Tender For Provision Of Storage Shed Including Central Ac Plant And Other Services At Kandrori Under Ge (South) Pathankot, pathankot-Punjab

Military Engineer Services-MES has published Tender For Provision Of Storage Shed Including Central Ac Plant And Other Services At Kandrori Under Ge (South) Pathankot. Submission Date for this Tender is 14-12-2023. Shed Construction Tenders in pathankot Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

40588574
Corrigendum : Tender For Provision Of Storage Shed Including Central Ac Plant And Other Services At Kandrori Under Ge (South) Pathankot
Open Tender
Indian
Punjab
pathankot
14-12-2023

Tender Details

Tender For Provision Of Storage Shed Including Central Ac Plant And Other Services At Kandrori Under Ge ( South ) Pathankot

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 24-Nov-2023 corrigendum2 Other 07-12-2023
2 24-Nov-2023 corrigendum1 Date 07-12-2023
3 24-Nov-2023 corrigendum3 BOQ 07-12-2023
4 07-Dec-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 14-12-2023

Key Value

Document Fees
INR 2000 /-
EMD
INR 542000.0 /-
Tender Value
INR 4.67 Crore /-

BOQ Items

Name of Work:PROVN OF STORAGE SHED INCLUDING CENTRAL AC PLANT AND OTHER SERVICES AT KANDRORI UNDER GE (SOUTH) PATHANKOT
Sl. No. Item Description
1Lumpsum price worked out by the contractor for Buldings works as listed in Schedule "A" Part-I.
2Lumpsum price worked out by the contractor for Site clearance works as listed in Schedule "A" Part-II.
3Lumpsum price worked out by the contractor for Plumbing Works as listed in Schedule "A" Part-III.
4Lumpsum price worked out by the contractor for InternalElectrification Works as listed in Schedule "A" Part-IV.
5Lumpsum price worked out by the contractor for Internal WaterSupply Works as listed in Schedule "A" Part-V.
6Lumpsum price worked out by the contractor for Road, Path & Culvert as listed in Schedule "A" Part-VI.
7Lumpsum price worked out by the contractor for Sewage Disposal works as listed in Schedule "A" Part-VII.
8Lumpsum price worked out by the contractor for Area Drainage works as listed in Schedule "A" Part-VIII.
9Lumpsum price worked out by the contractor for Security Wall & Gate Works as listed in Schedule "A"Part-IX.
10Lumpsum price worked out by the contractor for External water supply as listed in Schedule "A" Part-X.
11Lumpsum price worked out by the contractor for Lightening Protection Works as listed in Schedule "A" Part-XI.
12Lumpsum price worked out by the contractor for External Electrification as listed in Schedule "A" Part-XII.
13M&L for construction of septic tank for 25 users (Brick construction with fly ash bricks), complete all as specified and as shown on drgs
14M&L for construction of soakage well, excavation in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonary with top ring of M-25 (Design mix) concrete including intercepting chamber and screen chamber made of brick masonary in CM, RCC cover slab in M25/SFRC cover, interconnecting pipes of RCC/DWCcomplete filled with brick bats of size 2.14 M dia X 3.0 M effective depth complete all as specified and directed.
15Supply, install, testing and commissioning Automatic power factor coorection (APFC) Panel outdoor type (double door) for 3 Phase 415 V & 50 Hz system with MD-SL capacitor of capacity 50 (20x1+10x2+5x2) KVAR and with sutable rated TPN MCCB of 25/35 KA rupturing capacities dyly controlled by auto and manual option with free standing configuration relay, auxilliary contracts, CTS, indicator lamps etc and necessary wiring complete and meter eqpt including necessary PCC 1:3:6 type C2 using 40mm graded aggregate foundation for fixing/installed the panel on floor etc complete alongwith:- (a) Power factor meter-01 No (b)Ammeter-01 No, Volt meter 0-500V-01 No (c) APFC relay with suitable stage with selector switch, including provn of suitable rated CTs in main incoming panels & control wiring/flexible copper conductor cable for connecting APFC panel to main incoming panel etc complete all as specified and directed.
16Construction of Steel Gate (5.50 x 2.40 m) with RCC Pillars as specified & as shown on drgs
17LIGHTENING PROTECTION :-Supply and fixing test point terminal block made of gun metal of phosporus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hexagonal head screws including provision of 30cmx25cmx8cm sheet metal box made out of 3.15 mm thick CRCA sheet with front hinged door shutter & locking arrangement and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
18Material and labour earthing with steelearth plate electrode ofsize 60x60cmx6mm thick buried directly in ground to a depth not less than 2.25mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to galvanized iron strip of size 32x6mm as earthing lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full length of earth plate, 40mm dia GI light grade watering pipe with funnel and wire mesh, RCC pit cover of size 300x300x40mm reinforced with XPM having weight not less than 4Kg /sqm including 6mm dia MS bar handle made to shape, PCC pit with 1:3:6 type C1 using 20mm graded crushed stone aggregate with angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, excavation , earth work in any type of soil, removal of excavated soil and returning filling in all as required at site complete all as specified in earth plate No 3 of SSR Part-I and all as specified orindicatedincludingtesting on completion. (NOTE :-Rates inclusive of necessary excavation in any type of soil, earth work, PCC pit, RCC cover, funnel with watering pipe, GI earth strip upto 7.5 m long for connecting totest point etc. all as required at site for complete earthing.)
19Internal Electrification:Supply and fixing for LED Lamp 10 watt B-22 holder base with polycarbonate body and aluminium heat sink warm white complete all as specified and directed by Engineer - in - Charge.
20S & F high performance IP66 LED Streetlight 20 watt, housing made of die-cast aluminium, with street optic lens,with all accessories and connecting up with and including provision of 3 core flexible copper wire of size 1.5sqmm from ceiling rose, and 20W LED light etc. drawn through and including 32mm bore GI light grade protecion pipe upto 1.0m length with suitable fixing accessories on walls, complete all as specified and as directed.
21External Electrification: Supply, installation, test and commissioning of copper wound step down transformer, outdoor type, oil immersed , naturally cooled ONAN, rated temperature rise in oil & winding 45/50 degree centigrade complete with standard fittings of capacity 160 KVA HT 11 KV, 3 phase, LT, 433V, 4 wire, 50Hz ofvector group DYN-11 with off load tap changing device on HT side to vary secondary voltage from + 5% to-10% in steps of 2.5%including cable box on LT and HT side , first fill of new transformer oil having dielectric strength not less than 60 KV, suitable mounting rails of appropriate gauge and other standard accesssories all as per IS:1180 (Part 1) : 2014 with maximum total losses as per energy efficiency level 3 of IS:1180 (Part 1) : 2014 complete all as specified and directed. Note : Accessories such as oil level gauge, rating and diagram plate, monogram plate,explosive vent with daiphargm,thermometer pocket with thermometer, top filter valve, gun metal drain valve at bottom,Air release plug, Inspection cover, lifting lugs/hooks, earthing pads, bi-directional plain rollers, oil temperature indicator, winding temperature indicator, Buchholz relay with valve, marshalling box, silica gel breather & other standard accessories all as perIS:1180 (Part 1) : 2014 etc. Any other item as per manufacturer recommendations for best function of transformer if required are deemed to be included in qouted rates.
22Construction of transformer platform for 160 KVA capacity all as specified and as shown on drawing No CEPZ/C-TD/002/13 sheet 1/5 to 5/5.
23Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frameLED type (with total lumen output not less than 7920 lumens and suitable wattage for efficiency not less than 110 lumens/Watt) min wattage 72watt,with ingress protection IP 66 and surge protection device of 10 KV capacity etc incl necessary, angle iron supports , clamps etc completeand testing on completion all as specified and as directed
24Earthing complete with galvanized steel earth plate electrode 60cmx60cmx6 mm thick buried directly inground (Earth pit not less than 2.25 Mtr deep below normal ground level )with topedge of the plate not less than 1.5 Mtr belownormal ground level connecting with galvanizediron GI earth wire 4mm dia by means ofbolt nut check nuts and washersof galvanized iron and provision of GI tubing medium grade (ISI marked)of size 15mm for protection of GI earth wire upto test point, 20mm dia GI light grade watering pipe with funnel and wire mesh, RCC pit cover of size 300x300x40mm reinforced with XPM having weight not less than 4Kg/sqmm including 6mm thick MS bar handle made to shape, PCC pit with 1:3:6 type C1 with angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, excavation , earth work in any type of soil, removal of excavated soil and returning filling in all as required at site complete all as specified in plate No 3 of SSR Part-I and all as specified orindicatedincludingtesting on completion.NOTE :-Rates inclusive of necessary excavation in any type of soil, earth work, PCC pit, RCC cover, funnel with watering pipe, GI earth strip upto 7.5 m long for connecting totest point etc. all as required at site for complete earthing). and dismantling old defective earthpit. (LA + GOD)
25Supply and fixing timelite distribution boards (street light DBs) 40 A 3 polewith 230 V Astronomical time switch complete all as specified and as directed by Engr-in-Charge.
26LT Panel: Supply, installing, testing and commissioning of LT feeder pillar box factory made oudoor type, double door, slopy canopy, fabricated out of 3.15mm thick CRCA sheet with angle iron base frame made of 65 x 65 x 6mm ,45 cm height, dust and vermine proof, suitable for voltage 415 V 3 Phase 4 wire weather proof, with IP-54 protection, with separate hinge door for each compartment for incoming and outgoing MCCB etc with locking arrangement, with back door openable (Screwed), legs groutedin PCCincluding paintingwith two coats of epoxy powder paint over a coat of primer after under going a rigorous metal treatment process involving alkaline degreasing, descaling in dilute sulphuric acid or any other acid and phosphate and with aluminium busbar (TPN), suitable double compression copper cable glands complete in all respect for DG set main Panel and includingprovn of the following:- (Note: The panel shall be as per CPRI certificate. Rates inclusive ofPCC complete.) (i) Aluminium Bus bar 400-A- mounted on porcelain insulator - 01 Set ( Set of 4 Nos) with PVC sleeve insulation. (ii)MCCB 4 pole 415 V 3 phase 250 Amp, 36 KA (Thermal magnetic release) Ics=100%Icu and adjustable overload setting 80% to100%- 02 Nos (incomming+DG Set) (iii) MCCB 3 pole 415 V 3 phase 200 Amp, 36 KA (Thermal magnetic release) Ics=100%Icu and adjustable overload setting 80% to100%- 01 Nos (outgoing) for AC Plant (iv) MCCB 3 pole 415 V 3 phase 100 Amp, 25 KA (Thermal magnetic release) Ics=100%Icu and adjustable overload setting 80% to100%- 01 Nos (outgoing) for APFC Panel (v) MCCB 3 pole 415 V 3 phase 32 Amp, 16 KA (Thermal magnetic release) Ics=100%Icu and adjustable overload setting 80% to100% - 08 Nos (5outgoing+03 Spare) . (vi) 4 pole On load change over switch of capacity 250 Amps -01 Nos (vii) Digital Voltmeter of size 96x96mm rating 0-500 volts with selector switch - 01 Nos (viii) Digital Amp meter of size 96x96mm rating 0-1000 Amp with CT"s & slection switch - 01 Nos (ix) RYB LED indicator- one set (x) Aluminium Busbar -LS
27Supply, install, test and commissioning of 160 KVA diesel engine driven Generating set with alternator out put Voltage 415 Volts +/- 1% at set value of 415 V at a frequency 50HZ +/- 0.5% with suitable standard control panel, (NTP for suitable for installing at kandrori area Pathankot, allmounted in acoustic enclosure andControl panel as per manufacturers design and specification as per approved CPCB-04 norms confirming to thedetailed specifications appended below :- (I)ENGINE (a) General: Suitable four stroke compressed ignition, radiator water cooled,Turbocharged aspiration, continuous duty with 10% overload capacity for any one hour in 12 hours running, 50°C intake air temperature, CPCB-02 Euro emission engine developing 200 BHP at 1500 RPM coupled to alternator mounted on Channel Iron base frame with in built fuel tank of minimum capacitysuitable for 12 Hrs continous running. The prime mover provided should be as per IS specifications. (b) Air intake system :Should comprise of dry type intake air filter mounted on engine, one in number vacuum indicator mounted on intake piping. (c ) Exhaust System: Should comprise of one exhaust manifold, dry type, mounted on engine, one exhaust residential type silencer which should be positioned in such a way that the exhaust gas is not sucked by the fan on the radiator, thereby affecting the cooling system. The silencer should cater to the noise level tolerance prescribed in the relevant IS/BS. The silencer should be provided with flaps with a provision so that it will open only when the generator is running. The complete exhaust system shall be properly supported so that entire lot of the exhaust system shall not fall on the DG Set.
28(d) Fuel System: Should comprise of disposal type element fuel filter, pressure type fuel pump mounted on engine, non return check valve in fuel supply and drain lines, wire braided hose between filter and pump, fuel system with suitable capacity electronic governor and engine mounted actuator. The fuel tank must have proper locking arrangement with level indicator and to be integrated with base frame. (e) Cooling System: Should comprise of radiator designed and tested for 50ºC ambient temperature with 7 PSI pressure cap mounted on base rail. The thermostat installed in the engine coolant outlet, fresh water pump mounted on engine, fan and fan hub mounted on engine. A reservoir of 50% of radiator capacity to replenish coolant by gravity (as and when required) is also to be provided. (f) Lubricating System: Should comprise of lubricating oil sump mounted on engine, gear driven lub oil pump mounted on engine, lubricating oil cooler-fresh water cooled integral with engine cool out circuit mounted on engine, oil filter lubricating with cap and lubricating oil dip stick for oil level check mounted on engine. The system should be capable of feeding lube oil to the main end& large end bearings, cam shaft, valve rocker gear and all moving parts. (g) Starting System: Should comprise of suitable voltage DC electrical starter mounted on engine, with suitablemaintenance free batteries -2 Nos of capacity 12 V DC with suitable AH to be mounted in trays (having rubber insulation) on the main frame. It should have the provision to charge the battery from external sources during static condition and while running of the generator.
29(h)AC Generator :The generator shall be horizontal and foot mounted, 160 KVA, 415 Volts, 3 phase, 4 wire, 0.8 PF, 50 HZ, self excited, self regulated, brushless AC generator, suitable for an ambient temperature of 50° C with IP-23 enclosure class H insulation and temperature rise limited to class H as per following technical details (i) Type, Brush less AC Generators (ii) Output rating 160 KVA (iii) Output Voltage: 415 ± 1% under all loading conditions. (iv) Output frequency 50Hz ±0.5% up to 0.8 lagging. (v) No of Phases: 3 phase with 01 Neutral (4 wire) (vi) Mounting : Horizontal foot mounted. (vii) Enclosure :Minimum IP-23 / Drip proof and screen protected. (viii) Automatic voltage regulator. (ix) Class of insulation-"H"
30NOTE : Following shall be deemed to be included in rate quoted by contractor :- (i) Suitable size RCC cement concrete foundation platform forDG set canopy base with height as required at site to mount the generator as per manufacturer"s instructions/ recommendations. The cost of foundation bed incl earth work etc is deemed to be included in the quoted rate. (ii) Connecting existing cables, from existing panels and connecting cables , cables glands, cable lugs to new panel complete with all necessary accessories. (iii) Install on the foundation, connecting fuel lines, cable etc. (iv) Test and commissioning complete (v) The cost of control cables from engine Control panel to AMF panel shall be deemed to be included in the cost quoted. (j) BASE FRAME: Shall be stand by and fabricated with CRCA sheet metal which shall be suitable to mount the engine, alternator and radiator, channel width of base frame shall be adequate to accommodate anti-vibration pads.
31AC Plant: Design, supply, Installation, testing & commissioning of water cooled invertor scroll type chilled water Central AC Plant of suitable capacity but minimum 3 x 36 TR (2 working 1 standby) complete-Each 03 (to achieve desired design parameters attached at Appendix "D")
32Note :- (a)  Contractor/ Bidderwill be responsiblefor performance guarantee of complete AC Plant to achieve the inside design conditions round the clock throughout the year with overall COP of the system not less than 3. (b) Rates quoted by the contractor shall include cost of labour, material, scaffolding, finishing as required with tools, plants.cartage. All work shall be executed as per approved drawings . All materials shall be duly approved by GE before incorporation in the actual work.(c) Design of AC plant should be vetted from the IIT / NIT by the bidder. The plant shall comprise the following :-
33(A) CHILLING UNIT:- Water cooled chilling machine, Supply, Installation, testing & commissioning of tentive capacity but minimum 2 x36TR (72 TR) working and 1x36TR standby water cooled Inverter scroll Chilling Machines fitted with hermetically sealed lnvertor scroll compressors, multi/single circuit chiller, water cooled shell & tube condenser, Microprocessor basedBMSCompitablecontrolpanel,suitableforR-407C/R-410aecofriendly Refrigerant, Shell & Tube Insulated Evaporator, Expansion tank of suitable capacity Control Mechanism of actual Cooling capacity .-Each 03
34The unit shall confirm to ECBC norms as under:- (a) Minimum COP=4.5 (b) Minimum IPLV =0.4615 kW/ton R/IPLV = 7.619 kW/kW The unit shall be factory tested as per AHRI standard 550/590 latest edition. The conditions for condensor and chiller are as under:- Condensor: Water in 85 Deg F Water out 95 Deg F Fouling factor 0.0000440 M2 °K/W Chiller: CHW in 54 Deg F CHW out 44 Deg F Fouling factor 0.0000180 M2 °K/W
35(B) CHILLED WATER CIRCULATION SYSTEM COMPRISING OF:- (i) Supply, installation, testing and commissioning of suitable capacity chilled water Mono Block type centrifugal pump including necessary foundation oftentative & minimum capacity 8 LPS at 32 m head with bronze impeller, bearings, SS shaft, mechanical seal, TEFC squirrel cage induction motor of adequate HP having class F insulation suitable for operation on 3 phase, 415 V, +/- 10%, 50 Hz AC supply, base plate and mounting channel frame, accessories and fittings along with coupling, coupling guard, vibration isolation arrangementcomplete all as specified and as directed. (2 working 1 standby). Each 03
36(ii) Supply and fixing of Chilled water piping with MS, Heavy Grade(class C) ERW pipes of suitable diameter, including all weldable fittings for butterfly valves, NRVs & "Y" strainers, suitable size Pressure guage shall be provided at the outlet of each pump, stem type thermometer (Brass), water flow switch, Auto Air vent and balancing valves and interconnection between chiller, chilled water pumps with AHUs and cooling coil units. Chilled water piping shall be insulated with 25mm thick XLPE insulation, wrapped with polythene paper and final finished with glass cloth with vapour barrier star bond including necessary steel supporting structure complete all as specified and as recommended. -01 Lot
37(iii) Supply and fixing of Three way Mixing valve of suitable size with motorised actuator and modulatingcontrol for AHU including control wiring of suitable size as per OEM.
38(iv) PVC double layer Expansion tank of cap. 1000 ltrs dully insulated with 25 mm thick nitrile insulation and covered with 26 Gl sheet and placed on PCC/ Brick suitable staging.
39(C ) CONDENSER WATER CIRCULATION SYSTEM:- (i) Supply, installation, testing and commissioning of FRP rectangular shape, vertical, induced draught counter flow cooling tower of (tentative & minimum 2 x 43.5 TR) size (capacity considered 20% extra of AC plant. with uniform water distribution and optimal heat transfer, having tough fiberglass reinforced plastic (FRP) casing of sufficient structural strength to withstand vibrations and wind velocity upto 60 m/s, FRP basin, rigid honeycomb type PVC fill of suitable thickness, SS sprinklers and non-clogging sprinkler pipes, FRP drift eliminator, energy efficient induced draught axial type fans with factory set and dynamically balanced blades pitch, IE3 TEFC squirrel cage induction motor, suitable for operation on3- Ph, 415 V, 50 Hz AC supply with IP 65 protection for enclosure, conforming to IS 12615: 2018, inlet, outlet, drain and over-flow nozzle connections, etc. complete with accessories complete all as specified and as directed (both working with combined capacity of tentative minium 87 TR) Note: Water circulation system shall be designed so as to needt temparatrequirement as well humidification control as per requirment.
40(ii) S & F multilayered HDPE make-up water tank of 5000 liter capacity made up of 100% virgin material, white outer layer, threaded lid, extra insert lid for protection against algae formationcomplete with inter-connection piping and non-return valve etc including tank to placed on suitable PCC/ brick staging complete all as specified and as directed.Each -02
41(iii) Supply, installation, testing and commissioning of suitable capacity chilled water Mono Block type centrifugal pump including necessary foundation of tentative & minimum capacity 9 LPS at 20 m head with bronze impeller, bearings, SS shaft, mechanical seal, TEFC squirrel cage induction motor of adequate HP having class F insulation suitable for operation on 3 phase, 415 V, +/- 10%, 50 Hz AC supply (2 working 1 standby) 100 mm dia pressure guage shall be provided at the outlet of each pump including suitable size base plate & mounting channel frame, accessories and fittings along with coupling, coupling guard, vibration isolation arrangementcomplete all as specified and as directed. Each 03
42(iv) Supply and fixing of Condenser water piping with MS, Heavy Grade (class C) ERW pipes of suitable diameter, including all weldable fittings for butterfly valves/ gate valves, NRVs & "Y" strainers and interconnection between chiller unit, condenser water pumps with cooling towers, make up water tank, pressure switch on main header complete all as specified. -01 Lot
43(v) Supply and fixing of non chemical type scale preventor made of SS tube flanged ended of suitable size.
44Hot Water System Comprising of:- (i) Supply, installation and commissioning of electrical hot water generator equipped with sufficient no. of flanges and electric immersion heaters. The pressure vessel shall be constructed as per ASME standards and insulated on all sides with 2 layers of 50 mm thick fiberglass with 28 guage aluminium cladding as per specifications. The hot water generator shall be equipped with all automatic and safety controls such as manual reset, high temperature water outlet, step controller and recycling relay, on/off switch type thermostat, pilot light, low water cut off and other controls as per manufacturers recommendations. All basic control and terminals shall be located in an integral controlabinet factory wired and tested. The hot water generator shall be suitable for 415+/- 10% volts/50 cycles, 3 phase power supply. The entire hot water generator shall be factory assembled and testedofsuitable capacity required or controlling dehumidification only water in -110 Deg F Water out -120 Deg F both working of combined of suitable capacity required for controlling dehumidification only.
45(ii) Supply, installation, testing and commissioning of Monoblock type pump for re-circulation of hot water with ribbed rubber including necessary foundation of capacity 8 LPS at 32 M head with bronze impeller, bearings, SS shaft, mechanical seal, TEFC squirrel cage induction motor of adequate HP having class F insulation suitable for operation on 3 phase, 415 V, +/- 10%, 50 Hz AC supply (2 working 1 standby) suitable size pressure guage shall be provided at the outlet of each pump including suitable size base plate & mounting channel frame, accessories and fittings along with coupling, coupling guard, vibration isolation arrangementcomplete all as specified and as directed. Each 03
46(iii) Supply and fixing of hot water piping with MS, Heavy Grade(class C) ERW pipes of suitable diameter, including all weldable fittings for butterfly valves, balancing valve, NRVs & "Y" strainers, stem type thermometer (Brass), suitable size pressure guage, auto air vent and interconnection between HWG hot water pumps with AHUs and heating coil units. Hot water water piping shall be insulated with 25mm thick XLPE insulation, wrapped with polythene paper and final finished with glass cloth with vapour barrier star bond including necessary steel supporting structure complete all as specified and as recommended. -01 Lot
47(iv) Supply and fixing of Three way Mixing valve ofsuitable size with motorised actuator and modulatingcontrol for AHU including control wiring of suitable size as per OEM.-02 Nos Approx
48(v) PVC Triple layer Expansion tank of cap. 1000 ltrs dully insulated with 25 mm thick nitrile insulation and covered with 26 Gl sheet and placed on PCC/ Brick suitable staging.
49(vi) Pan type humidifier made of SS tank of 2 mm thick of cap. 9 KW complete with all water connection with GI piping of suitable size.
50(vii) Material & labour for automation system to operate the hot water generator and there pumps automatiocally to maintain the relative humidity inside the shed with necessary control & fittings -01 Job
51Air handling Unit:Supply, installation, testing and commissioning of double-skin type horizontal, floor-mounted, top discharge air handling unit capable of delivering tentative minimum 25500 CFM so as to ensure ambient and similar discharge from all air outlets air at 80mm W.G. static pressure using gaskets and self-adhesive tapes and 0.6 mm thick pre-coated outer skin and 0.6 mm thick GI inner skin, 25±2 mm thick double skin panel with pressure injected CFC & HCFC free PUF having "k" value of 0.02 W/°C/m & density 40 kg/m³, AMCA certified energy efficient plug fans with backward curved blower, having pre filter section of 50 mm thick combination of 8 rows deep chilled water coils and 2 row deep heating coil with anti-corrosion aluminium fins, suitable high efficiency (IE3) TEFC squirrel cage induction motor and marine lamp, limit switch, SS-304 drain pan, vibration isolators/rubber pads inspection windows / doors complete all as specified and as directed.- 01 Each
52The AHU shall comprise of the following: [a] Suitable DIDW backward curved plug fan, dynamically balanced, with AMCA certified blower. [b] Foot mounted (B3 construction) 3-Phase squirrel cage induction motor 415 V ± 10%, 50 Hz ± 5 %, combined variation ±10%, insulation class F. [c] Flexible connetion made with airtight ASTM E84 (Class I) polyester fire retardant cloth riveted on periphery of cloth with extruded aluminium "L" angle flange as per fan size at discharge duct/plenum [d] A wetted type or viscous type & Washable type of "EU4" filter (pre-filter, efficiency 90% down to 10 micron)
53[e] 8 rows deep chilled water cooling coil and 2 row deep heating coil section with 0.15 mm thick copper fins and 0.36 mm diameter copper tubes tested on 21 kg/cm²,with SS sandwiched drain tray, etc. (a 350 mm service section between eliminator and heater is required). [f] Condensate drain pan fabricated from 18 gauge SS 304, powder coated and insulated with elastomeric insulation of suitable thickness.
54Supply, installation, testing and commissioning of fire damper, at least of 90 minutes fire-rating, spring activated on melting of fusible link having melting point 67.13° C complete with smoke detector / thermistor, fusible link etc. and actuator as required for operation, located in the SA / RA ducts, at all fire rated crossovers (shafts, walls, etc.). along with control panel (located in such a way that the reset can easily be done), interlocked with the building management system for the fire detection or HVAC to trip / close in the event of fire/smoke in the respective zone and tested as per ULL- 555 and certified by CBRI complete all as specified and as directed. The fire dampers shall meet the following criteria: [a] Bare fire dampers with 150 mm sleeve. [b] Control panel actuator, including electrical spring type actuator, remote indication of the fire damper position. [c] Interconnection wire for the fire detection & alarm system with the AHU and the smoke dampers. [d] Sealing any openings around the sleeve of the fire dampers with approved fire sealant as per the specification & recommendations of the manufacturer.
55Motorized, spring return type, combination fire and smoke damper -02 Nos Approx
56Control panel actuator, including electrical spring type actuator, remote indication of the fire damper position -02 Nos Approx
57Supply, installation, balancing and commissioning of site fabricated galvanized steel sheet metal (G.S.S.) having thickness 24 G and 22 G as required or directed , rectangular ducting having zinc coating of 120 g/m² total on both sidesand complete with neoprene rubber gasket, elbows, splitter dampers, vanes, hangers, supports, etc. as per approved drawings and conforming to the latest edition of IS 655: 2006 & HVAC Duct Construction Standards - Metal and Flexible of SMACNA. First five meter of the duct will be acoustically insulated with 25 mm thick fibre glass wool (density 24 Kg/Cum) and 28 SWG aluminium perforated sheet. Duct will be insulated with closed cell "Class"O" nitrile sheet having 9 mm thick. No volume control damper shall be provided in the ducting as the flow of air shall be controlled by the VCD damper installed in supply air grilles. - 01 Lot Note: The design supply and fixing of support of duct on both side of 15 mtr wide road shall also be part of the quoted rate in addition to supporting structure for duct elsewhere whenever duct is running.
58S & F of aluminium anodised grills/ diffusers complete with MS volume control damper for supply grills/ diffuserscomplete all as specified and as directed. - 01 Lot
59S & F of aluminium anodised return grill without aluminium volume control damperscomplete all as specified and as directed. - 01 Lot
60Electrical :-Supply, installation, commissioning and testing of factory made, CPRI type tested, outdoor, cubical compartmental type "HVAC Panel" of suitable size, conforming to IEC 61439-1 &2, IEC 61641, having both sides openable with hinged & locking arrangement and IP 42 protection made out of 2mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation(1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc, complete all as specified and as directed. The HVAC Panel shall comprise of the following: Each -01 Approx Busbar Chamber: [i] 01 Set (3L + N) of copper busbar of rated capacity 600 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection.
61Incoming: [i] 450 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. [ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. On hrs & interrupts- 01 Nos. [iii] LED phase indicators (Red, Yellow, Blue)- 01 Set
62Outgoing: [i] 125 A, 415 V, Ics = Icu = 16 kA, conforming to IEC 60947- 2, 50 Hz, FP MCCB with adjustable thermal settings & fixed magnetic settings with compression lug connectors and thermal magnetic trip unit (TMD)- 03 Nos. [for chillers] [ii] 100 A, 415 V, Ics = Icu = 16 kA, conforming to IEC 60947- 2, 50 Hz, FP MCCB, 25kA - 05 Nos. [for AHUs] [iii] 63 A, 415 V, Ics = Icu = 16 kA, conforming to IEC 60947- 2, 50 Hz, FP MCB (C-Curve) with DOL starter- 10 Nos. [for chilled water pump, condenser water pump, Hot water pumps & cooling tower] [iv] Auomatic DOL starter for chilled water circulation pump -3Nos [v] Auomatic DOL starter for condenser water pump -3Nos [vi] Auomatic DOL starter for cooling tower fan motor-2Nos [vi] Auomatic DOL starter for hot water pumps-2Nos [vii] LED phase indicators (Red, Yellow, Blue) [viii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 13 Nos.
63SUB CONTROL PANEL FOR AHUs: Supply, installation, commissioning and testing of factory made, CPRI type tested, outdoor, cubical compartmental type "Sub control Panel" of suitable size, conforming to IEC 61439-1 &2, IEC 61641, having both sides openable with hinged & locking arrangement and IP 42 protection made out of 2mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation(1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc, complete all as specified and as directed.Each -02
64Incoming: [i] 100 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz FP MCB, having microprocessor based trip unit. [ii] LED phase indicators (Red, Yellow, Blue)- 01 Set
65Outgoing: [i] 40 A, 415 V, MCB with adjustable thermal settings & fixed magnetic settings with compression lug connectors and thermal magnetic trip unit - 01 Nos. [for AHU Motor] with SDS starter [ii] 40 A, 415 V, MCB with adjustable thermal settings & fixed magnetic settings with compression lug connectors and thermal magnetic trip unit - 01 Nos. [for Pan type Humidifier] with DOL starter
66Supply, installation, commissioning and testing of factory made, CPRI type tested, cubical compartmental type "control console panel" of suitable sizeto operate the AHUs from Plant having ON/OFF lighting push buttoms with copper control cable (which is measured and paid seperatly) -Job 01
67M & L for earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6 mm size, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to GI wire of 4.0 mm diameter as earth lead, by means of bolts, buts, check nuts and washers of galvanised iron or steel, galvanized iron pipe of 40mm diameter,connectedtoearthingtestpoint,allasshowninelectricalplateNo.5connectedto earthing test point all as specified or indicated including testing on completion and including excavation, earthwork, PCC earth pit of dimensions 550 mm X 550 mm (outer) and 300 mm X 300 mm (inner) and 250 mm deep, with a 10 mm thick CI cover, hinged to CI frame on ground level, GI watering pipe, funnel, etc. complete as specified and as directed. (i)The cost of GI earth continuity conductor with GI pipe 40mm medium grade upto 7.5m is deemed to be included above item (ii) The earth chamber tobe constructed0.5m fromedge ofearth pitwith necessarywatering arrangement. The cost for the same is deemed to be included in above item. - Each 20 Approx
68M & L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buriedingroundordrawninconduit/pipeorfixedtopolesoranyotherindicatedsituationforloop earthing etc. as required Aluminium strip of 25 x 3 mm thick complete as specified and as directed
69ARMOURED CABLE:-Necessary cable connection from main electrical panel and AHU sub panesl to all the equipments in plant room with suitable size/ dia multi stranded aluminium conductor armoured cable and AHU motor, heater banks respectively with suitable size stranded copper conductor armoured cable with cable glands complete as specified and as directed. Note : Excavation work, return and filling, sand cushioning and laying of bricks deems to enclusive of rate quoted.
70CIVIL WORK COMPRISING OF THE FOLLOWING:-Civil work such as foundation as per manufacturer specifications/ recommendations for chilling unit, chiller, condender & pumping sets, cooling tower, makeup & expansion tank and AHU and making opening in brick wall/ PCC and making good for ducts, pipes, cables and fresh air intake etc. - Job 01
71MISCELLANEOUS ITEMS:- (i) All civil works connected with installation of plants and AHU, cutting of holes in walls, floor and making good etc. including provn of foundations. (ii) Drain pipes from variuos equipments to the drain out points. (iii) Intial charge of compressor oil and refrigerant. (iv) Any other connected work which is not mentioned above but required at site for commissioning and performance of the above air condition plant. (v) Provn of pre-filters of the fresh air intake points for the AHU. (vi) Return air washers with accessories. (vii) Testing & commissioning of above plant.
72Fabrication of supporting structure for duct using MS channel of required size wirh clamp welded to hold duct with nuts, bolts & washers as required incl. cutting, welding, drilling, bending hot & cols etc embedded in PCC with base plate welded on bottom grouted in PCC with four nos nuts, bolts & washers all as confirming to Fe-410-F and painting with two coat of synthetic enamel paint over one coat of red oxide primer all as spd and dirteced. Note:- Cost of PCC and earth work deemed in quoted rate.
73Outsourcing for maint and operation of central AC Plant of capacity including connected LT control panels. AHUs, pumpsets, cooling towers etc complete of any capacity, Diesel Generating Set with connected control panel which shall be run when electric brakdown occures, complete round the clock in three shifts of 8 hours with deployment One Ref/Mech (skilled) and one unskilled Ref/Mech (Helper) for each shift of 08 hours including daily periodical maintenance like cleaning, greasing and oiling in moving parts etc, are cleaning upto 10 mtrs surrounding the station complete all as specified and directed by Engr-in-Charge.