes with sound level 65 DB to 120 DB measuredat 1.5 Mtr with sound output variation of + 5 DB 500 mtrs rangeall as specified and as directed.
138Supply and installation of battery 12 V 7 AH.Make:-Exide/Amron/Luminious
139Supply, laying and testing of 1.5 sqmm 2 core copper cable with 15mm PVC conduit pipe all as specified and as directed.
Disclaimer :