Tender For Supply, Installation, Testing, Commissioning Of Hvac Work At District Hospital Mandore (3Rd To 5Th Floor Ccu), Jodhpur, jodhpur-Rajasthan

Rajasthan State Road Development And Construction Corporation Limited has published Tender For Supply, Installation, Testing, Commissioning Of Hvac Work At District Hospital Mandore (3Rd To 5Th Floor Ccu), Jodhpur. Submission Date for this Tender is 09-10-2023. HVAC Tenders in jodhpur Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

39993921
Tender For Supply, Installation, Testing, Commissioning Of Hvac Work At District Hospital Mandore (3Rd To 5Th Floor Ccu), Jodhpur
Open Tender
Indian
Rajasthan
jodhpur
09-10-2023

Tender Details

Tender For Supply, Installation, Testing, Commissioning Of Hvac Work At District Hospital Mandore ( 3Rd To 5Th Floor Ccu ) , Jodhpur

Key Value

Document Fees
INR 1180 /-
EMD
INR 160000.0 /-
Tender Value
INR 80 Lakhs /-

BOQ Items

Name of Work: SITC of HVAC work at District Hospital Mandore (3rd to 5th floor CCU), Jodhpur
Sl. No. Item Description
1Supply, Fabricating & installing following sizes of powder coatedperforated M.S. cable trays including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with M.S. suspenders, fastners, supports etc. as required.
2200mm x 62.5mm x 2.0mm
3450mm x 62.5mm x 2.0mm
4600mm x 62.5mm x 2.0mm
5Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as requiredcomplete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
6Supply,Installation, Testing & Commissioning of modular type VariableRefrigerantFlow/VariableRefrigerantVolumeaircooled Outdoorunitssuitable for cooling and heating,having100% hermetically sealed inverter type Scroll Compressor(s) withand minimum two compressors along with two Condensing fan,above 14/18 HPmodules,microprocessorbased Controller, Side / top discharge type condensing unit(s), with R-410 A Refrigerant,vibrationisolators,withsuitablefoundationetc. completeasrequired.Theunitshalldelivertheratedcapacityat AHRIConditions andwork evenat 50°C ambient temperature without tripping.The unit shall be suitable to work on 400V +/- 10%, 3Phase,50HzACpowersupply.Theunit shallbefilledwithfirst charge of the refrigerant and ready for use as required. The EER at 100% load with AHRI conditions shall not be less than 3.5 andIncluding OEM supplied Piping connection Kit etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
7Supply,installation,testingandcommissioningoffollowing minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor,coilsection with DXCoppercoil,electronicexpansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation,Cordedremotecontroletc., suitableforoperationon single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down valve in case of fire on receivingsignalfromBMSSystem. Thecoolingcapacityofindoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
8Ceiling Mounted4 Way Cassette type Units with Remote Control
90.8 TR
101 TR
111.2 TR
121.6 TR
132.4 TR
143.2 TR
154 TR
16Supply, installation, testing & commissioning of Group controller for monitoring the status and working condition of all indoor and outdoor units, The controller shall act as an advanced air conditioning management system to given complete control of VRV/VRF air conditioning equipment with Starting/stopping of air-conditioning as a zone or group of individual units. Temperature setting for each Indoor units of zone, Switching between temperature control modes, switching of the fan speed and direction of airflow, enabling/disabling of individual remote controller operation, Alarm code display in case of any problem. It shall be able to control up to 64 (max. 512 if required) number of Indoor units. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
17Supplying and installation of high-pressure grade required size OEM make copper connectionY or T Joints / refnet for liquid and suction line complete erected on wall/ceiling with supports/raceways, Nitrile rubber insulation, painting etc. with brazing and testing for leakages confirming the normal operation of the VRV / VRF air conditioning system. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
18Refrigerant Piping
19SITC of Interconnecting refrigerantcopper pipe forsplit/Ductable/ Casseette AC of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink MarkBrand Printing on Hard Tubes should be present. Piping between each set of indoor & outdoor units of different sizesas per OEM requirement & specifications including class "O" Nitrile rubber sleeves, chase cutting, supports, making good the same with sand cement plaster etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
20Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping withfittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing,support with MS hanger on ceiling or recessed in wallwith chasing & plastering with 6 mmthickclosedcellelastomeric nitrile rubberinsulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
2125 mm
2232 mm
2340 mm
24Supply & Laying of ISI marked Copper conductor shielded control cum transmission cable in PVCconduit for looping between indoor & outdoor VRV system & to main Central remote controller system.Make Copper wire - Finolex / Polycab /KEI / R R kable.PVC Conduit - Precision / AKG / BEC / RICHA.
252C X 1.5 Sq. mm
26Gas charging of VRF/VRV system with R410A refrigerant gas. Before gas charging system shall be flushed with high purity Nitrogen Gas to remove carbon content, dirt particles to make sure that there is no chance of mixing any impurity with Refrigerant Gas. Thereafter System shall be tested with Nitrogen Gas at 1.5 Times of working pressure of R410 Refrigerant Gas to ensure leakproof system. Whole system shall be Vacuumed up to 500-micron level which ensures the zero-moisture content level in piping to ensure better cooling efficiency and long life of the system. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .