Tender For Supply, Installation, Testing, Commissioning Of Hvac Work At Dental College, Jodhpur, jodhpur-Rajasthan

Rajasthan State Road Development And Construction Corporation Limited has published Tender For Supply, Installation, Testing, Commissioning Of Hvac Work At Dental College, Jodhpur. Submission Date for this Tender is 16-10-2023. HVAC Tenders in jodhpur Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

40125748
Corrigendum : Tender For Supply, Installation, Testing, Commissioning Of Hvac Work At Dental College, Jodhpur
Open Tender
Indian
Rajasthan
jodhpur
16-10-2023

Tender Details

Tender For Supply, Installation, Testing, Commissioning Of Hvac Work At Dental College, Jodhpur

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 11-Oct-2023 Corrigendum Other 16-10-2023

Key Value

Document Fees
INR 1180 /-
EMD
INR 131000.0 /-
Tender Value
INR 65.50 Lakhs /-

BOQ Items

Name of Work: SITC of HVAC work at Dental College, Jodhpur
Sl. No. Item Description
1Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia
2100 mm dia per running inch length
3Supply, Fabricating & installing following sizes of perforated Powder coated MS cable tray with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
4225mm x 50mm x 1.6mm
5450mm x 50mm x 2.0mm
6600mm x 50mm x 2.0mm
7Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as requiredcomplete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
8Supply,Installation, Testing & Commissioning of modular type VariableRefrigerantFlow/VariableRefrigerantVolumeaircooled Outdoorunitssuitable for cooling and heating,having100% hermetically sealed inverter type Scroll Compressor(s) withand minimum two compressors along with two Condensing fan,above 14/18 HPmodules,microprocessorbased Controller, Side / top discharge type condensing unit(s), with R-410 A Refrigerant,vibrationisolators,withsuitablefoundationetc. completeasrequired.Theunitshalldelivertheratedcapacityat AHRIConditions andwork evenat 50°C ambient temperature without tripping.The unit shall be suitable to work on 400V +/- 10%, 3Phase,50HzACpowersupply.Theunit shallbefilledwithfirst charge of the refrigerant and ready for use as required. The EER at 100% load with AHRI conditions shall not be less than 3.5 andIncluding OEM supplied Piping connection Kit etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR . Make :- HITACHI /MISTUBHISHI /DAIKIN /OGENERAL . THE COMPLETE AC SYSTEMSHALL BE IN THE COMPREHENSIVE MAINTANANCE PERIOD OF FIVE YEARS AND SHALL BE MAINTANED BY THE OEM OR ITS AUTHORISED DISTRIBUTOR.
9Supply,installation,testingandcommissioningoffollowing minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor,coilsection with DXCoppercoil,electronicexpansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation,Cordedremotecontroletc., suitableforoperationon single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down valve in case of fire on receivingsignalfromBMSSystem. Thecoolingcapacityofindoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
10Ceiling Mounted4 Way Cassette type Units with Remote Control
111 TR
121.6 TR
132 TR
142.4 TR
153.2 TR
164 TR
17Supply, installation, testing & commissioning of Group controller for monitoring the status and working condition of all indoor and outdoor units, The controller shall act as an advanced air conditioning management system to given complete control of VRV/VRF air conditioning equipment with Starting/stopping of air-conditioning as a zone or group of individual units. Temperature setting for each Indoor units of zone, Switching between temperature control modes, switching of the fan speed and direction of airflow, enabling/disabling of individual remote controller operation, Alarm code display in case of any problem. It shall be able to control up to 64 (max. 512 if required) number of Indoor units. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
18Supplying and installation of high-pressure grade required size OEM make copper connectionY or T Joints / refnet for liquid and suction line complete erected on wall/ceiling with supports/raceways, Nitrile rubber insulation, painting etc. with brazing and testing for leakages confirming the normal operation of the VRV / VRF air conditioning system. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
19Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping withfittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing,support with MS hanger on ceiling or recessed in wallwith chasing & plastering with 6 mmthickclosedcellelastomeric nitrile rubberinsulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
2025 mm
2132 mm
2240 mm
23Supplying and drawing Fire Resistant flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existingsurface or recessed PVC/ MS conduit/casing capping/ Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
242 x 1.5 Sq.mm Unarmoured With Outer Sheath in Red Color