Power Development Department has published Tender For Augmentation Of Conductor Size From 100Mmsq Acsr To 200 Sqmm Acsr And Its Allied Material For 33 Kv Ahmedpora -Beerwah Line (From Khag Tapping Point Village Arwah To Receiving Station Beerwah) Under Capex -Part B. Submission Date for this Tender is 06-01-2024. Conductor Tenders in budgam Jammu And Kashmir. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 02-Jan-2024 | EXTENSION 1 | Date | 06-01-2024 |
Sl. No. | Item Description |
1 | Supply and Erectionof 11mtr Long ST Polewith base plate and top cap (ST-410 SP56 ) including excavation of pit and back filling by boulders upto 1ftas per REC construction Standard |
2 | Providing and fixing of duly fabricatedGI Channel/ V/Pole Top /top Bracket including clamp of sorts as per site requirement |
3 | Providing/Laying,stringing ,tensioning and binding of 0.2 ACSR Conductor (PANTHER) as per REC standards |
4 | Providing and fixing of PG clamps suitable for0.2ACSR as per REC standards |
5 | Supply,installation,testing and commissioning of 33 kV Polymeric composite Pin Insulator(36kV,10kN, LightingImpulse 170KV positive and 180kV negative) of reputed make as per REC standards |
6 | Supply,installation,Testing and commissioning of 33 KVDISC Insulators ( Polymeric ) complete with tension fitting suitable for0.2ACSRof reputed make as per REC standards |
7 | Providing and fixing of GI Nuts & Bolts of sorts as per site requirements |
8 | Providing and fixing of Danger Plates with clamps of standard make |
9 | Providing and fixing of Anti Climbing Devices with clamps of standard make |
10 | Providing and fixing of Earthingof ST poles Complete by GI Pipe40 mm3mtr long throughGI Strip(25x3mm) |
11 | Providing and Paintingof 11 mtr long ST Poles with one coat of red oxide and two coats of aluminum paint to give even shade. |
12 | Providingand laying of Cement bottoming of 11 mtr long ST Poles in mix 1:2:4using 20mm crush stone aggregate including shuttering ,form work etc. as per REC standards 0.6cum /pole |
13 | Providingand fixing of Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete |
14 | Dismantling of existing 0.1ACSRand transportation of the same to divisonal stores (complete job) |
15 | Dismantling of existing channel/V cross arms and transportation of the same to divisonal stores (complete job) |
16 | Dismantling of 33kV Pin insulatorsand transportation of the same to divisonal stores (complete job) |
17 | Dismantling of 33kV Disc insulators wth fittingsand transportation of the same to divisonal stores (complete job) |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy