Tender For Attending Day To Day Faults, Repairing, Maintenance Of Outdoor Type Transformer Substations And Rewinding Of 25/63 Kva, 11Kv/0.415Kv Oil Cooled Transformers With Associated Works At Various Telephone Exchanges, Mobile Btss Sites In Zo, cuttack-Odisha

Bharat Sanchar Nigam Limited-BSNL has published Tender For Attending Day To Day Faults, Repairing, Maintenance Of Outdoor Type Transformer Substations And Rewinding Of 25/63 Kva, 11Kv/0.415Kv Oil Cooled Transformers With Associated Works At Various Telephone Exchanges, Mobile Btss Sites In Zo. Submission Date for this Tender is 16-10-2023. Transformer Supply Tenders in cuttack Odisha. Bidders can get complete Tender details and download the document.




Tender Notice

40100959
Tender For Attending Day To Day Faults, Repairing, Maintenance Of Outdoor Type Transformer Substations And Rewinding Of 25/63 Kva, 11Kv/0.415Kv Oil Cooled Transformers With Associated Works At Various Telephone Exchanges, Mobile Btss Sites In Zo
Open Tender
Indian
Odisha
cuttack
16-10-2023

Tender Details

Attending Day To Day Faults, Repairing, Maintenance Of Outdoor Type Transformer Substations And Rewinding Of 25 / 63 Kva, 11Kv / 0.415Kv Oil Cooled Transformers With Associated Works At Various Telephone Exchanges, Mobile Btss Sites In Zone-I Under Repair And Maintenance Of Bsnl Transformer Substations

Key Value

Document Fees
INR 590 /-
EMD
INR 11516.0 /-
Tender Value
INR 5.75 Lakhs /-

BOQ Items

Name of Work: Attending day to dayfaults,repairing & maintenance of outdoor type transformer substations andRewinding of 25/63 KVA,11KV/0.415KVoil cooled Transformers with associated works at various Telephone Exchanges, Mobile BTSs Sites in Zone-I under Cuttack BA(For 2023-24) Phase-I .
Sl. No. Item Description
1Attending to break down calls, physical inspection of Substation accessories, overhead lines, feeder panels, meter box etc. to find out thefaultsand taking corrective measures for restoration of power supplyi/crectification of minor faults such as replacement of pin/post insulators, jumper wires, LT side cable , LT side switch gears etc.if required any. (Materials are not in the scope of this item)
2For sites distanceup to and including 50 KMs
3For sites distanceabove 50 KM and up to and including 100 KMs
4For sites distanceabove 100 KM and up to and including 150 KMs
5For distanceabove 150 KM and up to and including 200 KMs
6Liaison with different units of the supply authority i.e. DIvision/Sub Division/Section offices/MRT office/E & MR office and field staff etc.forobtaining shut down of 11KV line, breaking of meter sealif required to carry out therepairing and maintenance works of the Sub Station and re-energisation, testingetc.as required.
7To carry outminor repairing works such aspin/post insulators, jumper wires, LT side cable , LT side switch gears etc.
8To carry out major repairing workssuch as rewinding/ replacement/ repairing & overhauling of Transformer, AB switch, DO fuse unit, replacement of HT cable and its end termonations or any other major repairing works of the DP structure & associated overhead lines.
9Thorough servicing of AB Switch, adjustment of bearings, male/female contacts, lubricating of movingitems i/c replacement ofminor defective parts like nuts, bolts, clamps, wire braided copper strips and checking the functional operation,etc.as required.
10Replacement of the following defective spare parts ofthe transformer substation by new one i/c fitting, connectionetc. as reqd.
11Male contact and Female contacts made of hard drawn copper for 200 Amps air break switch with wire braided strip etc. comprising of 3nos per set.
12Rotor mechanism for 200 Amps air break switch.
13Square/round bar for AB switch (Horizontal unit)
1411KV Post Insulator for 200Amps AB switch/ HG fuse unit
15Operating Handle made of 25/32mm Medium class GI pipe with wire braided copper strip
16Heavy duty operating pipe for air break switch i/c fabrication etc. as required.
17Replacement of damaged breather for 25 KVA 11KV/0.415KV transformer by a new one with dry silica gel etc. as required.
18Replacement of faulty/damaged pin insulators by new oneof 11 KV grade pin type insulator with large steel head G.I. pin, nuts, washers on existing HT pole/ DP structure etc. complete as required.
19Replacement of faulty/damaged discinsulators by new one of 11 KV, 45 KNporcelain disc insulator with galvanized insulator fittings, ball and socket type and complete with galvanized strain clamps, bolts, nuts, washers etc. as required.
20Replacement of faulty Lightening arrestorsby newones of nonlinear resistor typelightning arrestor suitable for 3 wire, 11 KV overhead lines with rated voltage 9 KV (rms) with a nominal discharge current rating of 5 KA and complete with galvanized clamping arrangement, G.I. bolts, nuts, washers etc. as required, comprising of 3nos per set.
21Replacement of damaged and unserviceable AB switch by new one of11 KV, off load, single break, triple pole, horizontal type, gang operated air break switch having 2 nos. 11 KV post type insulator per phase complete with galvanized channel iron base, arcing horns, 25 mm dia. 6mtr. long GI pipe, tinned copper wire braided flexible earthing wire & operating handle with locking arrangement etc. complete as required.
22Replacement of damaged and unserviceable DO/HG fuse units by new one of 3 phase, 11 KV outdoor type Horn Gap Fuse unit having 2 nos. 11 KV post type insulator per phase complete withchannel, cu-wire etc. as required. (one set comprising 3 units).
23Supply & drawing of 55 sqmm. AAA conductor for overhead line and DP structures i/c binding with insulators etc. complete as required.
24Rewiring of the DP structure of Transformer Sub Station with 55sqmm AAA /50sqmm insulated Al.conductor stranded cable with al. Lugs/sockets, binding with post insulators etc. complete as required.
25Replacement of thedefective parts/components by new ones of following sizes & ratingsaluminium/copper sockets/lugsforPVC sheathed / XLPE aluminium/copper conductor cable of 1.1 KV grade i/cfixing/crimpingetc. as required.
2616/25 sqmm Al socket.
2735 sqmm Al socket.
2855 sqmm Al socket.
29Dismantling the following ratings faulty transformer from the existing D.P. structure/Plinth & installation of standby/repaired transformer i/c testing and commissioning, recording the required parameters etc. by qualified staff, arranging required tools & plant with proper precautionary measures etc. as required.
3025 KVA, 11KV/0.415KV, 50 Hz Aluminium wound oil cooled Transformer
3163 KVA, 11KV/0.415KV, 50 Hz Aluminium wound oil cooled Transformer
32Repairing of 25/63 KVA Aluminium/copper wounded transformerat factory/workshop by dismantling the faulty transformer, re-insulating the windings, heating, reassembling i/c replacement of gaskets, nuts & bolts, washers, carry out factory tests etc. complete as required. (Rewinding of Transformer is not in the scope of this item)
33Repairing of 25 /63 KVA Aluminium/ copper wounded transformer at site i/c opening top cover, checking the bush, inter connectionswires/strips from bushings to transformer windings, tightening the connections, etc.as required. (Rewinding of Transformer is not in the scope of this item)
34Rewinding of the HT windings ofthe following ratings Oil immersed Distributionclass Transformerwith superior grade andsuitable size Double paper coveredTransformer winding conductor , providingre-insulation of LT winding etc. includingdismantling the transformer parts i.e. conservator tank, terminal boxes, bushings, removing the core and windings from the tank, draining of transformer oil, cleaning of tank,reassembling the core & windings and all the aforesaid parts after rewinding/repairing, replacement of gaskets, worn out nuts, bolts and washers/cork washers etc, heating in heat chamber, carry out factory testsand submission of test reportsetc.complete as required. (The dismantled aluminium winding and other materials can be retained by the agency and credit for the same to be given in the quoted rate of this item)
3525 KVA, 11KV/0.415KV, 50 Hz Aluminium wound oil cooled Transformer
3663 KVA, 11KV/0.415KV, 50 Hz Aluminium wound oil cooled Transformer
37100 KVA, 11KV/0.415KV, 50 Hz Aluminium wound oil cooled Transformer
38Supplying and pouring of transformer oil (IS:325) of suitable make & grade for topping up/replacement of old deteriorated oil etc. complete as required.
39Filtration and de-hydration of existing Transformer oil at factory / work shop ( In case of rewinding/repairing of Transformer at factory / workshop), testing of BDV and submission of oil testing reportetc. as required.
40Replacement of the following defective spare parts ofthe transformerby new one i/c fitting, connectionetc. as reqd.
41HV Bushings
42LV Bushings
43Painting of the transformer body with primer & two coats of weather proofsynthetic enamel paints after scrapping the rust etc complete as reqd.
44Providing 25 KVA/63 KVA 11KV/0.415 KV Distribution class star rated Transformer on hiring basis as a stop gap arrangement etc. as required. (BSNL will not be held responsible for occurrence of any faults in the hired Transformer while working at site or any damage or loss occurred to the said Transformer during transportation, loading, unloading and negligence of the agency etc.). (Commencement date shallbe the date of energisation and commissioning at site)
45Making arrangements for inspection and testing of the re-winded transformer by the designated inspector of supply company at factory / workshop and obtaining test certificates and clearance for re-installation and energisation of the said transformer etc. complete as required.
46Transportation of spare/new/repaired/standby 25/63 KVA transformer from BSNL office /factory /workshop to respective sites and faulty Transformer from sites to back by using suitable transportation medium including loading and unloading at both ends etc. complete as required. (The rate should be inclusive of toll gate fee/charges wherever applicable, nothing extra will be paid. Distance will be on shortest route only).
47Distanceup to and including 50 KMs (Up and Down)
48Distanceabove 50 KM and up to and including 100 KMs (Up and Down)
49Distanceabove 100 KM and up to and including 150 KMs (Up and Down)
50Distanceabove 150 KM and up to and including 200 KMs (Up and Down)