Tender For Repair/Maintenance Of Fire Fighting And Fire Alarm System At Af Stn Halwara, halwara-Punjab

Military Engineer Services-MES has published Tender For Repair/Maintenance Of Fire Fighting And Fire Alarm System At Af Stn Halwara. Submission Date for this Tender is 25-10-2023. Alarm Systems Tenders in halwara Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

39863556
Corrigendum : Tender For Repair/Maintenance Of Fire Fighting And Fire Alarm System At Af Stn Halwara
Open Tender
Indian
Punjab
halwara
25-10-2023

Tender Details

Tender For Repair/Maintenance Of Fire Fighting And Fire Alarm System At Af Stn Halwara

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 18-Oct-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 25-10-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 76000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work : REPAIR/MAINT OF FIRE FIGHTING & FIRE ALARM SYSTEM AT AF STN HALWARA
Sl. No. Item Description
1Preventive and comprehensive maintenance of complete fire fighting, detection and alarm system(s) installed at multistory MAP Qtr and Technical area in reliable, safe and efficient manner using latest techniques & expertise consultancyby regularly examining the sensor/detector, Main fire alarm control panels, Repeater panels, Hooters, MCP, Sirens pump motor, alarm system, examining leakage, various valves including damage/repair replacement etc of various type / capacity / make, including making the non-functional parts of fire alarm system into fully functional condition, attending day to day complaint / fault(s) in general shift of 08 hrs every day including Sunday & Holiday, including quarterly cleaning of the detectors and monthly joint testing/inspection of the complete fire alarm system, including replacement of minor items such as wires, lugs, nut, bolts, screws, electronic circuit,including minor items complete all as specified and directed by Engr- in- charge. Note : (i) The contractor will have to employ minimum 01 No of Fire technician (ITI Technician) & 01 No Pipe fitter (ITI pass, Semi-skilled) every day including Sunday and holiday to attend day to day complaints as well as periodical / routine maintenance and joint inspection / testing of fire fighting, detection and alarm system(s) installed at various locations / areas and maintain a register which is to be countersigned by JE I/C and also submit the feedback on daily basis to the Engineer-in-Charge/ concerned JE E/M. Weekly off to the workers shall be given and in place reliever of the same qualification shall be provided as per labour law & cost deemed to be included in qouted rates. (ii) The tradesmen/Technician (s) should be having ITI qualified withminimum 3 years work experience of respective trade. (iii) In case, additional manpower other than mentioned here-in-above, will be required for smooth functioning of fire alarm system or attending day to day complaints or periodical / routine maintenance or joint inspection / testing of fire alarm system(s) installed at various locations / areas, the contractor shall arrange the same without any extra cost to Deptt. (iv) The comprehensive / preventive / periodical maintenance includes monthly joint inspection / testing of entirefire fighting, detection and alarm system(s), in presence of representative of user. The joint inspection / test report duly signed by contractor, user representative and MES representative will be submitted along with each RAR/payment. If contractor fails to complete the joint inspection / testing of fire alarm system(s), the compensation / penalty of Rs. 1000.00 (Rupees One Thousand only) per day shall be recovered from the contractor’s dues. (v) The complete existing fire alarm system(s) will be handed over to contractor in present condition and no claim on this effect will be accepted at any stage. Hence, the bidder is advised to visit the site to assess the quantum of work to be carried out in this contract and quote their rates accordingly. (vi) The cost of all kind of repair /servicing/ replacement of defective equipment/devices and other minor parts/spares or cell/ batteriesas and when required for making the entire fire alarm system(s) fully functional, is deemed to be included in quoted rates and no extra cost shall be paid to the contractor on this effect. However, the Cost of majorequipment / devices shall be measured & paid separately under relevant item of this Schedule/BOQ. (vii) All the complaint / fault (s) will be attended within 02 hrs from the time of receipt of complaint. If, contractor or his tradesmen fails to attend the complaint within 02 hrs from the time of receipt of complaint verbaly or telephonically, the compensation/penalty of Rs. 500.00 (Rupees Five Hundred only)per complaint per hr for first 04 hr and after that Rs. 1000 (Rupees one thousand only ) per complaint each day (i.e 24 hrs ) shall be recovered from the contractor’s dues. (vii) The contractor shall provide all the necessary T&P, uniform and stationary such as Attendance Register, Periodical Maintenance Register, logbook etc to the technician without any extra cost to Deptt. (ix) The following documents to be produced for monthly payment:- (a) Monthly testing report of all fire hydrant duly signed by user, MES rep & contractor. (b) Serviceability of pump sets signed by rep of MES & Engr-in-charge. (c) Serviceability test report of all fire alarm system duly signed by user, MES rep & contractor. (d) The attendance register for workers is to be maintained by JE E/M and to be produced to Engr-in-charge weekly for countersigned . Absentees if any will be penalised at the rate of Rs. 2000/- per day per person.Photo copy of Attendance register will be submitted alongwith each RAR/Final bill.
2Excavation in trenches n.exc 1.5m wide and 1.50m in depth for laying of electric cables or for poles and stay or for laying pipes (where provided for protection of cables) and getting out, trimming the sides forming bottom surface to required level in soft/loose soil complete all as specified and directed by Engineer-In-Charge .
3Returning , filling in , including spreading , leveling, watering and well ramming in layers not exc 25 cm in soft/loose soil complete all as specified and directed by Engineer-In-Charge .
4Removing excavated material n exc. 50m and depositing where directed at a level not exc 1.50m above the starting point complete all as specified and dircted by Engineer-In-Charge .
5M&L in repair/ replacement for hose box made of 18 gauge MS sheet 800mm X 600mm X 250mm,double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet duly painted with fire red colour out side and brilliant white inside yard including takingdown old unserviceable item complete all as specified and as directed..
6Supply and fixing in repair/ replacement of canvas hose pipe suitable for fire hydrant of 63 mm bore , 15 mtr long with coupling made out of brass and nozzle of size 63 mm to 20mm dia as per bureau of indian standards including takingdown old unserviceable item complete all as specified and directed by Engr-in- Charge.
7M&L inrepair/ replacement for Yard hydrant post /stand post made out of 80 mm dia GI/MS both flanged type 1.5 M height complete including takingdown old unserviceable item complete all as specified and as directed.
8Supply and fixing inrepair/ replacement of fire hydrant landing valve type `B` (single/ double head outlet) 63 mm dia confirming to IS-5292 including takingdown old unserviceable item complete all as specified and as directed.
9Supply and fixing inrepair/ replacement of branch pipe gun metal 63 mm instantaneous 15 mm bore nozzle long type confirming to IS-903 including takingdown old unserviceable item complete all as specified and as directed.
10Supply and fixing in repair/ replacement of alarm/sounders/sirens elctronic type horizontal single stage continuos normal opeation for at least 50 minutes with sound level 65DB to 120 DB measured at 1.5 mtr with sound out put variation of + 5 DB 500 mtr range including takingdown old unserviceable item complete all as specified and directed.
11Taking out of unserviceable CI/GI/MS pipes 25mm bore (including all fittings) with spigot and socket ends and lead joints including burnt out joints with welding complete all as specified for the following sizes :-(Note :- Excavation and earth work will be measured and paid separately.)
12All as per Srl item No. 11.00 above but 80 mm bore
13All as per Srl item No. 11.00 above but 100 mm bore
14All as per Srl item No. 11.00 above but 150 mm bore
15All as per Srl item No. 11.00 above but 200 mm bore
16All as per Srl item No. 11.00 above but 250 mm bore
17All as per Srl item No. 11.00 above but 300 mm bore
18Supply , laying , jointing and testing in trenches , alongwith walls and column 25 mm bore GI pipe flanged heavy class with all fitting in complete all as specified and as directed.
19All as per srl item No. 18 above but 80 mm bore .
20All as per srl item No. 18 above but 100 mm bore .
21Laying and fixing 100mm bore existing centrifugally cast (Spun) ductile iron pressure pipes for water with socket and spigot ends suitable for rubber gasket pushon joining confirming to IS 8329:2000 having inside cement mortar lining and outside zinc coating with finishing layer of blue epoxy in standard length, classification K9 in standard length of 5.50/6.0 mtrs including push on joint with cement mortar lining complete all as specified and directed
22All as per Srl item No. 21.00 above but 150 mm bore
23Supply, fixing & testing ofMS ERW pipe of size 80mm bore as per IS- 1239 Part-1I including all accessories such as flanges, tees, bends, ruducers jointing with welding, nuts and bolts and painting with two coat of first quality enamel paint on pipe exposed to suface and anticorrosive treatment with one coat of bitumen followed by wrap pinning with bitumen hessian cloth complete all as specified and as directed.
24All as per Srl item No 23.00 above but 100mm bore
25All as per Srl item No 23.00 above but 150mm bore
26All as per Srl item No 23.00 above but 200mm bore
27All as per Srl item No 23.00 above but 250mm bore
28All as per Srl item No 23.00 above but 300mm bore
29Supply, fixing & testing of Air Vessel (Air cushion tank) 250mm x 1000mm high with dished top made of minimun 6mm thick MS pipe/plate complete with 20mm dia brass Air valve (ball type), 20mm dia stop valve, pressure gauge with brass stop cock, nipple, tress, elbows and all necessary connection including takingdown old unserviceable item complete all as specified and as directed.
30Supplyand fixingin repair/ replacement of cast iron sluice valve heavy dutyclass PN-1.6 conforming to IS 14846-2000with flanged ends 80 mm dia ISI marked complete with gun metal or stainless steel spindle and cast iron hand wheel including rubber /fiber board gasket nuts, washers etc,suitable for fire fighting pressurised pipe lineincluding necessary excavation, returning and filling including takingdown old unserviceable item complete all as specified and as directed.
31All as per Srl item No 30.00 above but 100mm dia
32All as per Srl item No 30.00 above but 150mm dia
33Supply & fixing in repair/ replacement of cast iron butter fly valve with Nitzile rubber ISI Marked PN 1.6 confirming to IS:13095 of size 80 mm dia including takingdown old unserviceable item complete all as specified and as directed.
34All as per Srlitem No 33.00 above but 100mm dia
35All as per Srl item No 33.00 above but 150mm dia
36Supply, fixing & testing of 80 mm dia cast iron reflux valve double Air/ single air (non return valve) heavy duty with gun metal seat, both ends flanged joint complete with nuts,bolts and washers confirming to IS:780 ISI marked including takingdown old unserviceable item complete all as specified and as directed.
37All as per Srl item No 36.00 above but 100mm dia
38All as per Srl item No-36.00 above but 150mm dia.
39Supply, fixing & testing of fire Brigade inlet valve connection of 2 way ,63 mm dia instantaneous type male couplings with non return valve and sluice valve including nuts,bolts & rubber insertions as required including takingdown old unserviceable item complete all as specified and as directed.
40Supply, fixing & testing of fire Brigade inlet valve connection of 4 way ,63 mm dia instantaneous type male couplings with non return valve and sluice valve including nuts,bolts & rubber insertions as required including takingdown old unserviceable item complete all as specified and as directed.
41Supply,fixing & testing of pressure gauge of size 100mm with isolation cock suitable for a working pressure of 14kg / Sqmm rating along with stop cock with all accessories including takingdown old unserviceable item complete all as specified and as directed.
42Supply, fixing & testing of pressure switch universal type alongwith all accessories including takingdown old unserviceable item complete all as specified and as directed.
43Supply & fixing in repair/ replacement offire hose reel drum 30m, wall mounting swining type complete with drum, bracket, gate valve/ stop cock 20mm dia,15/30mtr long high pressure hose reel tubing of Thermoplast Type ll hose conforming to IS12585 with ISI mark with gunmetal shut off nozzle 5mm including takingdown old unserviceable item complete all as specified and as directed.
44Supply & fixing in repair/ replacement of cast iron football valve of size 150mm dia for suction pipe including all necessary connection including takingdown old unserviceable item complete all as specified and as directed.
45Supply, fixing in repair/ replacement of hydrant valve with single outlet/ double outlet, gun metal grade with 80 mm flanged inlet, brass spindle, 63 mm female instantaneous outlet completewith blank cap chain bearing IS:6290 ISI marked (INTERNAL HYDRANT) including ERW pipe of size 80 mm welded to ERW pipe of size 100 mm dia down pipe including takingdown old unserviceable item complete all as specified and as directed.
46Supply installng, testing and commissioning floor mounted LT panel in door type of suitable size cubical type factory made, weather and vermin proof made out of CRCA sheet 3 mm thick and angle iron frame of 40x40x6mm and 04 Nos legs on angle iron 50x50x6mm each 45 cm long panel duly powder coacted heaving insulated bus bar TPN with openable shutter on both side (Front and rear side) with locking arrangement duly pre-wired with suitable size of copper conductor cable with proper size of copper lugs/thimbles,with cable gland and connecting to MCCBs with suitable size copper strip duly bended and fixed with nut & bolts and washers from bus bar to MCCBs and legs grouted in PCC 1:2:4 type B:1 (20 mm graded stone aggregate Powder Coated Spray painted from outside and inside with approved stove enameled grey paint two coats over one coat of red oxide primer including taking out oldunserviceable panel complete as under:- (a)Bus bar chamber comprising 4 Nos copper strip busbar air insulated of capacity 600 Amps with colour coding in separate sheet steel enclosure with front shutter in two halves having lockable arrangement (b)MCCB 415 volts, 400 Amps rating FP with adjustable thermal release for incominh supply with over load, short circuit and earth fault protection of braeking capacity 36 KA- 01 No. ( c) Voltmeter 0-500 volts digital type of size 96 mm x 96 mm square flush mounted complete with selector switch - 01 No. (d)Am-Meter 0-300 Amps digital type of size 96 mm x 96 mm square, flush type, CT operated including CT"s complete - 01 No. (e)LED type indicating lamp panel mounting type of RYB - 01 Set (set of three) (f)MCCB 125 Amps 415 volts, 50 Hz, FP adjustable thermal release with over load & short circuit protection of breaking capacity 25 KA - 02 Nos (g)Automatic DOL starter 3 phase , 415 volts, 50 Hz without overload relay and single phasing preventor feature, ON/OFF ,TRIP, indication lamp, contactors & selector switch for manual /auto ete suitable for 75 HP- 01 No. (h)DOL starter , 3 phase,415 volt,50 Hz with overload & single phase preventor feature, ON/OFF & TRIP , indication lamp, contactors , selector switch for manual/auto etc suitable for 12.5 HP motor - 01 No. (Jockey Pump) (j)Set of control system to make the system automatic as per functional requirements (k)Amp meter 0-150 Amps flush type for main fire pump,Diesel Engine pump motor & jockey pump motor - 03 Nos (l)Wiring with single core PVC insulated conductor FRLS cable of suitable copper conductor cable of suitable size incoming to bus bar and bus bar to outgoing MCCB"s/MCB"s - 01 Job (m)Fine wiring with single core PVC insulated conductor FRLS copper conductor cable, thimbles,lugs etc for instruments / indicating lamps - 01 Job (n)Provision of start the diesel engine fire pump automatically in event of pressure drop beyond preset limit on mains failure or failure of electric driven pump complete all as specified
47Supply & fixing in repair/ replacement of low density polythylene pipe (LDPE) of pressure of rating 6 Kg/Sqcm of size 50 mm dia including takingdown old unserviceable item complete all as specified and as directed.
48Supply and fixing in replacement of brass hydrant male coupling brass 63 mm dia including takingdown old unserviceable item complete all as specified and as directed.
49Supply and fixing in replacement of brass hydrant female coupling brass 63 mm dia including takingdown old unserviceable item complete all as specified and as directed.
50Supply, fixing & testingmanual call point(resettable type) with working voltage 24 volts DC, push button, breakable glass, chain, hammer etc painted with red shade including takingdown old unserviceable item complete all as specified and as directed.
51Supply & fixing inrepair/ replacement of low intensity hooter (Loop powered sounder) operating on single phase 220volts 50 HZ for warning of fire connected with central control panel installed in each zone inside the rooms including takingdown old unserviceable item complete all as specified and as directed.
52Supply & fixing inrepair/ replacement ofDetectors Complying with and type certified to EN - 45 Addressable type smoke detector Photoelectric /Optical with base with selfinbuilt intelligence as per IS: 11360with suitable fixing arrangements including takingdown old unserviceable item complete all as specified and as directed.
53Supply only in replacement optical type multisensor smoke with heat detector supply voltage 9 to 33 V DC, UL/FM/LPCB approved with junction box and base to be fixed with suitable fixing arrangement including takingdown old unserviceable item complete all as specified and as directed.
54Supply. installation, testing and commissioning in replacement flame proof triple sensor UV/IR flame detector with rugged explosion proof and FM/ATEX/PESO approved enclosure UV range 185-260 nm, IR 3000-5000 nmquiescent current < 80 mA separate LED indication for normal and alarm air purging provision protection class IP 66. operating temp 10 Deg C to +55 Deg C, conforming to NFPA 72 E, FM standars class No 3260 and IS code 2189 IP & performance certification by ETDC, Govt of India, LPCB 1259 a/02 approved including takingdown old unserviceable item complete all as specified and as directed.
55Supply and fix in repair/ replacement of microprocessor based automatic fire alarm control panel including supplyand fixingbatterycharger having battery box for 2 loop microprocessor based 2 wire fault tolerent loop , required loop network type (with loop capacity of 240 devices any combination) fire alarm/ detection control panel. The panel shall be able to work automatically switch ON/OFF respective control module wheneverany alarm is triggered. The panel shall have external/inbuilt printer to log all fire or fault events complete in all respect . The Panel shall be sheet steel painted , degree of protectionIP-30 . The panel shall have 20 zone with individual LED indicator, expandable to 80LED indicators. The Panel shall have 3 serial ports including takingdown old unserviceable item complete all as specified and as directed.Make SEIMENS or compatible with the existing system Note : The total No of DC batteries, rating and capacity shall be as recommended by OEM and cost of the same is deemed to be included in the qupted rates.
56Supply & fixing in repair/ replacement of PVC insulated FR LS copper conductor 1.5 sqmm 3 core multi-strandard flexible cable drawing in existing steel conduit /New PVC/ steel conduitincluding takingdown old unserviceable item complete all as specified and as directed.
57All as Srl per item No 56.00 above but 2.5 sqmm 3 core.
58Supply, laying, connecting & testing 1100 volts grade PVC insulated and sheathed aluminium conductor armoured stranded control cable of size 16 Sqmm 3 core fixed on wall/ roof with saddles,clamps etc all as required & directed at site (for Terrace Pump)including takingdown old unserviceable item complete all as specified and as directed.
59Supply, laying and testing only cable XLPE insulated screened PVC bedded , galvanised steel strip of wire armoured , electric power cable (heavy duty) laid in trenches and through ducts with aluminium conductor 1100 volt grade of size 70 Sqmm 3.5 core including testing including takingdown old unserviceable item complete all as specified and as directed.
60Supply & fixing earth continuity of GI wire 4mm thick for connecting the Terrace pump with running earth wire with saddles, clamps etc all as required including takingdown old unserviceable item complete all as specified and as directed.
61Supply, fixing & testing fire alarm system. The panel having 2 Nos of single loop card for detector & modules with extendable type , per single loop card in any flexible combination with alarm & connected accessories for zone. The panel having LCD screen for displaying system status with easy navigable multi function button. The panel shall have 240 volts power supply, automatic battery charger including 24 volts maint free battery as standby and then be capable of operating the system in emergency condition as required including takingdown old unserviceable item complete all as specified and as directed.
62Supply and fix hydrant male coupling brass 63 mm dia
63Supply and fixing brass nozzle for canvas hose 63 mm dia
64Supply and fix canvas hose male/ female coupling brass 63 mm dia
65M&L for preparation of old painting steel surface and applying one coat of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. Note : Colour of paint shall be stricity as per existing colour
66M&L and testing of fire alarm detection panel of any make for major repair to include replacement of defective parts, electronic circuit and software through OEM/ auth/ accredited agency including transportation, taking down, refixing and testing of the panel complete all as directed by Engr-in-charge.
67Supply and fix in repair/ replacement of Volt meter 0-500 volts digital type.
68Supply and fix in repair/ replacement of Amps meter 0-100 Amps digital type.
69Supply and fix in repair indicating amps 22.5 mm dia LED type, 230 V AC to show three phase avallability
70Opening, and disassembling CF pump from electric motor 7.5 HP capacity, including shifting, transportation, overhauling shaft metering, welding , brazing and grinding the shaft and replacing of worn out parts and re-assembling and connecting it to the electric motor complete all as directed by Engr-in-Charge. Note : (i) The unit rate shall include for minor spares such as bolts, nuts washers, oil seal, gasket, greasing etc as required. (ii) Major spares as required shall be measured and paid for separately.
71All as per item No 70.00above but 12.5 HP.
72All as per item No 70.00above but20 HP including booster motor
73All as per item No 70.00 above but 75 HP including booster motor
74All as per item No 70.00abbove but100 HP including booster motor
75Rewinding of electric motor of capacity upto 7.5HP for centrifugal non clog pumping set with supper enameled copper winding wire of existing gauge, size and weight with insulating material complete all as specified and directed by Engr-in-Charge. Note :- Rewinding of motors if made unserviceable during currency of contract/defect liability period,the same shall be rewinded again without any extra cost to the Govt.
76All as per item No 75.00above but 12.5 HP.
77All as per item No 75.00above but20 HP including booster motor
78All as per item No 75.00above but75 HP including booster motor
79All as per item No 75.00above but100 HP including booster motor
80Supply & fixingMS coupling with rubber bush and coupling nuts & bolts for 20 HP non clog pumping set complete
81Supply & fixing Impeller GM for 20 HP CFpumping set
82Supply & fixing Gland box for 20 HP CFpumping set
83Supply & fixing ball bearing for 20 HP non clog pumping set.
84Supply & fixingin replacementBall bearing of electric motor upto 12.5 HP capacity.
85Supply & fixingin replacement Gun metal bushes of pump upto 12.5 HP capacity. .
86Supply & fixingin replacement MS couplingof pump upto 12.5 HP
87Supply & fixingin replacementBall bearing of electric motor upto 7.5 HP capacity.
88Supply & fixingin replacement Gun metal bushesof pump upto 5 to 7.5 HP capacity.
89S & F power contractor 3 pole AC control AC-3 rating 85 Amps (75 HP) 415 volts including Aux contact 1 No + NC with colil voltage 380/415 volts
90S & F in replacement MCCB 4 Pole 125A breaking capacity ICU at 415 (25KA)
91S & F in replacement MCCB 4 Pole 400A breaking capacity ICU at 415 (36KA)
92S & F in replacement MCCB 4 Pole 630A breaking capacity ICU at 415 (50KA)
93S & F Electronic timer for three phase submersible pump starter.
94All as per item No. 93.00 above but capacity 3 pole MNX 95 (Model as per site requirement)
95All as per item No. 93.00 above but capacity 3 pole MNX 140 (Model as per site requirement)
96Supply and fix in repair of over load relay for motor clainer of motor 75 HP capacity (model as per site requirement)
97Supply and fix in repair of over load relay for motor clainer of motor 100 HP capacity (model as per site requirement)
98Supply and fix in repair of over load relay for motor clainer of motor 12.5/20 HP capacity (model as per site requirement) .
99M&L for masonary valve pit of size 1.2x1.2x1.1m (internal size) by using PCC 1:4:8 type D2 using 40mm graded stone aggregate for foundation, brick wall with sub class `B’ bricks built in CM 1:6,PCC 1:2:4 type B1 using 20mm graded stone aggregate for coping, internal/external rendering 15mm thick in CM (1:4) including provision of MS sheet cover 2mm thick fixed to MS angle frame made out of 50x50x6mm thick with 2 coats of synthetic enamel paint over one coat of red oxide primer to steel surfaces and locking arrangementsincluding dismantling old one with necessary excavation and earth work in any type of soil complete, all as specified and directed by Engineer-in-Charge.
100All as per item No 99.00 but size 0.9x0.9x0.9 m.
101M&L for boring under road/path/hard standing to pass the Pipe linesupto 150mm dia bore with the own arrangement of T&P complete all as specified and directed.
102Supply and fixingHand Wheel for Actuator suitable for200mm/150mm/100mm/ 80mm dia sluice valve / Butterfly Valve.
103M&L for earthing complete with GI earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground vertically at a depath not less than 2.25m below normal level with top level of earth plate at depth not less than 1.5m below normal ground level surrounded from all sides by 15 cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connection by using GI strip 32mmX6mm by means of bolts ,nuts,check nuts and washers of galvanized iron and protected by GI pipe light grade 50mm bore connected to main switch board or main control board and GI pipe light grade 20mm bore for watering and including funnel ,wire mesh,80mm thick pre-cast RCC 1:2:4, type B-1 cover reinforced with hard drawn steel wire fabric weighing not less than 4 kg/sqm in lieu of CI cover , PCC 1:3:6 type C2 pit/chamber including all necessary excavation , and earth work,disposal of surplus soil to a distance not exceeding 50m all as specified and as shown in electrical plate No.3 of MESschedule part-I (2009) complete including takingdown old unserviceable item complete all as specified and as directed.
104M & L for PCC (1:4:8) type D-2 using 40 mm graded stone aggregate in foundation of struts PCC blocks including necessary form work and fair finish to exposed surfaces without using extra cement etc, complete all as specified and directed by Engr - in - Charge.
105S&F in repairs 20mm dia bore Gun metal gate valve with iron wheel head screwed both ends for iron pipes and fixed complete all as specified and directed.
106All as per Srl item No. 105.00 above but 25mm bore.
107M&L for CI/GI specials such as bends, tees, collars tail pieces flanges, socket,elbow,tee,reducers etc complete suitable for CI/GI mains of following sizes complete all as specified and directed Upto 300 mm.
108Supply and laying bricks common brunt clay building bricks sub class B as in cable protection including removing of old bricks complete all as specified and directedby Engr - in - Charge.
109Material and labour for sand cushioing with a layer of fine sand 8cm thick before laying of cable and 15cm thick after laying of cable in trenches complete all as specified and directed. Notes-: Thickness18cms after punning down shall be considered for payment.
110S&F in repair/replacement maint free batteries 12 volt, DC 07 AH complete all as specified and etc all as directed by Engineer-in-Charge.
111Supply & fixing in repair/ replacement of PVC insulated FR LS copper conductor 1.5 sqmm single core multi-strandard flexible cable drawing in existing steel conduit /New PVC/ steel conduitincluding takingdown old unserviceable item complete all as specified and as directed.
112All asper item No-111.00 above but 2.5 sqmm single core.