Name of Work:Construction of UGR &Firefighting system of Panthanivas Puri.
Sl. No. Item Description
1UGR
2Earth work in oridinary soil within 50m, initial lead and 1.5m, initial lift including rought dressing and breaking clods to maximum 5cm to 7cm and laying in layers not exceeding 0.3m in depth and as per direction of Engineer-in-charge.
3Filling foundation trenches and plinth with excavated earth including laying the earth in layers not exceeding 23.5cm (9”) thick ramming and watering with all leads and lifts including cost of all labour, T&P etc. complete as directed by the Engineer-in-charge.
4Disposal of excess earth by mechanical means / manually including cost of loading, unloading, transporting & spreading to a level surface complete in all respects including cost of all labour, tools & plant etc. to complete the work.
5Upto 10 KM
6Supplying, filling in foundation and plinth with sand including watering and ramming with cost, conveyance, royaltiesof sand with labour and T&P required for the work etc. complete (Measurement will be taken on finished compacted section only).GROUND FLOOR
7Providing & layingPlain Cement concrete (PCC )of proportion (1:4:8) in foundation and floors using 4cm (1½”) size clean hard black crusher broken granite stone metal of approved quality and from approved quarry including hoisting, lowering and laying concrete in layers not exceeding 15 cm. (6”) thick to the required level ramming, watering, curing etc. complete including cost, conveyance, royalties and ,es of all materials with all labour, cess and T&P required for the work etc. complete in all respect.
8R.C.C. work of Grade- M 25 in following works using20mm size & down graded hard black crusher broken granite stone chips of approved quality from approved quarry in specified proportion includingcentering & shuttering,hoisting, lowering, laying and compacting concrete, watering and curing and finishing the exposed surfaces smooth with cost, conveyance, royalties of all materials with all labour and T&P required for the work etc. complete in all respect as per the direction of engineer incharege but excluding the cost and conveyance of HYSDrods or Tor steel and binding wire of 18 to 20 gauge and labour charges for straightening, cutting, bending, binding and tying the grills and placing in proper position.
9GROUND FLOOR
10Raft
11Wall
12Roof Slab
13Reinforcement for RCC work including straightening, cutting, bending, placing in position HYSD and binding all complete. lifting and placing in position as per design complete including cost of bars , binding wires , including cost of all materials, labour, conveyance, loading and unloading,, royalties, sundries, tools and plants, etc. complete as per the direction of the Engineer-in-charge. (linear measurement will be taken and quantity will be calculated on standard weight for all heights)-Thermo Mechanically Treated bars
14GROUND FLOOR
15Providing and fixing on wall face unplasticised Rigid PVC soil, waste and rain water pipes conforming to IS: 13592 Type A, including jointing with seal ring conforming to IS: 5382, leaving 10mm gap for thermal expansion, (i) Single socketed pipe.
16110 mm dia PVC (SWR) pipe Class ‘A’ (with wall thick of 2.20 mm to 2.70 mm)
17Providing and fixing SFRC Main hole cover of size 800x800mm
18FIRE PUMPROOM EQUIPMENT
19SITC of Electrical Motor Driven Fire Hydrant Pump of Capacity 1620 LPM, 56 mtr head, with30 KW/40 HP, 2 Pole IE2 motor, Cast Iron Body, bronze impeller, Carbon steel shaft(C-45), fitted with Gland Packing, base frame, coupling, coupling guard etc complete set, as per technical data sheet enclosed. Pump shall be capable of furnishing not less than 150% of rated capacity at a head of not less than 65% of the rated head. The shut off head shall not exceed 120% of rated head Make : KIRLOSKAR/Willo/KSB/LUBI SCOPE OF SUPPLY : PUMP + MOTOR + BASE PLATE + COUPLING etc. completeas per direction of Engineer-in-charge.
20Supply, erection, testing & commissioning of electrical motor driven Jockey pump of horizontal centrifugal end suction back pull out type with gland packing and capable to deliver 180LPM at 56MWC.The pump shall be coupled to TEFC motor of suitable HP with speed of 2900RPM and complete set shall mounted on common base frame.KIRLOSKAR/Willo/KSB/LUBI etc. completeas per direction of Engineer-in-charge.
21Supply, installation, testing & commissioning of Diesel Engine Driven Horizontal End Suction back pullout type Fire Pump of Capacity 97 m3/hr, 56 mtr head, with 42 HP Radiator Cooling Diesel Engine, 1800 RPM Cast Iron Body, bronze impeller, Carbon steel Shaft(C 40), fitted with Gland Packing, base frame, coupling, coupling guard etc , but without Battery, as per Technical Data Sheet enclosed. Pump shall be capable of furnishing not less than 150% of rated capacity at a head of not less than 65% of the rated head. The shut off head shall not exceed 120% of rated head IRLOSKAR/Willo/KSB/LUBI SCOPE OF SUPPLY : PUMP + ENGINE + BASE PLATE + COUPLING etc. completeas per direction of Engineer-in-charge.
22Supply, installation, testing and commissioning of fire control panel metal clad type suitable for 415 V AC three phase 4 wire 50Hz supply system. The panel shall be suitable for automatic operation ofthe fire pumps as per the specified parameters.The panel shall becompletely compartmentalised and complete with relays, contactors, starters, Aluminium Bus Bars, designation labels as per requirement, continuous earth bar, panel separators,protective screens, cable clamping support system,top/bottom cable gland plates forincoming and out going cable entries etc. completeas per direction of Engineer-in-charge.
23Supplying, laying,testing & commissioning of FRLS, XLPE insulated, PVC outer sheateh, steel armoured, aluminium / copper conductor, 1100v grade power cables with glands etc. The cables shall be laid in tray / Hume pipe / in trenches/on walls/ floor etc. as required. For cables laid out door the rate shall include earth excavation providing brick and sand protection, refilling and compacting the earth.The rate shall excludes tray & Hume pipes. The quoted rate shall includes the end terminationfor 1.1KVcableswith double compression type cableglandandheavydutytinned copper cable sockets as per the relevant IS standards.Rate shall be inclusiveof allsundrymaterials like adhesivetape , PVC sleeves , boltsandnuts, washers etc. including plugging unusedholes. Above 10 mm² shall be aluminium conductor type. The minimum size of the cables shall as mentioned below, Make/Plltcab/Gloster etc. completeas per direction of Engineer-in-charge.
243C x 35 sq.mm
253C x 16 Sqmm.
262 C x 2.5 Sqmm. - 6 Run
272 C x 1.5 Sqmm.
283 C x 10Sq.mm
29PUMPING SYSTEM
30Supplying and fixing of perforated G.I.sheet cable tray with neccessory angle iron suspension supports, anchor fasteners etc. complete. Maximum height of suspension shall not exceed 500 mm.Size of the tray shall be suitable for laying the above mentioned cables etc. completeas per direction of Engineer-in-charge.
31G.I. Earthing strips of 50mm x 6mm thick, strip shall be run on floor / ceiling / walls, from the equipment to the nearest Earth pit with necessory accessories as required. ( Erath pit shall be executed by other agencies) etc. completeas per direction of Engineer-in-charge.
32Supply, installation, testing and commissioning of GI Pipeconforming to IS:1239-Make Jindalwith all accessories etc. completeas per direction of Engineer-in-charge.
33200mm nominal dia
34150mm nominal dia
3580mm nominal dia
3625 mm dia
37Supplying, installing, testing and commissioning of C.I. waffer type Non-return valves( PN 16 ) swing check type with required flanges, nuts, bolts and gaskets etc. complete..Make.Kartar/Sant/Zoloto etc. completeas per direction of Engineer-in-charge.
38150 mm nominal dia
3980mm nominal dia
40Supplying, installing testing and commissioning of Cast Iron Body flanged Y-type Strainer with SS screen complete with suitable flanges, nuts, bolts, gaskets etc. complete..Make.Kartar/Sant/Zoloto etc. completeas per direction of Engineer-in-charge.
41150 mm dia
42100mm dia.
43Supplying, Installing, testing and commissioning C.I.butterfly valves as per BS 5155 slim seal standared lever operated type with required flanges, nuts, bolts etc. complete..Make.Kartar/Sant/Zoloto etc. completeas per direction of Engineer-in-charge.
44150mm nominal dia
45100mm nominal dia
4680mm nominal dia
4750mm nominal dia
48SITC of C.I flanged foot valve with suitable flangers, nuts, bolts, gaskets etc. complete. ISI (Kartar) etc. completeas per direction of Engineer-in-charge.
49150mm dia
5080mm dia
51Supplying, installing, testing and commissioning of Gun metal chrome finished Ball valves with fittings of screwed end type..Make.Kartar/Sant/Zoloto etc. completeas per direction of Engineer-in-charge.
5225 mm nominal dia
5315 mm nominal dia
54SITC of Priming Arrangement for above pump etc. completeas per direction of Engineer-in-charge.
55Supply and installation testing and commissioning of differential Pressure switches of suitable range (0 to 12 bar) for pumpsets complete with necessay Ball valves, Fittings like unions / colors / reducers etc.Make H-Guru etc. completeas per direction of Engineer-in-charge.
56Supply and installation testing and commissioning of Pressure gauges of suitable range (0-16 bar), 100 mm diameter dial for pumpsets completes with necessary Ball valves, siphon, Fittings like unions / colors / reducers etc.Make.danfoss/ etc. completeas per direction of Engineer-in-charge.
57Structural steels as requited for pump House str. Like Uclamp, Angel, Achor bolt, Not bolt washer, Ms angel etc to system complete for wet-riser system etc. completeas per direction of Engineer-in-charge.
58Supply, fixing, testing and commissioning of air vessel tank shall be fabricated out of of 200 mm dia MS pipe to 2000 mm long complete with 25mm inlet, 25mm drain,25mm dia connection for air release valve including legs, painting with red oxide primer and finished with fire red enamel paint. It shallbe inclusive of all relevant pipes, valves, specials upto pump headerand other accessories etc. completeas per direction of Engineer-in-charge.
59Exhuast pipe for Diesel engine of 80 mm dia M.S. Medium grade with mineral wool insulation with aluminum sheet. The quoted rate shall include 100 mm diameter MS pipe medium grade conforming to IS 1239 Part-1 and mineral wool insulation with aluminum sheeting and Pipe supports also etc. completeas per direction of Engineer-in-charge.
60Supplying, installing, testing and commissioning of electrical motor driven Booster pump of Monoblock type capable to deliver 450LPM at 35MWC.The pump shall be coupled to TEFC motor of suitable HP with speed of 2900RPM and complete set shall mounted on common base frame. Make.Willo/Kiloskr/KSB etc. completeas per direction of Engineer-in-charge.
61R.C.C. Pump foundation for Terrace Pump - DONE BY CLIENT 10000 Litter capacity Water Tank on Terrace floor
62Control Panel for Fire pumps. Providing and fixing dust and vermin proof motor control panel fabricated from 14 SWG MS sheet with stove enamelled paint and comprising of: (for Fire Booster pump automatic operation ) etc. completeas per direction of Engineer-in-charge.
63WET RISER SYSTEM
64Supply, installation, testing and commissioning of GI Pipeconforming to IS:1239-Make Jindal/tata with all accessories etc. completeas per direction of Engineer-in-charge.
65100mm nominal dia
6680mm nominal dia
67SITC of Single headed hydrant valve as per IS 5290, made of SS with 63 mm dia instantaneous outlet of 80 mm dia fanged inelt ,Blank caps , chain and hand wheels etc complete.Make.Kartar/Sant/Zoloto etc. completeas per direction of Engineer-in-charge.
6815 M long, 63mm dia RRL hose conforming to IS 636 Type A with SS instantaneous couplings and Hoses shall be stored inside fire Hose Box. Make.Kartar/Sant/Zoloto etc. completeas per direction of Engineer-in-charge.
69SITC of 1 no. S.S short branch pipe with nozzle. Make.Kartar/Sant/Zoloto etc. completeas per direction of Engineer-in-charge.
70SITC of First aid Hose reel drum of 180° swinging type with 19mm dia Rubber braided hose of 30M. length with Ball Valve and 6mm diameter Shut off nozzle, complete. The hose reel shall conforming to IS 884 Make.Kartar/Sant/Zoloto etc. completeas per direction of Engineer-in-charge.
71SITC of M.S. Hose Box wall mounted type fabricated out of M.S. sheet of 16 swg. with glass fronted ( 4mm thick glass with rubber beeding) door and size of the cabinet shall be 750mm x 600 mm x 250 mm Quoted rate shall be includes suitable stand for mounting, all fasteners etc, and cabinet shall be powder coated of approved colour both inside and outside. Make.Kartar/Sant/Zoloto etc. completeas per direction of Engineer-in-charge.
72Supplying, installing and commissioning of fire brigade inlet connection of4 way with each of 63 mm dia. built - in Gun metal instantaneous coupling type arranged on 150 mm dia.Make.Kartar/Sant/Zoloto etc. completeas per direction of Engineer-in-charge.
73Supplying and fixing approved make of 25mm dia automatic air release valve spring loaded type complete with unions etc. complete.Make.Kartar/Sant/Zoloto etc. completeas per direction of Engineer-in-charge.
74Structural steels as required like U clamp, Angel, Anchor bolt, Not bolt washer, Ms angel etc to system complete for wetriser system etc. completeas per direction of Engineer-in-charge.
75Providing and Fixing of 4.5 Kgs. Capacity CO2 gas type ISI marked fire extinguisher (IS: 15683) fitted with high pressure 1 mtr. Long discharge hose & horn complete with refill gas, carrying handle and wall mounting bracket etc as required.make. Minimax/Ceasefire etc. completeas per direction of Engineer-in-charge.
76Providing and Fixing ISI marked ABC stored pressure type Fire extinguisher of 6 Kgs. Capacity confirming to IS: 15683 with discharge hose, nozzle, Mono Amonium Phosphate base & ABC powder pressurised with nitrogen gascarrying handle and wall mounting bracket etc as required.make. Minimax/Ceasefire/Intime etc. completeas per direction of Engineer-in-charge.
77Fire buckets round bottom type enamel painted, white inside & Red out side and Letter "FIRE" in black out side and handle with mounting bracket etc. completeas per direction of Engineer-in-charge.
78Fire bucket stand fabricated by MS angles to install 2 Nos. of buckets etc. completeas per direction of Engineer-in-charge.
79AUTOMATIC FIRE DETECTION AND ALARM SYSTEM
80Supply, Installation,Testing & Commisioning of 4 Loop Panel Microprocessor based Addresable fire alarm control panel , fully networkable with each loop capable of taking 99 devices, 8 line x 40 character alpha- numeric liquid crystal display .The panel shall be soft addressable type . The panel shall be able to give pin point location of all fire/fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered. The panel shall have integral SMF lead acid batteries with sealed cells of 24 V capable of running for a minimum of 8 hours with integral battery charger complete as required and as per specification. The fire alarm panel shall be suitable for software integration with BMS & PA system.Make.Honywell/Edward/Notifire etc. completeas per direction of Engineer-in-charge.
81Supplying, installing, testing and commissioning of Addressable Manual Call Point with back box..Make Honeywell Morely,Bosch,Notifire,Edward as per direction of Engineer-in-Charge.Make.Honywell/Edward/Notifire etc. completeas per direction of Engineer-in-charge.
82Supplying, installing, testing and commissioning of Analogue Addressable Loop powered Sounder with strobe light .Make Honeywell Morely,Bosch,Notifire,Edward as per direction of Engineer-in-Charge.Make.Honywell/Edward/Notifire etc. completeas per direction of Engineer-in-charge.
83Supplying, installing, testing and commissioning of Multi criteria smoke detector with base, junction box and other accessories.Make Honeywell Morely,Bosch,Notifire,Edward as per direction of Engineer-in-Charge.Make.Honywell/Edward/Notifire etc. completeas per direction of Engineer-in-charge.
84Supplying, installing, testing and commissioning of rate of rise heat detector with base, junction box and other accessories.Make Honeywell Morely,Bosch,Notifire,Edward as per direction of Engineer-in-Charge.Make.Honywell/Edward/Notifire etc. completeas per direction of Engineer-in-charge.
85Supplying, installing, testing and commissioning of 2C x 1.5 mm², armoured, single stand, outer sheathed, FRLS, PVC insulated copper conductor cable confirming to specified IS standards . Make. Polycab/Gloster/Kei etc. completeas per direction of Engineer-in-charge.
86EMERGENCY EVACUATION SYSTEM/PUBLIC ADDRESS SYSTEM
87Supplying, installing, testing and commissioning of 6 Watt wall mounted speakers with built in line matching transformer, grill flush mounting type in side the utility rooms.Make. Honywell/Bousch etc. completeas per direction of Engineer-in-charge.
88Supplying, installing, testing and commissioning solid state Compact Mixer Amplifier with 5 Zone remote paging microphone including necessary control wires, jocks etc. complete.Make. Honywell/Bousch etc. completeas per direction of Engineer-in-charge.
89Supplying, installing, testing and commissioning of 19" Rack 650mm depth, 17 U high amplifier rack assembly made of aluminum channel equivalent to euro rack system, with side and rear panels made of 14 swg powder coated sheet steel front transparent persplexdoor and with rails, rollers & bearings. Fans shall provided at the top for ventilation side panels will be ventilated type. The rack shall be powder coatedof approved color and spare "U" shall be covered with blank panels.Make. Honywell/Bousch etc. completeas per direction of Engineer-in-charge.
90Supplying, installing, testing and commissioning of 2 Core x 1.5 Sq.mm Twisted Pair PVC insulated FRLS unarmored Cable with Accessories confirming to IS standards and specifications. Make/Polycab/Gloster/KEI etc. completeas per direction of Engineer-in-charge.
91Supplying, installing, testing and commissioning approved make PVC FRLS conduits on ceiling / wall / floor etc. complete with accessories like, Junction boxes, Collars, Bends etc. completeas per direction of Engineer-in-charge.
9220 mm dia.
93Supplying, installing, testing and commissioning approved make 20 mm dia.PVS FRLS flexible conduits on ceiling / wall / floor etc. complete with accessories like, Junction boxes, Collars, Bends etc. completeas per direction of Engineer-in-charge.
94Providing and installing in position the following tupe of sign boards made out of 3mm thick "Opaque" PVC foam board with computer cut. PVC non-reflective self adhesive vinyle painted foam board, complete with mirror fasteners etc. completeas per direction of Engineer-in-charge.
95Signages with printed "IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED OTHERWISE" of 1.5cm height letters in red with white back ground. The size of the board shall be 25cm * 30cm and shall be fixed at the height of 2mts, from finished floor near Manual Call Points etc. completeas per direction of Engineer-in-charge.
96Floor identification signage (i.e, GROUND FLOOR… ETC.,) at each stair enclosure on every floor, indicating the floor number in words, lettering size shall be 7.5cm with contrasting colour from back ground. Size shall be 15cm * 60cm etc. completeas per direction of Engineer-in-charge.
97Fire Exit signageat each stair on every floor, indicating the direction of fire exit, lettering size shall be 7.5 cm with contrasting color from back ground. Size shall be 15cm x 60cm etc. completeas per direction of Engineer-in-charge.
98Providing and fixing in position the signage of " Incase of fire do not use Lift Size 8" x 8" etc. completeas per direction of Engineer-in-charge.
99Providing and fixing in position the signage of " Fire Extinguisher " to be pasted immediately above the every extinguisher.Size 6" x 8" etc. completeas per direction of Engineer-in-charge.
100Testing and Commissioningwith proper management of entire Fire fighting system etc. completeas per direction of Engineer-in-charge.