Public Works Department-PWD has published Tender For Electrical Installation Work For Proposed Level Ii Trauma Center At Anamoy Sswh Second Campus Of Bmch In The Dist. Of Purba Bardhaman (Electrical Work) 6. Supply Installation Testing And Commissioning Of Fire Alarm System.. Submission Date for this Tender is 25-01-2024. Alarm Systems Tenders in purba West Bengal. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Cleaning, servicing and checking of all existing Intelligent multisensor Fire Detectors inbuilt with optical smoke sensor as well as additional heat detector sensor as per direction of EIC. |
2 | Supply, Installation,Testing & Commisioning of Micropresssor controlled AddressableMultisensor detector IP 42 ( VDS / UL /ERTL/ LPCB / FM approved ) withinbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolatoras per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. (Approved Make : Cerberus Pro / Honeywell/Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST ) |
3 | Supply, Installation,Testing & Commisioning of Addressable Manual Call Point( VDS / UL /ERTL/ LPCB / FM approved ) with in built short circuit fault isolatoras per NFPA style 7 wiring complete asrequired. (Approved Make : Cerberus Pro / Honeywell/Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST ) |
4 | Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/Gloster/ RR Kable/Polycab ) through 19 mm dia PVC "FR" type Rigid Conduit pipe with necessary arrangement as per G.S. (Make : Precision/ AKG/ Universal/ Polycab) on the surface of the wall. |
5 | Supply, Installation, Testing & Commissioning of IP Addressable Loop Powered Hooter ( sound output of minimum 90 db )cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. Degree of protection IP65 ( VDS / UL /ERTL/ LPCB / FM approved) approved. (Approved Make: Cerberus Pro/Honeywell/ Johnson Controls / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/ GST ) |
6 | Testing, rectification and rechecking of Loop line connected with the existing 1 no. Microprocessor based Intelligent Addressable Fire Alarm Control Panel ( VDS / UL / LPCB & FM approved ),and total system healthy with all detector and hooter (Approx-500)incl. Detectors and other Devices for addressing the entire fire detection system as per direction of EIC. of Anamoy SSW Hospital. The rate is incl. of 12V, 9AH, SMF Maintenance Battery (Mk. Exide / Amra Raze) incl. all accessories. |
7 | Making necessary drawing of total new & existing repairing installation and submitted to the office as per direction of EIC. |
8 | Supply, Installation, Testing & Commissioning of Intelligent signal processing unit having Voltage free NO contact which would be connected in series with magnetic coil of AHU power supply unit. In case of Fire, the voltage free contact would close the circuit to isolate the power supply of AHU. (Approved Make: Siemens Cerberus Pro/ Securiton / Bosch) |
9 | Labour charges for dismaintaling the existing fire detection system same such as PVC pipe,wire,dector,device and other accessories etc.[ 4 nos. labour for 3 days] |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail