Tender For Repair Maintenance Of Ht Distribution System And Allied Works At Khunmoh Grn Under Ge 861 Ews, Srinagar-Jammu And Kashmir

Military Engineer Services-MES has published Tender For Repair Maintenance Of Ht Distribution System And Allied Works At Khunmoh Grn Under Ge 861 Ews. Submission Date for this Tender is 01-01-2024. Insulators Tenders in Srinagar Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

40930873
Corrigendum : Tender For Repair Maintenance Of Ht Distribution System And Allied Works At Khunmoh Grn Under Ge 861 Ews
Open Tender
Indian
Jammu And Kashmir
Srinagar
01-01-2024

Tender Details

Tender For Repair Maintenance Of Ht Distribution System And Allied Works At Khunmoh Grn Under Ge 861 Ews; 1 Excavation In Trenches, Not Exc 1.5 Mtr Wide And Not Exc 1.5 Mtr In Depth For Foundation, Laying Of Cables, Erection Of Poles, Stays Etc. And Getting Out In Soft / Loose Soil, Complete All As Specified And Directed. 2 Excavation In Trenches, Not Exc 1.5 Mtr Wide And Exc 1.5 Mtr But Not Exc 3.0 Mtr In Depth For Foundation, Erection Of Poles, Stays Etc. And Getting Out In Soft / Loose Soil, Complete All As Specified And Directed. 3 Removing Excavated Soil To A Distance Not Exc 50 Mtr And Depositing Where Directed At A Level Not Exc 1.5 Mtr Above The Starting Point, Complete All As Specified And Directed. 4 Returning, Filling In Trenches Including Spreading, Leveling, Watering And Well Ramming In Layers Not Exc 25Cm Thick, Complete All As Specified And Directed. 5 M&L For Dry River Sand, Laid In Trenches For Cable Protection, As 15Cm Thick Below The Cable And 8Cm Thick Above The Cable, Complete All As Specified And Directed.Note :- Punned Thickness Of Sand Shall Be Measured And Paid. 6 Supplying And Laying Reinforced Precast Concrete Cable Cover, Class Hv, Type-2, Flat, Of Size 450X180x40mm, Complete All As Specified And Directed. 7 M&L For Plain Cement Concrete 1:4:8, Type D-2 ( Using 40Mm Graded Crushed Stone Aggregates ) As In Foundation, Filling In And Mass Concrete Etc., Complete All As Specified And Directed. 8 M&L For Plain Cement Concrete 1:3:6, Type C-2 ( Using 40Mm Graded Crushed Stone Aggregates ) As In Foundation, Filling In And Mass Concrete Etc, Complete All As Specified And Directed. 9 M&L For Plain Cement Concrete 1:2:4, Type B-1 ( Using 20Mm Graded Crushed Stone Aggregates ) As In Stay Filling Or Pole, Coping Etc. Including Necessary Form Work, Complete All Specified And Directed. 10 Supply, Laying, Commissioning & Testing Xlpe Insulated, Screened, Pvc Bedded, Galvanised Steel Strip Or Wire Armoured, Electric Power Cable ( Heavy Duty ) With Aluminium Conductor, 11000 Volts Grade, Cross Sectional Area 95 Sqmm 3 Core And Including Taking Up / Down Existing Unsv Cable, Complete All As Specified And Directed. 11 Supply, Laying, Commissioning & Testing Xlpe Insulated, Screened, Pvc Bedded, Galvanised Steel Strip Or Wire Armoured, Electric Power Cable ( Heavy Duty ) With Aluminium Conductor, 11000 Volts Grade, Cross Sectional Area 70 Sqmm 3 Core And Including Taking Up / Down Existing Unsv Cable, Complete All As Specified And Directed. 12 Supply, Installation And Erection In Vertical Position Steel Tubular Swaged Poles, Type 410, Sp-55 ( 11 Meters Long ) With 300X300x6mm Thick Mild Steel Base Plate Continuously Welded To Pole, Ms Plate 3Mm Thick Finial Taper Plug Bolt, Nuts And Screws All As Specified Including Factory Painted With Two Coats Of Black Bituminous Paint Internally Throughout And Externally For Embedded Portion And Applying Two Coats Of Aluminium Paint Over A Coat Of Red Oxide Primer On Remaining Exposed Surfaces And Making Alternate Black And White Strips 30Cm High With Super Enameled Paint Over A Coat Of Red Oxide Primer Upto 1.5 Mtrs Height From Ground Level / Coping After Erecting, Complete All As Specified And Directed. Note :-Excavation, Pcc For Foundation And Earth Work Shall Be Measured And Paid Separately Under Respective Items Of This Boq. 13 S&F In Replacement Cable Jointing Kit For 11 Kv ( Earthed ) Grade Cable For Straight Through Heat Shrink Type Joint Complete With Jointing Material And Accessories, Suitable For 3 Core Xlpe Armoured Aluminium Conductor Cable Of Size 70 To 95 Sqmm, Complete All As Specified And Directed. 14 S&F In Replacement Cable Jointing Kit For 11 Kv / 6.6 Kv Grade Cable For Indoor Termination Heat Shrink Type Joint, Complete With Jointing Material And Accessories, Suitable For Size 3 Core Xlpe Armoured Aluminium Conductor Cable Of Size 70 To 95 Sqmm, Complete All As Specified And Directed. 15 S&F In Replacement Cable Jointing Kit For 11 Kv / 6.6 Kv Grade Cable For Outdoor Termination Heat Shrink Type Joint, Complete With Jointing Material And Accessories, Suitable For Size 3 Core Xlpe Armoured Aluminium Conductor Cable Of Size 70 To 95 Sqmm, Complete All As Specified And Directed. 16 Supplying, Fixing And Testing Gang Operated Air Breaker Switch, Triple Pole, Mechanically Operated Mounted On Insulators And Steel Frame With Operating Mechanism Worked From Ground Level Using Heavy Duty Gi Pipe For Current Rating 200 Amps, Outdoor Type ( Confirming To Latest Is Specifications ) , Ht 11 Kv, Tripple Pole With Fixed Contacts Of Phosphorous And Bronze And A Set Of Drop Out Ht Fuse Assembly, Fuse Carrier Fitting, 12 Insulator Type Mounted On Ms Channel Operating Rod With Pad Lock Arrangement Including Dismantling Old One, Complete All As Specified And Directed. 17 M&L For Repairs / Replacement Mild Steel Cross Arms, Bracings, Supports, Clamps And Back Plates, Fabricated From Structural Steel Sections Including Nuts, Bolts, Washers, Welding, Bending Cold Or Hot, Drilling Holes For Bolts, In Any Shape Or Size As Indicated Or Directed And Inclusive Two Coat Of Synthetic Enamel Paint Over One Coat Of Red Oxide Zinc Chrome Primer After Preparation Of Surface, Complete All As Specified And Directed. 18 S&F In Replacement Lightning Arrestor, Gapless Metal Oxide Type Complete With All Fittings, Suitable For A System Voltage Of 11 Kv And Of Class 10 Ka, Complete All As Specified And Directed. 19 S&F In Replacement Danger Notice Plate, Made Out Of 1.6Mm Thick Mild Steel Sheet, Vitreous Enameled White With Letters, Figures And Conventional Skull And Bones In Signal Red Colour And Fixed With Ms Clamps, Bolts And Nuts Of Approved Size, For Ht Of Size 25X20cm, Complete All As Specified And Directed. 20 S&F Expulsion Type Drop Out Fuse With All Accessories And Contact Insulator Etc., Fixed On Ht Pole Rating Above 10 And Upto 25 Amps, Suitable For 11 Kv 3 Pole With Two Nos Insulators Per Pole Including Dismantling Old Unserviceable One, Complete All As Specified And Directed. 21 S&F Post Type Insulator With All Accessories And Contact Insulators Etc., Fixed On Ht Pole Channel With God Or Other Rating Above 10 And Upto 25 Amps, Suitable For 11 Kv Grade Including Taking Down Old Unserviceable Insulator, Complete All As Specified And Directed. 22 M&L For Replacement Stay Assembly Complete With 20Mm Dia Stay Rod With Accessories Shown In Electric Plate No. 01 Including Stay Clamps, Complete All As Specified And Directed.Note :- Loop Insulator, Stay Wire, Excavation And Concrete Work Shall Be Measured And Paid Seperately Under Respective Items Of Boq. 23 Taking Down And Reinstall Transformer Step Down 11 Kva 415 Volts Complete, Outdoor / Indoor Type Of Capacity Upto 300 Kva Including Transportation To The Workshop And Back To Site, Complete All As Specified And Directed. 24 M&L For Strip Opening Of Transformer And Removing The Top Cover For Inspection, Draining The Transformer Oil And Taking Out The Core Along With Ht / Lt Coil ( Windings ) Assembling The Core After Replacement Of Ht / Lt Coils Heating Varnishing, Testing And Housing Accessories In Transformer Body And Connection Up, Filling In Dehydrated New Transformer Oil And Connection With Existing Electrical System Ht / Lt And Commissioning, Complete On Load Of Capacity Not Exceeding 160 Kva, Complete All As Specified And Directed.Note :- Transformer Oil Shall Be Measured And Paid Separately Under Relevant Item Of This Boq. 25 All As Per Srl Item No. 24.00 Here-In-Above But On Load Of Capacity Above 160 Kva And Upto 300 Kva. 26 M&L For Winding Of Ht / Lt Coil Of Different Type, Capacity And Make Of Transformer With Approved Quality Supper Enameled Copper Wire / Strips Of Suitable Gauge And Number Of Turns Along With Allied Materials Such As Cork Sheet, Fiber Glass Insulations, Paper Insulations, Cotton / Empire Tap And Tube Wooden Blocks Bolts, Nuts And Washer ( Brass ) Soldering And Other Packing Material Etc. As Required, Complete All As Specified And Directed. 27 Disconnecting Ht / Lt Side Electrical Connection Carefully Existing11 Kv 440 Volts Stepdown Transformer Of Any Capacity, Draining Out Of Existing Transformer Oil After Filtration, Dehydration And Measuring The Die-Electric Strength Not Less Than 40 Kv At 2Mm Gap Including Re-Installation Of Transformer Satisfactory On Its Original Position, Connecting, Testing And Commissioning, Complete All As Specified And Directed. 28 Supply And Filling Transformer Power Oil Of Bdv Not Less Than 45 Kva For Topping Up Reduced Level Due To Evaporation / Leakage / Loss Due To Dehydration In Ht Transformer, Complete All Specified And Directed. 29 S&F In Replacement Ht Bushes Porcelain, Vitreous With Brass Spindle, Threaded With Washer, Nuts, Lock And Rubber Seal, Suitable For Transformer Of Capacity Upto 160 Kva, Complete All As Specified And Directed. 30 S&F In Replacement Ht Bushes Porcelain, Vitreous With Brass Spindle, Threaded With Washer, Nuts, Lock And Rubber Seal, Suitable For Transformer Of Capacity Exc 160 Kva But Not Exc 300 Kva, Complete All As Specified And Directed. 31 S&F In Replacement Lt Bushes Porcelain, Vitreous With Brass Spindle, Threaded With Washer, Nuts, Lock And Rubber Seal, Suitable For Transformer Of Capacity Upto 160 Kva, Complete All As Specified And Directed. 32 S&F In Replacement Lt Bushes Porcelain, Vitreous With Brass Spindle, Threaded With Washer, Nuts, Lock And Rubber Seal, Suitable For Transformer Of Capacity Exc 160 Kva But Not Exc 300 Kva, Complete All As Specified And Directed. 33 S&F In Replacement Breather Assembly Cast Iron Body Of Standard Size, Filled With Silica Gel Of Transformer Of Capacity Upto 300 Kva Complete With Nuts, Bolts And Washers, Complete All As Specified And Directed. 34 M&L For Replacement Gi Tubing Light Grade 80Mm Bore With All Fittings, Laid In Trenches Or Fixed To Walls / Alongwith Pole With Suitable Ms Clamps, Complete For Protection Of Electric Cable, Complete All As Specified And Directed. 35 M&L For Earthing Complete With Galvanised Steel Earth Plate Electrode Of Size 600X600x6mm Thick, Burried Directly In Ground, Earth Pit Not Less Than 2.25 Mtr Deep Below Normal Ground Level With Top Edge Of Earth Plate Not Less Than 1.5 Mtr Below Normal Ground Level, Connected To The Galvanised Iron Wire Of 4Mm Dia By Means Of Bolts, Nuts, Check Nuts And Washers Of Galvanised Iron, Protected By Gi Tube Light Grade 15Mm Bore Including Provision Of Concrete Pit In Pcc 1:2:4 Type B-1 ( Using 20Mm Graded Stone Aggregates ) With 40Mm Thick Rcc 1:2:4 Cover, Reinforced With Xpm Weight Not Less Than 4 Kg / Sqm And 6Mm Dia Round Bar Handle, Excavation And Earth Work In Any Type Of Soil, Charcoal Dust And Salt And 20Mm Bore Gi Watering Pipe Light Grade With Funnel And Wire Mesh Including Dismantling Old Unsv Earthing And Removal Thereof, Complete All As Specified And Directed By Engr-In-Charge. Notes :- ( I ) Main Earthing Strip From Earth Plate Electrode To Test Point Up To Length Of 7.5 Meters Length Shalldeem To Be Included In Quoted Rates. ( Ii ) On Testing After Completion If The Desired Resistenance Is Not Obtained The Contractor Shall Redo The Earthing Without Any Extra Cost To The Department . 36 M&L For Earthingcomplete With Galvanised Steel Earth Plate Electrode Of Size 600X600x6mm Thick, Burried Directly In Ground, Earth Pit Not Less Than 2.25 Mtr Deep Below Normal Ground Level With Top Edge Of Earth Plate Not Less Than 1.5 Mtr Below Normal Ground Level, Connected To The Galvanised Iron Strip Of Size 32X6mm By Means Of Bolts, Nuts, Check Nuts And Washers Of Galvanised Iron, Protected By Gi Tube Light Grade 40Mm Boreincluding Provision Of Concrete Pit In Pcc 1:2:4 Type B-1 ( Using 20Mm Graded Stone Aggregates ) With 40Mm Thick Rcc 1:2:4 Cover, Reinforced With Xpm Weight Not Less Than 4 Kg / Sqm And 6Mm Dia Round Bar Handle, Excavation And Earth Work In Any Type Of Soil, Charcoal Dust And Salt And 20Mm Bore Gi Watering Pipe Light Grade With Funnel And Wire Mesh Including Dismantling Old Unsv Earthing And Removal Thereof, Complete All As Specified And Directed. Notes :- ( I ) Main Earthing Strip From Earth Plate Electrode To Test Point Up To Length Of 7.5 Meters Length Shall Deemed To Be Include In Quoted Rates. ( Ii ) On Testing After Completion If The Desired Resistenance Is Not Obtained The Contractor Shall Redo The Earthing Without Any Extra Cost To The Department . 37 M&L In Replacement For Ht Cable Route Indicator, Made Out Of Gi Plate 3Mm Thick And 6 Inches Dia Duly Marked With Working Voltage And Route Indicator, Fixed With Angle Iron Of Size 25X25x3mm Thick, 50Cm Long, Embedded In Pcc 1:2:4 Type B-1, Of Size 20X20x20cm In Ground, Complete All As Specified And Directed. 38 S&F In Replacement Epoxy Resin Cast Ct For Ht Metering Side, Dual Core Of Ratio As Per Existing Accuracy Class 0.55, Burden 15 / 5 A / 7.5 Va For 11 Kv, Complete All As Specified And Directed. 39 S&F In Replacement Epoxy Resin Cast Pt For Ht Metering Side, Dual Core Of Ratio As Per Existing Accuracy Class 0.55, Ratio 11 Kv / 110V, Burden 50 Va For 11 Kv, Complete All As Specified And Directed. 40 S&F In Replacement Galvanised Iron Strip Of Size 32Mm X 6Mm, Burried In Ground Upto 50Cm Depth Or Fixed To Wall With Insulators Etc. For Loop Earthing Including Welding For Joints, Complete All As Specified And Directed.Note :- Earth Work Will Be Measured And Paid Separately Under Relevent Items Of This Boq. 41 M&L For Preparation Of Old Painted Surfaces, Removing Dust And Other Deposited Materials On Ht Tubular Pole Of 11 Mtr Long By Scraping And Applying One Coat Of Synthetic Enamel Paint Up To 1 Mtr From Bottom And Painting The Rest Of The Pole Including Cross Arms, Clamps Etc, Complete All As Specified And Directed. Note :- Colour And Pattern Of The Paint Shall Be Decided By Engr-In-Charge. 42 Taking Out From Trenches Or Taking Down From Poles / Walls Of Ht Ug Cables Of Any Size, Pvc Insulated Sheathed With Multistranded Aluminium Conductor Armoured And Relaying / Re-Fixing In Same Location & Position After Fault Rectification Withtesting, Complete All As Specified And Directed. 43 M&L For Scraping Old Paint With Sand Paper And Preparation Of Surfaces Of Transformer Of Any Capacity, Outdoor / Indoor Type And Applying Two Coats Of Smoke Grey Synthetic Enamel Paint By Spray Machine Complete And Including Making Good Condition Of Name Plate And Writting Mes / Sm Number With The Letters 100Mm Height With Systhetic Enamel Paint, Complete All As Specified And Directed. 44 Arrangement Of Standby Transformer, Copper Winding Upto 250 Kva During The Breakdown / Servicing Of Any Existing Transformer Including Transportation, Machinery, Installation And Taking Down Existing Transformer At Any Location As Directed By Eic, Complete All As Specified And Directed. 45 Notes :-An Amount Of Rs. 62, 625.00 On Account Of Credit Schedule For Schedule A Part-Ii Shall Be Deducted From Total Quoted Amount Of Boq To Arrive At The Contract Sum.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 25-Dec-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 01-01-2024
2 26-Dec-2023 Amendment Other 01-01-2024

Key Value

Document Fees
INR 500 /-
EMD
INR 28500.0 /-
Tender Value
INR 14.25 Lakhs /-

BOQ Items

Name of Work : REPAIR / MAINT OF HT DISTRIBUTION SYSTEM AND ALLIED WORKS AT KHREUH AND SHER-E-SHALI GRN UNDER GE 861 EWS.
Sl. No. Item Description
1Excavation in trenches, not exc 1.5 mtr wide and not exc 1.5 mtr in depth for foundation, laying of cables, erection of poles, stays etc. and getting out in soft/ loose soil, complete all as specified and directed.
2Excavation in trenches, not exc 1.5 mtr wide and exc 1.5 mtr but not exc 3.0 mtr in depth for foundation, erection of poles, stays etc. and getting out in soft/ loose soil, complete all as specified and directed.
3Removing excavated soil to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point, complete all as specified and directed.
4Returning, filling in trenches including spreading, leveling, watering and well ramming in layers not exc 25cm thick, complete all as specified and directed.
5M&L for dry river sand, laid in trenches for cable protection, as 15cm thick below the cable and 8cm thick above the cable, complete all as specified and directed. Note :- Punned thickness of sand shall be measured and paid.
6Supplying and Laying reinforced precast concrete cable cover, class HV, type-2, flat, of size 450x180x40mm, complete all as specified and directed.
7M&L for plain cement concrete 1:4:8, type D-2 (using 40mm graded crushed stone aggregates) as in foundation, filling in and mass concrete etc., complete all as specified and directed.
8M&L for plain cement concrete 1:3:6, type C-2 (using 40mm graded crushed stone aggregates) as in foundation, filling in and mass concrete etc, complete all as specified and directed.
9M&L for plain cement concrete 1:2:4, type B-1 (using 20mm graded crushed stone aggregates) as in stay filling or pole, coping etc. including necessary form work, complete all specified and directed.
10Supply, laying, commissioning & testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 11000 volts grade, cross sectional area 95 Sqmm 3 Core and including taking up/ down existing unsv cable, complete all as specified and directed.
11Supply, laying, commissioning & testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 11000 volts grade, cross sectional area 70 Sqmm 3 Core and including taking up/ down existing unsv cable, complete all as specified and directed.
12Supply, installation and erection in vertical position steel tubular swaged poles, type 410, SP-55 (11 meters long) with 300x300x6mm thick mild steel base plate continuously welded to pole, MS plate 3mm thick finial taper plug bolt, nuts and screws all as specified including factory painted with two coats of black bituminous paint internally throughout and externally for embedded portion and applying two coats of aluminium paint over a coat of red oxide primer on remaining exposed surfaces and making alternate black and white strips 30cm high with super enameled paint over a coat of red oxide primer upto 1.5 mtrs height from ground level/ coping after erecting, complete all as specified and directed. Note :-Excavation, PCC for foundation and earth work shall be measured and paid separately under respective items of this BOQ.
13S&F in replacement cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories, suitable for 3 Core XLPE armoured aluminium conductor cable of size 70 to 95 Sqmm, complete all as specified and directed.
14S&F in replacement cable jointing kit for 11 KV / 6.6 KV grade cable for indoor termination heat shrink type joint, complete with jointing material and accessories, suitable for size 3 Core XLPE armoured aluminium conductor cable of size 70 to 95 Sqmm, complete all as specified and directed.
15S&F in replacement cable jointing kit for 11 KV / 6.6 KV grade cable for outdoor termination heat shrink type joint, complete with jointing material and accessories, suitable for size 3 Core XLPE armoured aluminium conductor cable of size 70 to 95 Sqmm, complete all as specified and directed.
16Supplying, fixing and testing gang operated air breaker switch, triple pole, mechanically operated mounted on insulators and steel frame with operating mechanism worked from ground level using heavy duty GI pipe for current rating 200 Amps, outdoor type (confirming to latest IS specifications), HT 11 KV, tripple pole with fixed contacts of phosphorous and bronze and a set of drop out HT fuse assembly, fuse carrier fitting, 12 insulator type mounted on MS channel operating rod with pad lock arrangement including dismantling old one, complete all as specified and directed.
17M&L for repairs/ replacement mild steel cross arms, bracings, supports, clamps and back plates, fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive two coat of synthetic enamel paint over one coat of red oxide zinc chrome primer after preparation of surface, complete all as specified and directed.
18S&F in replacement lightning arrestor, gapless metal oxide type complete with all fittings, suitable for a system voltage of 11 KV and of class 10 KA, complete all as specified and directed.
19S&F in replacement danger notice plate, made out of 1.6mm thick mild steel sheet, vitreous enameled white with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size, for HT of size 25x20cm, complete all as specified and directed.
20S&F expulsion type drop out fuse with all accessories and contact insulator etc., fixed on HT pole rating above 10 and upto 25 Amps, suitable for 11 KV 3 Pole with two Nos insulators per pole including dismantling old unserviceable one, complete all as specified and directed.
21S&F post type insulator with all accessories and contact insulators etc., fixed on HT pole channel with GOD or other rating above 10 and upto 25 Amps, suitable for 11 KV grade including taking down old unserviceable insulator, complete all as specified and directed.
22M&L for replacement stay assembly complete with 20mm dia stay rod with accessories shown in electric plate No. 01 including stay clamps, complete all as specified and directed. Note :- Loop insulator, stay wire, excavation and concrete work shall be measured and paid seperately under respective items of BOQ.
23Taking down and reinstall transformer step down 11 KVA 415 Volts complete, outdoor/ indoor type of capacity upto 300 KVA including transportation to the workshop and back to site, complete all as specified and directed.
24M&L for strip opening of transformer and removing the top cover for inspection, draining the transformer oil and taking out the core along with HT/ LT coil (windings) assembling the core after replacement of HT/ LT coils heating varnishing, testing and housing accessories in transformer body and connection up, filling in dehydrated new transformer oil and connection with existing electrical system HT/ LT and commissioning, complete on load of capacity not exceeding 160 KVA, complete all as specified and directed. Note :- Transformer oil shall be measured and paid separately under relevant item of this BOQ.
25All as per Srl item No. 24.00 here-in-above but on load of capacity above 160 KVA and upto 300 KVA.
26M&L for winding of HT / LT coil of different type, capacity and make of transformer with approved quality supper enameled copper wire/ strips of suitable gauge and number of turns along with allied materials such as cork sheet, fiber glass insulations, paper insulations, cotton/ empire tap and tube wooden blocks bolts, nuts and washer (brass) soldering and other packing material etc. as required, complete all as specified and directed.
27Disconnecting HT/ LT side electrical connection carefully existing11 KV 440 Volts stepdown transformer of any capacity, draining out of existing transformer oil after filtration, dehydration and measuring the die-electric strength not less than 40 KV at 2mm gap including re-installation of transformer satisfactory on its original position, connecting, testing and commissioning, complete all as specified and directed.
28Supply and filling transformer power oil of BDV not less than 45 KVA for topping up reduced level due to evaporation/ leakage/ loss due to dehydration in HT transformer, complete all specified and directed.
29S&F in replacement HT bushes porcelain, vitreous with brass spindle, threaded with washer, nuts, lock and rubber seal, suitable for transformer of capacity upto 160 KVA, complete all as specified and directed.
30S&F in replacement HT bushes porcelain, vitreous with brass spindle, threaded with washer, nuts, lock and rubber seal, suitable for transformer of capacity exc 160 KVA but not exc 300 KVA, complete all as specified and directed.
31S&F in replacement LT bushes porcelain, vitreous with brass spindle, threaded with washer, nuts, lock and rubber seal, suitable for transformer of capacity upto 160 KVA, complete all as specified and directed.
32S&F in replacement LT bushes porcelain, vitreous with brass spindle, threaded with washer, nuts, lock and rubber seal, suitable for transformer of capacity exc 160 KVA but not exc 300 KVA, complete all as specified and directed.
33S&F in replacement breather assembly cast iron body of standard size, filled with silica gel of transformer of capacity upto 300 KVA complete with nuts, bolts and washers, complete all as specified and directed.
34M&L for replacement GI tubing light grade 80mm bore with all fittings, laid in trenches or fixed to walls/ alongwith pole with suitable MS clamps, complete for protection of electric cable, complete all as specified and directed.
35M&L for earthing complete with galvanised steel earth plate electrode of size 600x600x6mm thick, burried directly in ground, earth pit not less than 2.25 mtr deep below normal ground level with top edge of earth plate not less than 1.5 mtr below normal ground level, connected to the galvanised iron wire of 4mm dia by means of bolts, nuts, check nuts and washers of galvanised iron, protected by GI tube light grade 15mm bore including provision of concrete pit in PCC 1:2:4 type B-1 (using 20mm graded stone aggregates) with 40mm thick RCC 1:2:4 cover, reinforced with XPM weight not less than 4 Kg /Sqm and 6mm dia round bar handle, excavation and earth work in any type of soil, charcoal dust and salt and 20mm bore GI watering pipe light grade with funnel and wire mesh including dismantling old UNSV earthing and removal thereof, complete all as specified and directed by Engr-in-Charge. Notes :- (i) Main earthing strip from earth plate electrode to test point up to length of 7.5 meters length shalldeem to be included in quoted rates. (ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department .
36M&L for earthingcomplete with galvanised steel earth plate electrode of size 600x600x6mm thick, burried directly in ground, earth pit not less than 2.25 mtr deep below normal ground level with top edge of earth plate not less than 1.5 mtr below normal ground level, connected to the galvanised iron strip of size 32x6mm by means of bolts, nuts, check nuts and washers of galvanised iron, protected by GI tube light grade 40mm boreincluding provision of concrete pit in PCC 1:2:4 type B-1 (using 20mm graded stone aggregates) with 40mm thick RCC 1:2:4 cover, reinforced with XPM weight not less than 4 Kg /Sqm and 6mm dia round bar handle, excavation and earth work in any type of soil, charcoal dust and salt and 20mm bore GI watering pipe light grade with funnel and wire mesh including dismantling old UNSV earthing and removal thereof, complete all as specified and directed. Notes :- (i) Main earthing strip from earth plate electrode to test point up to length of 7.5 meters length shall deemed to be include in quoted rates. (ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department .
37M&L in replacement for HT cable route indicator, made out of GI plate 3mm thick and 6 inches dia duly marked with working voltage and route indicator, fixed with angle iron of size 25x25x3mm thick, 50cm long, embedded in PCC 1:2:4 type B-1, of size 20x20x20cm in ground, complete all as specified and directed.
38S&F in replacement epoxy resin cast CT for HT metering side, dual core of ratio as per existing accuracy class 0.55, burden 15/5 A / 7.5 VA for 11 KV, complete all as specified and directed.
39S&F in replacement epoxy resin cast PT for HT metering side, dual core of ratio as per existing accuracy class 0.55, ratio 11 KV / 110V, burden 50 VA for 11 KV, complete all as specified and directed.
40S&F in replacement galvanised iron strip of size 32mm x 6mm, burried in ground upto 50cm depth or fixed to wall with insulators etc. for loop earthing including welding for joints, complete all as specified and directed. Note :- Earth work will be measured and paid separately under relevent items of this BOQ.
41M&L for preparation of old painted surfaces, removing dust and other deposited materials on HT tubular pole of 11 Mtr long by scraping and applying one coat of synthetic enamel paint up to 1 Mtr from bottom and painting the rest of the pole including cross arms, clamps etc, complete all as specified and directed. Note :- Colour and pattern of the paint shall be decided by Engr-in-Charge.
42Taking out from trenches or taking down from poles/ walls of HT UG cables of any size, PVC insulated sheathed with multistranded aluminium conductor armoured and relaying/ re-fixing in same location & position after fault rectification withtesting, complete all as specified and directed.
43M&L for scraping old paint with sand paper and preparation of surfaces of transformer of any capacity, outdoor/ indoor type and applying two coats of smoke grey synthetic enamel paint by spray machine complete and including making good condition of name plate and writting MES/SM number with the letters 100mm height with systhetic enamel paint, complete all as specified and directed.
44Arrangement of standby transformer, copper winding upto 250 KVA during the breakdown / servicing of any existing transformer including transportation, machinery, installation and taking down existing transformer at any location as directed by EIC, complete all as specified and directed.
45Notes :- An amount of Rs. 62,625.00 on account of Credit Schedule for Schedule "A" Part-II shall be deducted from total quoted amount of BOQ to arrive at the contract sum.