Tender For Special Repair Of Ac Plant For Missile Shed 3 And 4 At Military Station Kanasar Under Age (I) Kanasar, kanasar-Rajasthan

Military Engineer Services-MES has published Tender For Special Repair Of Ac Plant For Missile Shed 3 And 4 At Military Station Kanasar Under Age (I) Kanasar. Submission Date for this Tender is 13-01-2024. HVAC Tenders in kanasar Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

41134827
Corrigendum : Tender For Special Repair Of Ac Plant For Missile Shed 3 And 4 At Military Station Kanasar Under Age (I) Kanasar
Open Tender
Indian
Rajasthan
kanasar
13-01-2024

Tender Details

Tender For Special Repair Of Ac Plant For Missile Shed 3 And 4 At Military Station Kanasar Under Age (I) Kanasar

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 06-Jan-2024 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 13-01-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 86840.0 /-
Tender Value
INR 43.42 Lakhs /-

BOQ Items

Name of Work : Spl Repair of AC Plant for Missile Shed 3 & 4 at Military Station Kanasar under AGE (I) Kanasar
Sl. No. Item Description
1M&L for including the following works :- (a) Disconnection of defective compressor from base including removing the suction valve, discharge valve / liquid injection line, oil valve, refrigerant piping. (b) Defective compressor - loading / unloading from base to ground and lifting/ shifting/ loading of compressor in vehicle and transportation from site to authorised workshop for repair. (c) After repairing of compressor - collection of compressor, transport to original installed on site. (d) Fixing of compressor on base, fixing of suction valve, discharge valve, NRV, liquid line injection valve, vapor injection valve oil & refrigerant piping connection installation & testing complete all as specified and as directed. (e) Pressure testing, leakage testing in all system and rectification of leakage, if any. (f) Dismantling and removing of chiller, both side end, and MS pipe line and again taking the leak test of the chillers tubes after fixing the cork and repairing of leak tube through dead plug. (g) Taking the hydraulic test of the chiller and taking the leak test after replacing Copper tube all as directed and specified by Engineer-in-Charge. (h) Cleaning / flushing the chillers shell with CTC chemical, cleaning/flushing the condenser shell with CTC chemical, flushing the system of suction, discharge, liquid line, oil separator tank, NRV by using nitrogen and CTC chemical. (j) Vaccumising / dehydration of the system upto 10 days with cold trap/ice/salt complete.
2Description of serial item No. 1.00 contd… (k) Pressure testing in the system, taking/ rectifying the leaks and holding the pressure including of nitrogen gas cylinder, vaccumising the system and holding of 24 Hrs, break the vaccum with R-134 and revaccum the system. (l) Servicing of electrical panel, compressor, contactor, checked and set right, control wiring/inter locking, safety controls complete. (m) Filling the refrigerant gas with R134a upto suitable pressure and testing the chiller to the entire satisfaction of AGE. Note :- Refrigerant gas R134a shall be measured and paid for separately under respective item of Sch "A".
3Supply and fixing in replacement of very efficient copper tubing of length 10.5 feet,16mm dia having pressure bearing capacity 80 Kg/sqcm, ASTM B280 standard or AS1571 standard complete of 80 TR cooling capacity complete all as specified and directed.
4Supply, installation, testing and commissioning of screw type compressors having displacement 471cum per hour, rated speed 2950 RPM & capacity control range 25-100% stepless & semi hermatic flange mounted energy efficient motor with nominal capacity 90 HP operating at frequency 50 Hz, DOL starter, 415 Voltage, F Class motor insulation, Economizer operation, high efficiency screw rotor profile, dual capacity control, durable bearing structure, wide range VI option, build in oil seperator having three stage oil seperation with complete protection & accessories and approved under ISO 9001, ISO 45001 quality system, explosion proof model under ATEX, IECEx, CE conformity & UL listed, approved by chiller performance standard ASHRAE 90.1, EU 2016/2281 with operating charge of both refrigerant R-134a and compressor oil of 100 TR capacity fixed as in repair complete all as specified and directed and also existing make is Hanbell, Model No. RC2-470A VI2.6
5Supply, installation, commissioning and testing of induced draft top discharge counterflow type FRP Cooling Tower (Ractangular) with FRP body and base, water spray headers/cooling tower fills, fan with EFF 1 motor, supporting base frames as per manufacturer"s standard instructions complete all as specified of 100 TR capacity fixed as in repair complete all as specified and directed.
6Supply and fixing in replacement pressure gauge 100mm dia size (0-12 Kg/Sqm) filled with glycerine complete with ball valve of size 3/8" as required for chilled water circuit complete with syphon and fittings complete all as specified and as directed.
7Removing old insulation from chiller machine of 80 TR (Make : Voltas) and making surface preparation after derusting / descaling of complete tank, applying one coat of anti rust enamelled paint on one coat of rust preventive metal primer of complete chiller body and supply and applying XLPE N clad closed cell polyolefin thermal insulation foam self adhesive 40mm thickness having 25 Kg/Cum density, 0.31 W/m-K thermal conductivity, environment freindly, ASTM E 84 and class 0 BS 476 part 6 & 7 approved complete all as specified and directed.
8Supply and fixing in replacement water temperature sensor immersion & thermoelectric type compatible with electronic control motherboard of central AC plant as per existing installed on site complete all as specified and as directed.
9Supply and fixing in replacement High Pressure and Low Pressure transducer with thermoelectric sensor and operating switch as per installed in 80TR chiller unit as per existing installed complete all as specified and as directed.
10M&L for opening up both side top covers of condensor and making its flange spigot leak proof by refacing the spigot (length of spigot should remain same) and also making inner bifurcation flange/plate same as initial to separate out water flow and refitting same as functional complete all as specified and directed.
11Supply and fixing in replacement water flow switch with brass body 1 inch BSP suitable for more than 1000 LPM flow rate along with 220 Volt AC 10 Amp sensor (water/ liquid flow switch) for AC plant complete as per existing installed complete all as specified and as directed.
12Supply and charging of refrigerant R134a including transportation of accessories complete all as specified and as directed.
13Supply and filling screw type compressor oil (refrigerant lubricant) for top up purpose including transportation complete all as specified and as directed.
14Supply assembly and erection of GI sheet of 18 gauge with TDF flange rectangular /square or curvical duct made out of "L" shaped hollow profile or flat sheet, duly factory boxed including all accessories such as corner, cleat, carriage, bolt, gasket and appropriate sealant on longitudinal joints etc complete all as specified and directed.
15M&L in replacement of duct insulation with flexible NBR clad closed cell elastomeric thermal insulation foam self adhesive 32mm thickness having 25 Kg/cum density, 0.031 W/m-K thermal conductivity, environment friendly, ASTM E 84 and class 0 BS 476 part 6 & 7 approved complete all as specified and as directed.
16Supply and fixing in replacement liquid line filter and core drier filter as per installed in 80 TR chiller unit as per existing installed complete all as specified and as directed.
17Supply and fixing in replacement all filter (Either pre fine or fresh air/existing type filter) of AHU (Make : Voltas) capacity 100 TR, 36000 CFM as per installed at site complete all as specified and as directed.
18Supply & installation in replacement of PVC expansion tank with flexible NBR clad closed cell elastomeric thermal insulation foam self adhesive 50mm thickness having 25 Kg/cum density, 0.031 W/m-K thermal conductivity, environment freindly, ASTM E 84 and Class 0 BS 476 part 6 & 7 approved of capacity 2000 litres complete all as specified and as directed.
19M&L in replacement XLPE N clad closed cell polylefin thermal insulation foam self adhesive 25mm thickness having 25 Kg/cum density, 0.031 W/m-K thermal conductivity, environment friendly, ASTM E 84 and Class 0 BS 476 part 6 & 7 approved for applying on compressor, chiller pump & valve etc complete all as specified and directed.
20M&L in replacement MS pipe 150mm bore Heavy Class "C" (ISI marked),insulated with XLPE N clad closed cell polylefin thermal insulation foam self adhesive 25mm thickness having 25 Kg/cum density, 0.031 W/m-K thermal conductivity, environment friendly, ASTM E 84 and Class 0 BS 476 part 6 & 7 approved complete all as specified and as directed. Note :- Flange, gasket, nut, bolts & washers shall be deemed to be included in the qouted rates.
21M&L in replacement MS pipe 100mm bore Heavy Class "C" (ISI marked),insulated with XLPE N clad closed cell polylefin thermal insulation foam self adhesive 25mm thickness having 25 Kg/cum density, 0.031 W/m-K thermal conductivity, environment friendly, ASTM E 84 and Class 0 BS 476 part 6 & 7 approved complete all as specified and as directed. Note :- Flange, gasket, nut, bolts & washers shall be deemed to be included in the qouted rates.
22M&L in replacement MS pipe 80mm bore Heavy Class "C" (ISI marked),insulated with XLPE N clad closed cell polylefin thermal insulation foam self adhesive 25mm thickness having 25 Kg/cum density, 0.031 W/m-K thermal conductivity, environment friendly, ASTM E 84 and Class 0 BS 476 part 6 & 7 approved complete all as specified and as directed. Note :- Flange, gasket, nut, bolts & washers shall be deemed to be included in the qouted rates.
23Supply, installation, testing and commissioning of mercury in glass type thermometers filled with glycerine as required for the Chilled / Hot water circuit with syphon and fittings complete all as specified and directed.
24Supply and fixing Cast Iron butterfly valve of size 80mm dia, Class PN 1.6, stainless steel disc, wafer type, lever operated, ISI marked, with flanges, nuts, bolts, gasket and washers, suitable for flanged pipe connection including taking down existing unserviceable valve, complete all as specified and as directed.
25Supply and fixing Cast Iron butterfly valve of size 100mm dia, Class PN 1.6, stainless steel disc, wafer type, lever operated, ISI marked, with flanges, nuts, bolts, gasket and washers, suitable for flanged pipe connection including taking down existing unserviceable valve, complete all as specified and as directed.
26Supply and fixing Check Valve of size 80mm bore, cast iron body, (ISI marked), heavy duty, class ‘PN-1.6’, gun metal seat, both ends flanged and drilled, including nuts, bolts, washer and neoprene rubber gasket joint complete all as specified and as directed including dismantling & taking out old unserviceable non return valve of 80mm bore.
27S&F cast iron "Y" strainer with SS-304 grade screen of size 125mm bore, pressure rating PN 1.6, fixed in between MS flanged pipe, fixed in repairs, complete all as specified and as directed.
28S&F cast iron "Y" strainer with SS-304 grade screen of size 80mm bore, pressure rating PN 1.6, fixed in between MS flanged pipe, fixed in repairs, complete all as specified and as directed.
29S&F in replacement Pot strainer 150mm bore, pressure rating PN 1.6, fixed complete all as specified and as directed.
30S&F in replacement 2 way pressure independent balancing cum control valve 100mm bore in a single body pressure rating PN-1.6 complete all as specified and as directed.
31Supply, installation, testing and commissioning of 20mm dia ball valves for drain with complete fitting etc fixed in replacement complete all as specified and directed.
32Supply, installation, testing and commissioning of 25mm dia ball valves for drain with complete fitting etc fixed in replacement complete all as specified and directed.
33Supply, installation, testing and commissioning of 50mm dia ball valves for drain with complete fitting etc fixed in replacement complete all as specified and directed.
34Supply, installation, testing and commissioning of Air Vents 50mm dia fixed in replacement complete all as specified and directed.