Tender For Special Repair/ Replacement Of Existing Ac Plant At P-66 Ac Plant Room Under Ge (U) Bathinda At Bathinda Mil Stn, bathinda-Punjab

Military Engineer Services-MES has published Tender For Special Repair/ Replacement Of Existing Ac Plant At P-66 Ac Plant Room Under Ge (U) Bathinda At Bathinda Mil Stn. Submission Date for this Tender is 06-03-2024. HVAC Tenders in bathinda Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

41713584
Corrigendum : Tender For Special Repair/ Replacement Of Existing Ac Plant At P-66 Ac Plant Room Under Ge (U) Bathinda At Bathinda Mil Stn
Open Tender
Indian
Punjab
bathinda
06-03-2024

Tender Details

Tender For Special Repair/ Replacement Of Existing Ac Plant At P-66 Ac Plant Room Under Ge (U) Bathinda At Bathinda Mil Stn

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 10-Feb-2024 Corrigendum 2 BOQ 28-02-2024
2 10-Feb-2024 Corrigendum 1 Date 28-02-2024
3 10-Feb-2024 Corrigendum 3 Other 28-02-2024
4 28-Feb-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 06-03-2024

Key Value

Document Fees
INR 1000 /-
EMD
INR 222000.0 /-
Tender Value
INR 1.47 Crore /-

BOQ Items

Name of Work : SPL REPAIR/ REPLACEMENT OF EXISTING AC PLANT AT P-66 AC PLANT ROOM UNDER GE (U) BATHINDA ATBATHINDA MIL STN
Sl. No. Item Description
1Schedule "A" Part - I
2Dismantling and taking out unserviceable central Air Conditioningplant three unit of capacity 40 TR each including compressor, motors, condenser, water pumps, water tank and cooling towers including PCC staging and Air handling units(04 nos) and its ducting with hanging arrangements, LT panel boards, piping and cables i.e complete system of existing AC plant installed at the location as directed by GE and removing from site and depositing to MES store yard of AGE E/M(W/s & Refg) complete all as specified and directed by Engr-in-Charge. Note:- Rate quoted by contractor is deemed to include the cost of tools, plants, transportation& skilled labour and nothing shall be paid extraon this account.
3Note:- Design, supply, installation, testing and commissioning of central AC plant with the following parameters under specification complete mentioned in serialitem No. 2.01 to 56.00 here - in- after complete all as specified and directed.( Temperature maintain 20º C± 5º C and humidity 55%± 5%).
4Supply, installation, testing and commissioning of Minimum 40TR water cooled Scroll Chilling Machines fitted with hermetically sealed compressors, multi circuit Dx chiller, water cooled S&T condenser, Microprocessor based control panel, suitable for R-407 C Refrigerant, Shell & Tube Insulated Evaporator, Expansion Device, Suitable capacity Control Mechanism actual Cooling capacity on following Operation Parameters including cost of material and labour , testing , commssioning, installing, testing etc. all items mentioned under serial item no.2.01 to 2.20 of BoQ here-in-after to make the plant fully functional :-
5Chilled Water Entering Temperature : 12.17 deg C
6Chilled Water Leaving Temperature : 6.67 deg C
7Evaporator Fouling Factor : 0.0001 MKS
8Condenser Water Entering/Leaving Temperature at 36.2/32.4 deg C
9Refrigerant : R-407 C
10Maximum Allowable IKW / TR @ 100% Load : 1.55
111set.- Scroll compressor hermetic complete with suitable capacity squirrel cage induction motor with class "F" insulation suitable for operation on 415+ 10% volts, 50Hz, A.C. supply and automatic capacity control, safety switches, forced feed lubrication system etc. as per specifications.
121No. Close transition type automatic starter suitable for compressor motor complete with ammeter with CTs, over load protection, under voltage protection, protection against phase reversal & independent single phase preventers etc. complete as required.
131 Set - Lubrication device consisting of automatic electric oil pump, oil cooler, oil strainer, automatic pressure regulating valve, oil heater, oil heater thermal switch etc. as per specifications.
141 Set. - Matching Water Cooled condenser having Copper tube with Mechanically bonded aluminium fins.
151No. - Matching DX type chiller for Chiller units
161 Lot- Refrigerant piping fittings, valves and accessories to interconnect compressor, condenser, chiller and expansion valve.
171 Set- Microprocessor based control panel complete with all safeties, controls and LCD display as per specifications.
18Lot- Refrigerant line accessories comprising of safety valves, angle valve, liquid line indications.
19Lot- Suction line and chiller insulation with minimum 19mm thick polyvinyl nitril rubber insulation complete as required.
20Lot- Frame work for mounting the above condenser, chiller compressor and motor with base plate complete with anti vibration pads/springs.
21Lot- Initial / first charge of refrigerant gas and compressor oil.
221 No. Chilled water flow Switch of suitable size and capacity
23Lot-PCC cement concrete foundation for the Chiller unit as per manufature"s recommendation instructions.
24(2 W + 1 S) (2 working simultaneously and one working standby each of 50 % capacity)
25Supply, installation, testing and commissioning of centrifugal mono block type chilled water pump set all as per IS-12469 capable of delivering minimum 125 USGPM of water against 28 mtr head of 50% capacity each complete with all necessary accessories, flexible coupling, mechanical seals and drain connections , suitable for operation on 415+10% Volt, 50 Hz, 3 Phase AC power supply comprising of the following parameters including cost of material and labour , testing , commssioning, installing, testing etc. all items mentioned under serial item no.3.01 to 3.07 of BoQ here-in-afterto make the plant fully functional:-
261 No.- mono block type pump
271 No. - Suitable HP TEFC squirrel cage induction motor with class "F" insulation 2900 rpm synchronous speed, operating on 415+ 10% volts, 3 phase, 50 Hz A.C. supply.
28Lot- insulation of pump of 13 mm thick with aluminium foil faced closed cell chemically crossed linked XPE foam material.
292 Nos. -100 mm dia dial type pressure gauges.
30Lot- Mounting frame with Anti vibration pads.
31Lot-PCC cement concrete foundation for the pump unit as per manufacturer"s recommendation instructions
32(2 working simultaneously & 1 working standby---Each of 50% cap)
33Supply, installation, testing and commissioning of centrifugal mono block Condenser water pump set all as per IS-12469 capable of delivering minimum 170 USGPM of water against 22.00 mtr head each complete with all necessary accessories, flexible coupling, mechanical seals and drain connections , suitable for operation on 415+10% Volt, 50 Hz, 3 Phase AC power supply comprising of the following parameterscomprising of the following operation parametersincluding cost of material and labour , testing , commssioning, installing, testing etc. all items mentioned under serial item no.4.01 to 4.06 of BoQ here-in-afterto make the plant fully functional:-
341 No.- mono block type pump
351 No. - Suitable HP TEFC squirrel cage induction motor with class "F" insulation 2900 rpm synchronous speed, operating on 415+ 10% volts, 3 phase, 50 Hz A.C. supply.
362 Nos. -100 mm dia dial type pressure gauges.
37Lot- Mounting frame with Anti vibration pads.
38Lot-PCC cement concrete foundation for the pump unit as per manufacturer"s recommendation
39(2 working simultaneously & 1 standby---Each of 50% cap)
40Supply ,installation, testing and commissioning of centrifugal mono block type Hot water pump set all as per IS-12469 capable of delivering min. 90 USGPM of water against 28 mtr head of 100% capacity each complete complete with all necessary accessories, flexible coupling, mechanical seals and drain connections , suitable for operation on 415+10% Volt, 50 Hz, 3 Phase AC power supply comprising of the following parameters comprising of the following operation parametrsincluding cost of material and labour , testing , commssioning, installing, testing etc. all items mentioned under serial item no.5.01 to 5.06 of BoQ here-in-afterto make the plant fully functional:- :-
411 No.- mono block type pump
421 No. - Suitable HP TEFC squirrel cage induction motor with class "F" insulation 2900 rpm synchronous speed, operating on 415+ 10% volts, 3 phase, 50 Hz A.C. supply.
43Lot- insulation of pump of 13 mm thick with aluminium foil faced closed cell chemically crossed linked XPE foam material.
442 Nos. -100 mm dia dial type pressure gauges.
45Lot- Mounting frame with Anti vibration pads.
46Lot-PCC cement concrete foundation for the pump unit as per manufacturer"s recommendation
47(1 working simultaneously & 1 working standby---Each of 100% cap)
48Supply, installation, testing and commissioning of double skin floor mounted type air handling units fabricated & assembled complete, made of 25 mm thick panels consisting of GI casing of thickness 0.6mm outside layer and 0.6mm inside layer, injected at factory by moulding machine with polyurethane foam (PUF) insulation complete with blower section and filter section with filter of 5 micron at 95% efficiency, chilled water coil constructed out of copper tubes not less than 0.5mm thickness and aluminum fins, Suitable capacity TEFC drive squirrel cage induction motor 415 ± 10% volts, centrifugal forward / backward curved fan suitable for 50 mm SP, access door etc. complete as per standard specification. Maximum face velocity across the coil shall be 500 FPM and each 6 Row deep chilled water cooling coil and 2 Row deep hot water coil, and RH to be maintained at 55 %± 10 of following capacities and comprising of the following operation parametrsincluding cost of material and labour , testing , commssioning, installing, testing etcall items mentioned under serial item no.6.01 to 6.09 of BoQ here-in-afterto make the plant fully functional:- :-
49Coil of copper tube and aluminium construction sized at maximum face velocity of 500 FPM.
50Pre filter of 5 micron at 90% efficiency on the face of the coil in return air stream.
51Squirrel cage induction motors suitable for 415 ± 10% volts, 50 Hz, AC supply meeting criterion as per ASHRAE standard 90.1-2007 and high efficiency.
52Fan belt drive package
53Vibration isolators.
54Fan outlet velocity not exceeding 10 mps.
55Tag No. Space CFM
56AHU No. 1 (GF) of capacity 12600 C.F.M
57Note for serial item nos. 6.00, 6.01 to 6.09 of BoQ :- 1. The complete AHU shall conform to standard specification of capacity 40 Ton, 6-row coil deep, static pressure 120 and winter heating including foundation as per manufactureer"s recommendation complete. 2. Blower shall be DIDW ( Doube inlet Double width) Backward Curved/Airofoil type blade.
58Supply, installation, testing and commissioning of double skin floor mounted type air handling units fabricated & assembled complete, made of 25 mm thick panels consisting of GI casing of thickness 0.6mm outside layer and 0.6mm inside layer, injected at factory by moulding machine with polyurethane foam (PUF) insulation complete with blower section and filter section with filter of 5 micron at 95% efficiency, chilled water coil constructed out of copper tubes not less than 0.5mm thickness and aluminum fins, Suitable capacity TEFC drive squirrel cage induction motor 415 ± 10% volts, centrifugal forward / backward curved fan suitable for 50 mm SP, access door etc. complete as per standard specification. Maximum face velocity across the coil shall be 500 FPM and each 6 Row deep chilled water cooling coil and 2 Row deep hot water coil, and RH to be maintained at 55 %± 10 of following capacities and comprising of the following operation parametrsincluding cost of material and labour , testing , commssioning, installing, testing etcall items mentioned under serial item no.7.01 to 7.09 of BoQ here-in-afterto make the plant fully functional:- :-
59Coil of copper tube and aluminium construction sized at maximum face velocity of 500 FPM.
60Pre filter of 5 micron at 90% efficiency on the face of the coil in return air stream.
61Squirrel cage induction motors suitable for 415 ± 10% volts, 50 Hz, AC supply meeting criterion as per ASHRAE standard 90.1-2007 and high efficiency.
62Fan belt drive package
63Vibration isolators.
64Fan outlet velocity not exceeding 10 mps.
65Tag No. Space CFM
66AHU No. 2 (GF) of capacity 18000C.F.M
67Notes for serial item nos. 7.00, 7.01 to 7.09of BoQ:Note:- 1. The complete AHU shall conform to standard specification of capacity 40 Ton, 6-row coil deep, static pressure 120 and winter heating including foundation as per manufactureer"s recommendation complete. 2. Blower shall be DIDW ( Doube inlet Double width) Backward Curved/Airofoil type blade.
68Supply, installation, testing and commissioning of electric Hot Water Generator of 100 KW capacity for winter & Monsoon Reheating complete with control wiring complete all as specified and directed.
69Supply, Installation, commissioning & testing of horizontal (Wall/Floor mounted)Pan typehumidifier 5.0 KW made from stainless steel grade 304 sheet with inlet, drain & steam outlet, nozzle, insulation 25 mm thick fiber glasswool (150 crown) and cladded with 22 gauge GI sheet, low level switch, nylon ball, float valve, high temp, cut out thermostat duly factory wired with copper bus bar connector, electric panel with incomer S.F.U, out going contactors etc complete all as specified.
70Supply, Installation, testing and commissioning of FRP cooling tower in accordance with BS-4485 of minimum 50 TR heat rejection capacity (2 Working + 1 Standby) with FRP water basin PVC fillings with integral louvers and drift eliminators complete with hot water basin either fitted with spray nozzles or having self rotating sprinklers, statically & dynamically balanced axial flow type fan direct driven or driven through reduction gear box with TEFC induction motor , suction screen, make up quick filling arrangement, over flow and drain connections with necessary valves and suitable inspection aluminium ladder of suitable length, access arrangement for cooling lower interior, installed on MS girders (MS-I sections) fixed in masonry foundations with cement concrete footing, second class brick work and cement mortor1:6; all accessories, basin fittings, fan, fan motor suitable for 415 Volt supporting structure, anti vibration mountings etc. complete and 50 HZ power supply having isolator panel with MCB of suitable capacity at cooling tower to make it fully operational and maintanable.having following technical data:- (a)Water flow/tower 200 USGPM (b)Entering Water Temperature : 97 °F (c)Basin Water Temperature : 90 °F (d)Type of fan: Propeller type of motor suitable capacity, 415 volt ± 10% volts, 600 RPM , Weather proof. NOTE: 1. Cooling tower shall be located at 1200 mm height from ground level on staging as per manufactures recommendations. 2. The maximum allowable sound power at a distance of 1 metre from the fan shall be up to 75 DB(A).
71Supply, fabricating, installing, commissioning and testing factory (CPRI approved) fabricated LT panel boardconsisting of theTPN, 3 phase, 415 volt, 35 MVA rupturing capacity,04 wire (In separate chamber) made of 2 mm thick CRCA sheet powder coated conforming to IP-54,vermin proof including interconnection wiring, indicating lamps etc. for AC plant (indoor type)and angle iron of size 50mm x 50mm x 6mm, pedestal frame grouted in PCC (1:2:4) type B-1 using 20mm graded aggregates, thimble and cable entry boxes with cable glands. Panel should covered from all sides with front and back lockable door and hinges complete, The cubicle panel shall be free floor standing type, complete with interlocking arrangement & earth bus. The panel shall have compartmentalized arrangement to accommodate one feeder in each compartment. A vertical cable alley of suitable width shall be provided to serve one or two vertical feeder sections. Also the openings between the bus bar chamber and the feeder section shall be shrouded with Bakelite/hylam sheet with minimum 3 mm thickness. All the hardware used in fabrication of panel shall be galvanized with zinc passiveness complete all as specified and consisting of the following:-
72Contd serial item No. 11.00 Incoming (i) 1 No. 400 Amps, 35 KA TPN MCCB"s with O/C, S/C & E/F release. (ii) 1 NO. 0-500 Volts digital voltmeter 96x96 mm with selector switches etc as required (iii) 1 No.0-400 Amps, digital ammeter 96x96 mm with 3Nos.400/5 CT"s ratio with selector switch (iv) Phase indicating lamps etc with control fuses as required (v) Breaker On/Off trip indication (vi) 1 Set of 600 Amps TPN Aluminium Bus Bars with colour coded heat shrinkable sleeves. (vii) 1 Set digital type 3 phase 400 Amps Electronics KWH meter
73Contd serial item No. 11.00 Outgoings (i) 4 Nos. 125 amps TPN MCCB, 25 KA , electrically operated as outgoing feeders for 3 Nos. chilling unit compressor motors and 01 No. Hot water Generator. (ii) 11 Nos. TP MCB of 40 Amp with DOL starter for motor, over load relay with built in single phasing protection for chilled water Pumps, Hot Water Pumps, condenser water pumps & CT fan motors. The compartment shall contain an indicating lamp with MCB for ‘ON’ status of pump motor. (iii) The panel shall include the following components & accessories. (iv) Overload relay and single phase preventer as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. (v) Terminal block for power distribution. (vi) Power Contactor. (vii) Phase indicating lights and indicating light for ON status. (viii) 96 mm x 96 mm digital voltmeter and ammeter with selector switches and CTs-11 Sets . (ix) Time delay relay for delayed automatic restart of AHU motor (0-180 Sec) (x) Wiring for micro switch for starting / stopping the fan when fire damper closes. (xi) All Cable trays shall be Galvanized and Conduits shall be MS. (xii) ON/ OFF push button- 11 Sets.
74MOTOR CONTROL PANEL FOR AHUs .
75Supply, fabricating, installing, commissioning and testing factory (CPRI approved) fabricated LT panel boardconsisting of theTPN, 3 phase, 415 volt, 35 MVA rupturing capacity,04 wire (In separate chamber) made of 2 mm thick CRCA sheet powder coated conforming to IP-54,vermin proof including interconnection wiring, indicating lamps etc. for AC plant (indoor type)and angle iron of size 50 x 50 x 6mm, pedestal frame grouted in PCC (1:2:4) type B-1, thimble and cable entry boxes with cable glands. Panel should covered from all sides with front and back lockable door and hinges complete, The cubicle panel shall be free floor standing type, complete with interlocking arrangement & earth bus. The panel shall have compartmentalized arrangement to accommodate one feeder in each compartment. A vertical cable alley of suitable width shall be provided to serve one or two vertical feeder sections. Also the openings between the bus bar chamber and the feeder section shall be shrouded with Bakelite/hylam sheet with minimum 3 mm thickness. All the hardware used in fabrication of panel shall be galvanized with zinc passiveness complete all as specified and consisting of the following:-
76Contd serial item No. 12.00 Incoming Incoming (i) 1 No. 160 Amps, 16 KA TPN MCCB"s with O/C, S/C & E/F release. (ii) 1 NO. 0-500 volts digital voltmeter 96x96 mm with selector switches etc as required (iii) 1 No. 0-100 amps, digital ammeter 96x96 mm with 3 nos. 100/5 CT"s ratio with selector switch (iv) Phase indicating lamps etc with control fuses as required (v) Breaker On/Off trip indication (vi) 1 Set of 200 Amps TPN Cu. Bus Bars with colour coded heat shrinkable sleeves.
77Contd serial item No. 12.00 Incoming Outgoings 2 No.TP MCB of 32 Amp with DOL Starter for AHU motor, over load relay with built in single phasing protection. The compartment shall contain an indicating lamp with MCB for ‘ON’ status of AHU motor.
78Supply, laying& testing XLPE insulated screened PVC bedded, galvanised steel strip or wire armored, earthed electric power cables (heavy duty) with aluminum conductor 1100/660 volts grade LT UG cable laid in ground/ in ducts/in pipes/on cable trays of PVC insulated aluminum conductor armoured cables of 1.1 KV grade confirming to IS complete with cable tray, clamps, saddles etc, including effecting proper connection to the equipment of size 70 sqmm 3 corefor Chillers & Hot Water Generator panel complete all asrequired and specified
79Supply, laying& testing XLPE insulated screened PVC bedded, galvanised steel strip or wire armored, earthed electric power cables (heavy duty) with aluminum conductor 1100/660 volts grade LT UG cable laid in ground/ in ducts/in pipes/on cable trays of PVC insulated aluminum conductor armoured cables of 1.1 KV grade confirming to IS complete with cable tray, clamps, saddles etc, including effecting proper connection to the equipment of size 16 sqmm 4 core for main to 02 Nos. AHU Panels
80Supply, laying& testing XLPE insulated screened PVC bedded, galvanised steel strip or wire armored, earthed electric power cables (heavy duty) with aluminum conductor 1100/660 volts grade LT UG cable laid in ground/ in ducts/in pipes/on cable trays of PVC insulated aluminum conductor armoured cables of 1.1 KV grade confirming to IS complete with cable tray, clamps, saddles etc, including effecting proper connection to the equipment of size 6 sqmm 3 corefor Chilled Water, Condenser pumps, Hot Water Pumps , CT Fans & AHU Blowers
81Supply, laying& testing XLPE insulated screened PVC bedded, galvanised steel strip or wire armored, earthed electric power cables (heavy duty) with copper conductor 1100/660 volts grade LT UG cable laid in ground/ in ducts/in pipes/on cable trays of following PVC insulated aluminum conductor armoured cables of 1.1 KV grade confirming to IS complete with cable tray, clamps, saddles etc, including effecting proper connection to the equipment of size 1.5 sqmm, 4 corefor controls complete all asrequired and specified
82Notes for serial item no.13.00 to 16.00 of BoQ:- (i) The cost includes cost of suitable pipes for cable protection at road crossings, cable trays, protective bricks, sand , excavation returning filling and removing etc. (ii) All exposed cables in trenches/wall/ceiling/roof trusses shall be provided with silicon based fire resistance coating compatible for PVC cables. (iii) All terminations shall be made with proper lugs in the approved manner.
83Supply& Fixing GI earth strip 32 mm x 4 mm below ground, with and including 40 mm light grade GI pipe wherever required and on surface or in recess for connections etc. Note:- (i)Cost of earth work is deemed to be included in the quoted rate. Nothing extra shall be paid on this account.
84Material & Labourfor Earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 metre below normal ground level (with top edge of earth plate not less than 1.5 metre below ground level) connected to galvanized iron earth strip 32x6 mm , (main earthing lead) by means of galvanized bolts, nuts and washers all as shown in electrical plate No 3 of MES Schedule Part-I (2009) with connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt around earth plate & 32 mm dia GI pipelight grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia medium grade for watering pipe with funnel & wire meshincluding necessary earth work and PCC (1: 3 : 6) type C-1 for earth pit and 40 mm thick precast RCC cover in 1 : 2 : 4 type B-1 with 3 Nos 8 mm dia TMT bars both ways with 12mm dia round bar handle completeall as specified, directed and as shown in plate No. 03 of MES Schedule Part-I. NOTE: Earth lead wire and its protection pipe upto and including 7.5 mtr only from the top of earth electrode are included under this item and additional earth GI earth strip/protection pipe etc. if any required at site shall be measured and paid for separately under appropriate item of Schedule `A’ NOTE -The quoted rate is deemed to include for earth work in any type of soil, PCC (1:3:6) type C1 chamber, RCC 1:2:4 type B1 cover 50mm thick reinforced with 8mm dia TMT bars @ 150mm, center to center both ways, funnel with watering pipe.
85Supply & Fixing of 4mm GI wirecomplete all as specified and as directed byEngr-in-charge. Note:-(i) All terminations shall be made with proper lugs in the approved manner and rate of this aspect is included in this item and nothing shall be paid extra on this account.
86PIPING-CHILLED WATER
87Supply, installation, testing and commissioning of the following nominal sizes of chilled & Hot Water plumbing pipes MS ‘C’ CLASS as per IS: 1239 of size 125mm dia including fittings, inside the building(with necessary clamps, vibration isolators and fitting like valves, flanges, union etc. but excluding valves, strainers, gauges etc.) cut to required lengths and welded at joints and inclusive of accessories like elbows, tees, reducers, sockets etc. including insulating with 19 mm (for all pipes) and 13mm (for drain pipe) thick closed cell chemically cross linked fire retardant polyethylene foam insulation of density 30 Kg/cum. The thermal conductivity of the material should not exceed 0.035 W/Mk at an average temp of 40 deg C, covered with aluminium faced foil complete with application with rubber based adhesive Pidilite SR 998 and 50mm x 3 mm thick self adhesive tape on both longitudinal & transverse joints includingrepairing damage to building etc simultaneously completeall as specified.
88All as per item no 20.01 here -in-before 100 mm dia including fittings
89All as per item no 20.01 here -in-before 80 mm dia including fittings
90All as per item no 20.01 here -in-before 65 mm dia including fittings
91Notes for serial item nos. 20.01,21.00,22.00 & 23.00:- (i) The quoted rate is deemed to include cost of suitable fitting such as bend, tail piece andtees etc, and also included excavation returning filling and removing etc. Nothing extra shall be paid on this account. (ii) All exposed pipes in trenches/wall/ceiling/roof trusses shall be provided two coat synthetic enamel paint over a coat of red oxide primer.
92Supply and fixing in position butterfly valve, PN-1.6 handle operated type, Gun metal body conforming to BIS:5155, MSS SP67 & APT 609, duly insulated with same material as per ser item No. 20.01, screwed/flanged ends suitable for tubes of size 100mm bore.
93Supply and fixing in position butterfly valve, PN-1.6 handle operated type, Gun metal body conforming to BIS:5155, MSS SP67 & APT 609, duly insulated with same material as per ser item No. 20.01, screwed/flanged ends suitable for tubes of size 80mm bore.
94Supply and fixing in position butterfly valve, PN-1.6 handle operated type, Gun metal body conforming to BIS:5155, MSS SP67 & APT 609, duly insulated with same material as per ser item No. 20.01, screwed/flanged ends suitable for tubes of size 65mm bore.
95Supply and fixing in position balancing valve, high quality CI-220, BIS:1152, Grade 220 ASTM-a48 CT-35, duly insulated with same material as per ser item No. 20.01, screwed/flanged ends suitable for tubes of size 100mm bore.
96Supply and fixing in position balancing valve, high quality CI-220, BIS:1152, Grade 220 ASTM-a48 CT-35, duly insulated with same material as per ser item No. 20.01, screwed/flanged ends suitable for tubes of size 80mm bore.
97Supply and fixing in position balancing valve, high quality CI-220, BIS:1152, Grade 220 ASTM-a48 CT-35, duly insulated with same material as per ser item No. 20.01, screwed/flanged ends suitable for tubes of size 65mm bore.
98Supply and fixing in position check valve (Non-return Valve), CI body, screwed/ flanged ends duly insulated with same material as per ser item No. 20.01, screwed/flanged ends suitable for tubes of size 65 mm bore.
99Supply and fixing in position check valve (Non-return Valve), CI body, screwed/ flanged ends duly insulated with same material as per ser item No. 20.01, screwed/flanged ends suitable for tubes of size 50 mm bore.
100Supply and fixing in position butterfly valve, handle operated, suitablefor 32 mm bore tube, gun metal body screwed/flanged ends, complete all as specified.
101Supplying, installation, testing and commissioning of Auto air vents with isolating ball valves of 15mm bore size in the chilled water pipe complete all as specified.
102Supply, installation, testing and commissioning of 25 mm dia Ball brass valves, high pressure, with polythene float and flynut complete , screwed for iron pipe or brass ferrule and fixed for drain with fittings etc complete all as specified.
103Supply, fixing in position dial type industrial pressure gauge having dial size 150 mm complete all as specified.
104Supply, fixing in position dial type mercury-in- glass filled industrial thermometers complete with fittings all as specified.
105Supply and fixing in position water flow switch complete with copper control wiring for chilled water circuit of machine complete all as specified and directed.
106Supply, installation, testing and commissioning of insulated 3 way mixing valve for fixing in chilled water piping in the AHU complete for the Air Handling Units duly insulated complete with required controls wiring/installation kit etc complete all as specified and directed
107Supply, installation, testing and commissioning of proportional cooling only thermostats for the Air Handling Units complete with required controls wiring/installation kit etc. complete all as specified and directed
108Supply, fixing, testing and commissioning of condenser water pipes of MS class ‘C’ of 125mm diaand material along with necessary clamps, vibration isolators and fittings such as bends, tees etc but excluding strainer and gauges etc adequately supported on rigid supports/buried in ground including excavation & return filling etc complete all as specified. and directed.
109Supply, fixing, testing and commissioning of condenser water pipes of MS class ‘C’ of 100mm diaand material along with necessary clamps, vibration isolators and fittings such as bends, tees etc but excluding strainer and gauges etc adequately supported on rigid supports/buried in ground including excavation & return filling etc complete all as specified. and directed.
110Supply, fixing, testing and commissioning of condenser water pipes of MS class ‘C’ of 80mm diaand material along with necessary clamps, vibration isolators and fittings such as bends, tees etc but excluding strainer and gauges etc adequately supported on rigid supports/buried in ground including excavation & return filling etc complete all as specified. and directed.
111Supply, fixing, testing and commissioning of condenser water pipes of MS class ‘C’ of 65mm diaand material along with necessary clamps, vibration isolators and fittings such as bends, tees etc but excluding strainer and gauges etc adequately supported on rigid supports/buried in ground including excavation & return filling etc complete all as specified. and directed.
112Notes for serial item nos. 40.00 to 43.00:- Note:- Cost of earthwork and fittings required for fixing of pipe is included in the quoted rate. Nothing extra shall be paid on this account.
113Supply, fixing in position‘Y" type strainer, CI body of size 100 mmduly insulated complete all as specified.
114Supply, fixing in position‘Y" type strainer, CI body of size 80 mmduly insulated complete all as specified.
115Supply, fixing in position‘Y" type strainer, CI body of size 65 mmduly insulated complete all as specified.
116Supply and fixing in positionGI pipe medium grade of size 32 mm dia including allfittings such as elbows, brench, union, tees & reduceres, etc and cut to required lengths and installed with all screwed joints complete all as specified.
117Supply, installation, testing and commissioning of MS water storage tank ( cylinderical vertical with closed top),expansion tank of size 1000 Ltr complete with suitable with FR- XLPE/XPE 19 mm thick of minimum bulk density 28±4Kg/cum covered with vapour barrier and finished with 0.5 mm thick AI cladding and applied with Pidilite SR 998 complete with air vent and drain connection with float valve, quick fill and control valves and suitable foundation etc. complete all as specified and directed. Note:-1. The expansion tank shall be complete with all accessories so as to make it ready for installation and commissioning on site. 2. Securing the insulation with and including mechanically fastened nylon/ steel straps of size 12 mm/50 mm at maximum intervals of 1.2 metre. 3. Cost of foundation required at site is deemed to be included in the quoted rate. Nothing extra shall be paid on this account.
118Supply, installation ,testing and commissioning of HDPE, 3 layer, polyethylene water storage tank ( cylinderical vertical with closed top) make up tank of size 2000 Ltr. complete with air vent and drain connection & overflow, make up connection with float valve & foundation etc. complete all as specified and directed. Note:-1. The make up tank shall be complete with all accessories so as to make it ready for installation and commissioning on site. 2. Cost of foundation required at site is deemed to be included in the quoted rate. Nothing extra shall be paid on this account.
119AIR DISTRIBUTION
120Supply,assembly, erection and testing of rectangular/square ducts, hollow profile, duly factory boxed including all acessories such as corner, cleat, carriage bolt, gasket and appriate sealent on longtudinal joints etc. for supply air & return air system as per IS - 655 in accordance with the approved shop drawings and specifications using 24 gauge galvanised sheet steel complete all specified.
121Supply,assembly, erection and testing of rectangular/square ducts, hollow profile, duly factory boxed including all acessories such as corner, cleat, carriage bolt, gasket and appriate sealent on longtudinal joints etc. for supply air & return air system as per IS - 655 in accordance with the approved shop drawings and specifications using 22 gauge galvanised sheet steel complete all specified.
122Supply,assembly, erection and testing of rectangular/square ducts, hollow profile, duly factory boxed including all acessories such as corner, cleat, carriage bolt, gasket and appriate sealent on longtudinal joints etc. for supply air & return air system as per IS - 655 in accordance with the approved shop drawings and specifications using 20 gauge galvanised sheet steel complete all specified.
123Supply, fabrication, installation and testing the flexible connections constructed of fire resistant double resin sleeve as per the approved shop drawings complete all as specified
124Supplying, fixing, testing and commissioning of powder coated aluminium section of 20 G thick for supply/ return air grilles / diffusers without aluminium volume control dampers complete all as specified.
125Supplying, fixing, testing and commissioning of GI volume control dampers made of 20 G thick sheet complete all as specified .
126Fresh Air Grilles
127Supplying, fixing, testing and commissioning of power coated extruded aluminium section of 120 G thick for fresh air grill in weather maker room with volume control dampers, bird screen etc complete all as specified .
128Supply, installation, commissioning & testing of motorized combination fire and smoke damper (spring return type) of atleast 120 minute fire rating and all as specified.The fire damper shall be complete with electronic temperature sensor, electrically operated actuator, control panel & wiring.The fire dampers shall be located in the supply/return air ducts, at all fire rated crossovers (shafts/walls etc.) The control panel will be such located that the reset can be easily done, including Electrical spring type actuator,remote indication of the fire damper position complete. Note:- 1.The fire damper shall be of 20 gauge galvanised iron sheet. 2. The quoted rate is deemed to include cost of all items required for maing the fire damper fully functional irrespective of the descrption mentioned above.
129Supply, installation, commissioning & testing of Insulation material for duct acoustic lining resin bonded fiber glass wool 25 mm thick of density 48kg/ Cu. m with one side factory laminated either black glass woven cloth or black glass tissue.The Thermal conductivity of the fiberglass for air-conditioning application shall not exceed 0.034 k Cal per hour sq.m °C/metre at 30°C mean temperature andaverage Noise Reduction Coefficient (NRC=1) frequency range from100 Hz to 8000Hz )and cover the insulation with 213 SWG perforated almn sheet having atleast 20% perforation with joint overlapped and screwed to frame by means of brass screws to produce an even surface complete all as specified.
130Supply install test and commissioning of thermal insulation of duct with 13 mm thick closed cell chemically cross linked fire retardant polyethylene foam insulation of density 30 Kg/cum. The thermal conductivity of the material should not exceed 0.035 W/Mk at an average temp of 40° C, covered with aluminium faced foil complete with application with rubber based adhesive Pidilite SR 998 and 50mm x 3 mm thick self adhesive tape on both longitudinal & transverse joints simultaneously all as specified.
131NOTE FOR DUCT for serial itemNos 50.01 to 56.00 of BoQ:- (i) Duct design and layout to meet the air conditioning as well as acoustic need of the projectin accordance to IS:655 duly vetted by IIT/NIT will be submitted by the contractor for approval of GE before commencement of ducting work. (ii) For payment purpose area of duct shall be calculated on the basis of externaldimensions of duct. (iii) Cost of MS hangers including fasteners for erection of ducts is deemed to be included in the quoted rate. Nothing extra shall be paid on this account.
132NOTE:- (A) CIVIL WORK COMPRISING OF THE FOLLOWING :- (i) Masonry foundation for chilling units pumping sets cooling tower, electric panel, make up water tank and AHU shall be as per manufacturer’s instruction/recommendation and making opening in brick wall/other type of walls and making good for ducts, pipes cable and fresh air intake- 01 Job. (ii) Removing carefully false ceiling for dismantling AC duct and refixing after installation or new AC ducts including making good to damaged false ceiling all as directed by Engineer-in-Charge- 01 Job. (B) WATER SUPPLY (i) Water connection to be provided with GI pipe medium grade of suitable size (as directed by GE) within 100 metre distance including excavation and earthwork all as directed at site. (C) OIL (i) Initial charge of oil and refrigerant gas for complete system. (D) Mercury in glass industrial type screw thermometer and digital thermometer wall mounted to be provided as per manufacture"s recommendation and as directed. (E):- Sling psycrometer measureing RH between 10 to 100 % for DBT between 1 and 38 º C with as accuracty of ± 0.5º C of size 19 x 2.5 x 2.5 cms (7.5x1x1 inch) operating condition -5 and 50º C to be provided (02 Nos) Cost of material and labour required for exeution / implimentation of Note No. "A" to "E" is deemed to be included in the quoted rates of respective item as applicable .Nothing extra shall be paid on the account.
133Sub total of Part - I
134Schedule "A" Part - II
135Manning and Operation of Central Air Conditioning Plant/ chiller system scroll type compressor of capacity 80 Ton at P-66 AC Plant WEU at Bathinda Mil Stn in three shift ( each shift of 8 hours continuous duration operated by one skilled operator in each shift) including Sunday and holidaysincluding cleaning of central AC Plant comprising of compressor, motors, condensers, chiller, cooling tower, AHU , refrigerant piping, control pumps, water supply pipe line and controls, electric panel, instruments, starters, heating generator and control cabling/ wiring all as specified and directed by Engineer-in-Charge for smooth and efficient performance of AC plant to achieve desired inside condition through out the currency of contract.The timings and days of shift will be decided by Engineer-in-Charge
136Contd serial item no. 58.01 of BoQ Equipments as under :- (i)AC compressor 3x40 Ton (2x40 Ton in operation and 1x40 ton as stand by) (ii) Condensing unit Nos(2 Nos of operation and 01 No as stand by) (iii) 3 (Two running and one stand by ) Pump Sets for condenser water including pluming work. (iv) 3 (Two running & one stand by) Pump Sets for chiller units including plumbing work. (v) Air handling 04 Nos including blower motor, humidifier and dehumidifier. (vi) Electric panel including all controls and wiring. (vii) Cooling tower of 50 Ton capacity -03 Nos
137Manning and Operation of Central Air Conditioning Plant/ chiller system scroll type compressor of capacity 80 Ton at P-66 AC Plant WEU at Bathinda Mil Stn in three shift ( each shift of 8 hours continuous duration operated by one skilled operator in each shift) including Sunday and holidaysincluding cleaning of central AC Plant comprising of compressor, motors, condensers, chiller, cooling tower, AHU , refrigerant piping, control pumps, water supply pipe line and controls, electric panel, instruments, starters, heating generator and control cabling/ wiring all as specified and directed by Engineer-in-Charge for smooth and efficient performance of AC plant to achieve desired inside condition through out the currency of contract.The timings and days of shift will be decided by Engineer-in-Charge Note:- This item shall be operated immediately after satisfactorycompletion of serialitem No. 58.01 of this BoQ
138Contd serial item no. 58.03 of BoQ Equipments as under :- (i)AC compressor 3x40 Ton (2x40 Ton in operation and 1x40 ton as stand by) (ii) Condensing unit Nos(2 Nos of operation and 01 No as stand by) (iii) 3 (Two running and one stand by ) Pump Sets for condenser water including pluming work. (iv) 3 (Two running & one stand by) Pump Sets for chiller units including plumbing work. (v) Air handling 04 Nos including blower motor, humidifier and dehumidifier. (vi) Electric panel including all controls and wiring. (vii) Cooling tower of 50 Ton capacity -03 Nos
139Note for item No. 58.01 to 58.04 :- (a)Contractor shall employ one operator ( Skilled ) for shift of 08 hrs ( 03 shifts per day) to operate the AC plant during all working days, Sunday and holidays. (b) Timing of shift shall be as fixed by Engineer-in-Charge. (c) All the stationary, T & P , minor items required to maintain the installations in presentable manner and always keep installation neat and clean. (d) The contractor shall ensure to pay minimum wages of skilled labour ( including reliever to operator as per labour act) as notified by Government of India/ state Government / Local body published time to time whichever is higher. (e) The contractor shall change/ discontinue the M & O staff every 11 months to avoid claim of permanent job in Govt department. (f) The commencement of Phase-II will be effective immediately after physical completion of Phase-I work. (g) All stationary such as log sheet, attendance register, duty roster etc required for manning and operation are to be born by contractor without any extra cost.
140Contd Notes for serialitem No. 58.01 to58.04 of BoQ:- (i) EPF shall be applicable as per EPF Act 1952 .(ii) The reimbursement of Contribution Amount quoted by bidder for EPF &ESICshall bereimbursed by theGE (The Principal Employer) in RAR and Final Bill only after submission of valid and authenticated document insupport of proof of payment by the contractorto the concerned workmen in addition to following documents failingwhich payment against these heads shall not be made:- (ii)The complete list of workmen employed by contractor on commencement of work furnishing details such asname,father name, address, Aadhar, Bank account No. shall be submitted. Such list shall also form part ofRAR/Final bill. (iii) In case of EPF, statement of Universal Account Number (UAN) of workmen issued by Employees ProvidentFund Organisation (EPFO) and the same shall be verifiedby Principal Employer (GE) either directly from the EPFOportal or insisting on a payment receipt obtained by the contractor from EPFO portal while depositing contribution. (iv) In case of ESIC, the detail such as Employer code, Insurance number of the insured workmen and monthly contribution statement.
141Sub total of Part - II