Tender For Electrical Installation Work Allied Electrical Installation For Emergency Power Backup Supply From Existing 500 Kva Dg Set To Fire Fighting Pump Set During Emergency Period Under Chittaranjan Seva Sadan College Of Obstetrics, Gynaecology And C, Kolkata-West Bengal
TDR : 40566357
Tender Notice
BOQ
Expired
Kolkata
West Bengal
Tender For Electrical Installation Work Allied Electrical Installation For Emergency Power Backup Supply From Existing 500 Kva Dg Set To Fire Fighting Pump Set During Emergency Period Under Chittaranjan Seva Sadan College Of Obstetrics, Gynaecology And C
Name of Work: AlliedElectrical Installation for emergency power backupsupply From Existing 500 KVA DG Set to fire fightingpump set during emergency period under Chittaranjan seva sadan college ofObstetrics, Gynaecology & Child Health , Kolkata.
Sl. No.
Item Description
1
Supplying & Laying of one no.4 Core240 sqmm PVC/ XLPE aurmoured aluminium conductor cable (Polycab / Gloster / Havels)through existing cable trench ( MCH building LT Panel to Fire Fighting control Room).
2
Supplying & Laying of one no.4 Core150 sqmm PVC/ XLPE aurmoured aluminium conductor cable (Polycab / Gloster / Crystal/KEI) on wall on pre fixed L-Clamp . ( Changover switchto Fire Fighting control Panel)
3
S & F 415 Volt,315 Amp(Front operated) SFU with its 3 Nos DIN type HRC fuse with sheet steel enclosureon angel iron frame on wall including 1 no. Cabel entry box with nut and bolt arrangement. ( Make- L&T /siemens/ABB/equivalent).
4
S & F 415V, 315A FP on load change over switch with sheet steel enclosure on angle iron frame on wall with nut bolt arrangement (Mk. L&T / ABB / Siemens/HPL).
5
Supply & Fixing 415 V,320Afour pole MCCB of breaking capacity 26 KA with fixed thermal & fixed magnetic /adjustable thermaland fixedmagnetic setting on existing mainLT panelwith making necessary connection at Mother & Chilid Hub Building(Make- Legrand DPX3 630 cat No-422001/ABB/Equivalent)
6
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables.
7
a) 4core X 240 sq.mm.
8
b)4 Core x150 sqmm
9
Finishing of the XLPE/PVC insulated armoured cable ends by crimping method with cable sockets and insulated tapes etc., including supplying sockets, soldering materials, tapes etc. and making connection to switch, BDB and BBC etc.
10
a) 4core X 240 sq.mm.
11
b)4 Core x150 sqmm
12
Internal connection between existing Bus-bar & proposed 320 A rating MCCB by S & F 415 V,415A.4 Nos.electrolytic gradetinned copper falts bar (50mmx5mm) . The bar is to be rigidly supported on suitable DMC/SMC moulded non-hygroscopic insulating materials FRP chairs of robust fashion to withstand electromechanical stresses. All connections to bus is to be made by suitable nut bolt. The bus bar is to be wrapped with heat shrinkable PVC tape(Red,Yellow, Blue & Black) for identification with suitable box within the floor mounted industrial panel & hinged type door.
13
Supply & Fixing of L shape MS angel frame of length 12\"x6\"made from50x50x6 mm thick MS angle Including making drilled hole,Fixing on wall with 2 set anchor bolt with 2 coat RO primer and Paint.
14
Add: GST @18%
15
Add: LWC@1%
16
Defect Liability Period - 1 (One) year
17
Make & model of each and every material to be approved by EIC