Tender For Sitc Of Addressable Fire Detection And Fire Alarm System At Dtc 6Th Floor Str, New Telecom Building, Bengaluru Recall1., bengaluru-Karnataka

Bharat Sanchar Nigam Limited-BSNL has published Tender For Sitc Of Addressable Fire Detection And Fire Alarm System At Dtc 6Th Floor Str, New Telecom Building, Bengaluru Recall1.. Submission Date for this Tender is 14-11-2023. Flame Detectors Tenders in bengaluru Karnataka. Bidders can get complete Tender details and download the document.




Tender Notice

40438771
Tender For Sitc Of Addressable Fire Detection And Fire Alarm System At Dtc 6Th Floor Str, New Telecom Building, Bengaluru Recall1.
Open Tender
Indian
Karnataka
bengaluru
14-11-2023

Tender Details

Tender For Sitc Of Addressable Fire Detection And Fire Alarm System At Dtc 6Th Floor Str, New Telecom Building, Bengaluru Recall1.

Key Value

Document Fees
INR 590 /-
EMD
INR 25444.0 /-
Tender Value
INR 12.72 Lakhs /-

BOQ Items

Name of Work: SITC of Addressable Fire Detection and Fire Alarm System at DTC 6th floor STR, New Telecom Building, Bengaluru Recall1.
Sl. No. Item Description
1SITC of AFD System
2Fire Alarm Control Panel (FACP): Supply Installation Testing and Commissioning of Microprocessor based 2 wire fault tolerant. Networkable type Fire Alarm detection 2 loop Addressable type AFD control panel (each loop to suit minimum 99No of Fire detectors and 99 No of Modules/devices) The panel shall be able to give location of all fire and fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON/OFF the respective control modules whenever any alarm is triggered.The panel shall have rectifier loop cards, 80 characters LCD unit to indicate Fire, Fault signal with address and analog output with provision for adding external printer to log all fire of fault events complete in all respects. The panel shall be sheet steel powder coated sealed to IP:30. The panel shall have LED indicators for indication of various signals. The panel should have TCP/IP Connectivity and should have the facility to view remote access with similar view of FACP PMI . The panel shall have a built in power supply and battery charger along with maintenance free 7Ah 2 x 12Volts SMFbatteries capable of Running forminimum of 2hours with battery charger and conforming to BS: 5839 Standards and duly approved by EN54/LPCB/VDS/UL as per specifications complete in all respects etc. complete as required.
3Supply Installation Testing and Commissioningof intelligentanalogue Addressable MULTISENSOR type smoke detectors complete with single/twin LED, Hard Addressable having rotary decade Address switches from 01-99, with, mounting base conforming to BS:5839 standards and duly approved by EN54/UL/FM/LPCB/VDS etc complete as required. (Installed on real ceiling/on False ceiling/on false flooring)
4Addressable Heat Detector: Supply Installation Testing and Commissioning of EN54/ UL/ FM/ LPCB/ VDS Intelligent Analogue addressable ROR Heat detector with junction box etc. as required.
5Response Indicator: SITCof Response indicator having twin LEDs for mounting on false ceiling / wall at the entries of the cabin for indicating the operation of detectors in the above false ceiling / below false flooring detectors etc. as required.
6Manual Call Point: Supply Installation Testing and Commissioningof intelligentanalogue Addressable Type Manual call points having surface or Flush mounting option fully compliant to EN54 having Rotary Decade switches for addressing from 01-99 with back box for mounting as required conforming to BS5839 Standards and duly approved by EN54/ UL/ FM/ LPCB/ VDS as required.
7Electronic Hooter : Supply Installation Testing and Commissioning of addressable type loop powered Hooter complete with mounting base conforming to BS:5839 Standards and duly approved byEN54/ UL/ FM/ LPCB/ VDS as required.
8Fault Isolator Module: Supply Installation Testing and Commissioningof Addressable TypeFault isolator for isolating shorted, delinked and loose circuits between two successive fault isolators with automatic resetting arrangement to be interconnecting to loop cable and conforming to BS:5839 Standards and duly approved by EN54/ UL/ FM/ LPCB/ VDS etc. as required.
9Addressable control modules: Supply Installation Testing and Commissioning of Addressable control modules for providing tripping contacts for package Air Conditioning system/AHU’s (This shall be wired in loop and located near the AHU"s etc as required.
10Supply and Laying of additional 2 x 1.5 sq.mm PVC/XLPE insulated, PVC sheathed, FRLS armoured copper cable on surface of wall /ceiling with necessary glands, saddles etc., complete as required. (Make: Any ISI marked cable with FRLS insulation)
11Supplying & Fixing GIBox of following size (Nominal size) on surface of with suitable size phenolic laminated sheet cover in front including panting etc., as reqd. a)85x85mm x50mm deep
12Supply & making end termination with brass compression gland suitable for 2x1.5 sq. mm.copper cond. UG cable etc., as reqd.
13Re-arrangement of existing 2 x 1.5 sq.mm PVC insulated, PVC sheathed, FRLS armoured/flexible copper cable of old Fire Detection system to suit the new Addressable Fire Alarm system i/c dismantling of existing old detector, MCPs, Hooters, Response Indicators, AFD panel, Mimic diagram etc as per the direction of Engineer In-charge etc., as required.
Disclaimer :