Military Engineer Services-MES has published Tender For Servicing / Maintenance / Repairing Of Central Ac Plants At Mh And Mbt Arjun Under Ge (A) No 2 Jodhpur. Submission Date for this Tender is 28-10-2023. HVAC Tenders in jodhpur Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

39833091
Corrigendum : Tender For Servicing / Maintenance / Repairing Of Central Ac Plants At Mh And Mbt Arjun Under Ge (A) No 2 Jodhpur
Open Tender
Indian
Rajasthan
jodhpur
28-10-2023

Tender Details

Servicing / Maintenance / Repairing Of Central Ac Plants At Mh And Mbt Arjun Under Ge ( A ) No 2 Jodhpur

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 07-Oct-2023 CorrigendumNo.01 Date 21-10-2023
2 21-Oct-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 28-10-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 24000.0 /-
Tender Value
INR 12 Lakhs /-

BOQ Items

Name of work :- SERVICING / MAINTENANCE / REPAIRING OF CENTRAL AC PLANTS AT MH AND MBT ARJUN UNDER GE (A) NO 2 JODHPUR
Sl. No. Item Description
1M&L for descaling of Condenser unit of 25.4 TR AC Plant after opening from both side and using the descaling compound and brushes with long iron rod to clean the deposition in side the copper tubes and check the water flow in side the tubes including replacement of gasket set, nuts and bolt all as directed by Engr-in-Charge. Note :- 1. Descaling will be carried out two times in a year (12 Condenser Unit x 2 Times = 24 Jobs) 2.Condenser/Chillier coil cleaning by Basic chemical of approved make with preventing equipment from cleanser and avoidingany hazard to human being from chemical reaction.
2S&F in replacement of Scroll type sealed compressor of capacity 13.0 TR . Make : Danfoss model No. SZ185S4RC, 3 Phase, 380-400 Volts, 50 Hz , Thermally protected operating pressure H/L 31.9/25.0 bars suitableforexistingAC plants complete including testing and commissioning as directed by EIC
3Supply & Charging Refrigerant gas R 407 C at Central type AC plant complete all as directed. Note -Leakage detection using Nitrogen gas if required is deemed to included in thequoted rate.
4Supply & filling of Compressor oil suitable for gas R 407 C at AC plantcomplete all as directed and specified by Engr-in-Charge
5S&F Crank case heater for Compressor at AC plantcomplete all as directed and specified by Engr-in-Charge
6S&F Termination joint (connector) for connecting cables complete as directed and specified
7Servicing of Hot water Generator as per manufacturer norms of capacity 24/30 KW model No RC 24/30, 2 steps any make complete as directed and specified by EIC.
8S&F in repair, heating element/coil as per sample of hot water generator of capacity 24 / 30 KW model No RC 24 / 30, 2 steps any make as per sample complete as directed and specified by EIC.
9M&Lfor repairing / servicing / cleaning complete of Air Handling Unit capacity of 6000 CFM, complete with replacement of worn out /unserviceable parts and rectify the leakages and reassembling the same after complete repair/leakages with accessories as nuts, bolts, washers etc installation on existing foundation coupling with existing electrical motor with proper alignment including testing, commissioning complete to the entire satisfaction of Engr-in-Charge
10All as per item No. 9 above but capacity of 9000 CFM
11All as per item No. 9 above but capacity of 10000 CFM
12M&L for replacement ofContractor 4 Pole 40 Amps for AHU unit complete all as specified and as directed.
13All as per item No. 12 above but 32Amp
14S&F Temperature gauge suitable as existing with accessories complete all as directed
15S&F Mercury in glass industrial type Thermometer as existing with accessories complete all as directed
16S&F of Digital Amps meter complete all as directed
17M&L for Fan belt for 6000 CFM to 10000 CFM AHU as per existing complete all as directed
18M&L for Relay 8-22 Amps for 6000 CFM to 10000 CFM AHU as per existing complete all as directed
19S&F Three way motorised direct mounted actuator valve complete set 3"/2.5"/4" with all accessories and including piping arrangement, providing connections etc complete as specified and directed by Engr-in-charge. Note : cost of welding work for connection and disconnection of valve and pipeline, cost of MS pipe heavy duty of size 3"/2.5"/4" upto 3 mtrs pieces is deemed to be included in quoted rates.
20M&L of Thermostat for AHU all as directed
21M&L of rewinding of blower fan motor of capacity 6000 to 10000 CFM with all accessories required for installing and connection complete all as specified and directed by EIC.
22S&F in replacement air filter of AHU of size 6000 CFM as existing suitable complete all as directed
23All as per item No. 22 above but 9000 CFM
24All as per item No. 22 above but 10000 CFM
25M&L for cleaning, servicing of cooling tower of capacity upto 30 TR AC Plant withcleaning agentcomplete pipe lines, and FRP tank, greasing, servicing of cooling tower, motor and fan & make the necessary alignment complete all as specified and as directed Note :- 1.Servicing will be carried out two times in a year (4 Cooling Tower x 2 Times = 8 Jobs)
26S&F in repair of Rotor shaft with rotor of Cooling Tower of capacity 1/3 HP, 3Ph, 415 Volts, 50 Hz complete all as specified and directed
27S&F in repair of Bearing as existing size and model of Cooling Tower of capacity 1/3 HP, 3Ph, 415 Volts, 50 Hz complete all as specified and directed
28S&F in repair of Immersion proof cable gland as existing of Cooling Tower of capacity 1/3 HP, 3Ph, 415 Volts, 50 Hz complete all as specified and directed
29S&F in repair of Connection plate of Cooling Tower of capacity 1/3 HP, 3Ph, 415 Volts, 50 Hz complete all as specified and directed
30S&F in repair of outer casing with anti corrosion coating on the outside of Cooling Tower of capacity 1/3 HP, 3Ph, 415 Volts, 50 Hz complete all as specified and directed
31Disconnecting the electrical connection and taking down the burnt out cooling tower motor ofcapacity 1 to 3 Hp from any location and transporting to workshop for repair, dismantling the motor & taking out burnout copper winding and rewinding the same with super enamelled copper wire as pr existing gauge including replacement of bearing & correcting minor defects reassembling, transporting motor from workshop to site, reinstalled at site, reconnecting, testing and commissioning complete all as specified and directed by EIC.
32M&L for replacement unserviceable ball bearing of Cooling Tower of capacity of 30 TR including all necessary lathe works as required and greasingetc complete as per direction of Engr-in-Charge.
33M&Lfor replacement unserviceable sprinkler assemblyofCooling Tower of capacity upto 30 TR complete all as directed.
34S&F in repair unserviceable CT fan blade of cooling tower of capacity upto 30 TRas per existing size.
35M&L for replacement ofcooling pad/Fins of size 600mm x 300mm x 150mm for cooling tower/ air cooling plant including complete fitting as existing at various installations.
36Dismantling and taking out old non return valve of 65mm dia and supply, installation, testing and commissioning of Non return butterfly valve 65mm dia with duel plate of CI body SS plates NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including insulation as specified and directed.
37All as per item No. 36 above but 50mm dia
38M&L for repair/overhauling of centrifugal monoblock pump set of 3 to 5 HP by opening Gland bush , studs, nuts & washers Ball bearing of pump set Remetling grinding and polishing of pump shaft to required size Gl and packing, replacement of pump bearings and making its proper alignment etc & refixing after repair all as directed .
39M&L for rewinding of centrifugal monoblock pump set of 3 to 5 with all accessories required for installing and connection complete all as specified and directed by EIC.
40Dismantling and taking out old butterfly valve and supply, installation, testing and commissioning of butterfly valve class-II heavy duty for discharge & liquid line of 80 mm dia
41Dismantling and taking out old butterfly valve and supply, installation, testing and commissioning of butterfly valve class-II heavy duty for discharge & liquid line of 100 mm dia
42S&F in repair gun metal gate valve of size 25/32 mm dia as specified and directed by Engr-in-charge
43supply and fixing in auto air purge valve of size 15/20/25 mm dia as specified and directed by Engr-in-charge
44Dismantling and taking out old solenoid valve and supply, installation, testing and commissioning of solenoid valve class-II heavy duty for liquid line as per existing.
45Disconnecting and taking out old existing unserviceable current transformer of Amp meter of any description and Supply, fixing & testing round/ring type current transformer of ratio 100/5 Amp to 150/5 Amp, rated burden 5 VA and accuracy class 1.0 complete all as specified & directed.
46Supply, laying, testing and commissioning of LT UG cable XLPE insulated heavy duty armoured electric power cable with stranded aluminium conductor 1100 volts grade 95 Sq mm 3.5 core, laid in duct/trench/along pole/wall etc including nuts, bolts, washers, saddles & screws etc and making connection, complete all as specified and directed by Engr-in-Charge.
47All as per item No. 46 above but cable of size 70 Sqmm 3.5 core
48All as per item No. 46 above but cable of size 35 Sqmm 3.5 core
49All as per item No. 46 above but cable of size 16 Sqmm 4 core
50All as per item No. 46 above but cable of size 10 Sqmm 4core
51S&F in replacement of old unserviceable indicators any type with LED based indicating lamps of RYB colour including disconnecting and connecting of the same all as directed at site.
52S&F in replacement of Three Phase Preventer suitable for motor protectionand making all incoming and out going electric connections complete all a specified and directed. Type VSP2Make: Minilec/Jepro.
53S&F in replacement of AC contactor 3/4 pole, 415 volts current rating 32 Aand including making necessary electric connections and testing of circuit on full load complete all as specified and directed.
54All as per item No. 53 above but current rating 20 AMPs,3/4 pole
55All as per item No. 53 above but current rating 100 AMPs, 37 KW, 3/4 pole
56All as per item No. 53 above but current rating 63 AMPs,4pole
57Taking out old unserviceable MCCBs up to 200 Amp rating andSupply and fixing for MCCB, 4 pole,415Volt, 16 KAincluding cable lugs of suitable size, complete testing, commissioning complete to the entire satisfaction of Engr-in-charge, the following capacity of 63 Amps.
58All as per above Item No.57 but current rating 125 Amps
59All as per above Item No. 57 but current rating 100 Amps
60Taking out old unserviceable MCBs, S&F ofMCB, C Curve type, 10 kA, 63Amp, TPN with over load and short circuit protection, complete all as directed.
61S&F in replacementGI pipes heavy duty of 25mm size including taking down/up of existing pipe and replacing the same with new pipe including welding work, providing all type of GI fitting as required at site including testing for leakage/blockage of pipe complete all as specified and directed by EIC
62All as per item No 61 above but size 32 mm dia
63All as per item No 61 above but size 40 mm dia
64All as per item No 61 above but size 50 mm dia
65All as per item No 61 above but size 80 mm dia
66All as per item No 61 above but size100 mm dia
67M&L for insulation of MS pipe with PUF slab 30mm thick with and including applying bituminous compound and GI gladding with 26 gauge GI sheet complete of size 65mm dia
68Taking out old damaged AC duct and Supply, Installation & testing of Galvanised Sheet of size 22 Gauge FABRICATED DUCT as required at site with Connectors, GI Flanges, turning vanes, with proper duct sealing etc Complete with supports as per the specifications.
69All as per item No 68 above but thickness 24 Gauge
70S&F of external thermal insulation on ducts with closed cell cross linked polyethylene (XLPE) foam of density 33 Kg/m3 with 12mm thick complete all as specified and directed
71S&F of adjustable type air diffuser of size 12 x 12 inch, air square aluminium diffusers complete with wooden frame, volume control damper, painting, gasket, screws complete all as directed by Engr-in-Charge
72S&F double canvas connections for AHU"s in the system with the flanges, nuts, bolts, gaskets etc complete all as directed by Engr-in-Charge
73M&L for attending AC plant faults at MH ICU / MBT Arjun area, to check AC Plant for serviceability of continuous cooling effect rectifying including carrying out minor repairs / replacement etc as required to make AC Plant functional, all as specified and directed by Engr-in-charge. (i) Any other replacement of major items shall be measured & paid separately under respective items of this schedule. (ii) Minor items will be included on the quoted rates only.
74M&L for mild steel plates of Fe-410-W (Grade E-250) quality B, plain or chequered, 5mm thick or over in thickness complete all as directed by Engr-in-Charge
75Replacement of UNSV Earthing complete withgalvanized steel earth plate electrode 60 cmx 60 cm x 6 mm thick buried directlyin ground (earth pit notless than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 metres below normal ground level,connecting to theGI earth strip 25x4 mm by means of bolts, nuts , check nuts and washers of galvanized iron andsteelearth wire protected by provision of GI lightgrade pipe40 mmbore including provision of concrete pitmade from PCC ( 1:2:4) type B-1 (using20 mm graded stone aggregate) with 40mm thick cover of RCC 1:2:4 reinforced with XPM (Weight not less than 4 Kg/Sqm) and frame of angleiron40 x 40 x 6 mm and handle of 6 mmdia MS barmade to shape, GI light grade 20 mmbore pipefor watering perforated atbottom, 1.50metre long placed on top edge of earth plate, common salt &charcoalfilling, withfixing arrangement , funnel, wire mesh and earthwork in hard/dense soil, returning filling in and removal of surplus soilto a distance notexceeding50 metres, all as perelectrical plate No 3 of SSR 2009 Part-I and connecting to LT Panel / DG Sets / Voltage Stabilizer /Building all as specified or indicated including testing on complete all as specified and as directed by Engineer-in-Charge.