Tender For Replacement Of 350 Tr Chiller For Central Ac Plant At Rla Jaipur, Jaipur-Rajasthan

Public Works Department-PWD has published Tender For Replacement Of 350 Tr Chiller For Central Ac Plant At Rla Jaipur. Submission Date for this Tender is 28-09-2023. HVAC Tenders in Jaipur Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

39803817
Tender For Replacement Of 350 Tr Chiller For Central Ac Plant At Rla Jaipur
Open Tender
Indian
Rajasthan
Jaipur
28-09-2023

Tender Details

Replacement Of 350 Tr Chiller For Central Ac Plant At Rla Jaipur

Key Value

Document Fees
INR 1000 /-
EMD
INR 129720.0 /-
Tender Value
INR 64.86 Lakhs /-

BOQ Items

Name of Work:Replacement of 350 TR Chiller for central AC Plant at RLA Jaipur
Sl. No. Item Description
1Supply, Installation, Testing and Commissioning
2of AHRI certified water cooled chiller with hermetic / semi-hermetictwin Screw type Compressor chilling machineof minimum 350 TR (Actual) capacity on buyback of 350 TRModel no CPH3G3E1 B/02 (York) as per below parameters, suitable for R-134a / green refrigerant having multicompressors& multi refrigerant circuit , insulated flooded Evaporator & condenser , shell and tube typewith copper tubes rolled into steel tube sheets , flow switches at condenser and chiller outlet, integrated oil separator, Copper refrigerant piping, Refrigerant and oil (First Charge) gauge panel, drive package , anti vibration mountings , control and its control wiring, in built automatic continuous capacity control with electronic expansion valve with automatic unit capacity reduction upto 15 % and standard accessories etc. all mounted on M.S. frame with anti vibration mounts/rubber pads. Both compressors should be of equal capacity. Motor shall be suitable for 415 +/- 10% volts, 50 Hz +/- 3% , three phase AC supply with LCD display Microprocessor based Electrical control displaying system & system protection installedon existing civil foundation with civil work, MS edge protection as required for positioning. The Chiller will be installed in the basement therefore unloading & shifting of Chillers is included in the scope of work. Dismantling, removing pipe line connection and shifting of old chiller with loading unloading is in the scope of contractor without any extra cost. The chillershall be complete withfollowing AHRI certified datasheet .All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with P.W.D. Electrical B.S.R. 2022. Condenser water in : 90o F Condenser water out : 97.5o F Chilled water in : 54o F Chilled water out : 44o F FF Chiller - 0.0005 (FPS)h.ft2.ºF/Btu, FF Condensor - 0.001 (FPS) h.ft2.ºF/Btu IKW/TR: 0.65 Max. and IPLV 0.45 at above parameters(IKW/TR and IPLV to be measured at above mentioned parameters) Microprocessor based control panel complete with acessories and BMS compatible MODBUS protocol.AHRI selection sheet required for full load and part load datashall be submitted along with the BID showing selection printoutat above mentioned condition showing part load data at 100%, 75%, 50%, 25% loads at reducing condenser water temperature compliance with aplicable standards/ codes.
3Providing & Fixing of Industrial type V - Shape Thermameter.All as per pre approved by Engineer in charge.For additional technical parameters of products/work,refer Annexure ""A"" attached with PWD Electrical BSR 2022.
4Supply, installation, testing and commissioning of BS 5404 EPDM Body (ethylene propylene diene monomer) flexible connectionswith zinc plated carbon steel flange complete as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/work,refer Annexure ""A"" attached with PWD Electrical BSR 2022.200 mm PN16 flanged
5Supply, installation, testing and commissioning of BS 5404 EPDM Body (ethylene propylene diene monomer) flexible connectionswith zinc plated carbon steel flange complete as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/work,refer Annexure ""A"" attached with PWD Electrical BSR 2022.250 mm PN16 flanged
6Dismantling and reinstallation of existing Balancing valves All as per pre approved by Engineer in charge.For additional technical parameters of products/work,refer Annexure ""A"" attached with PWD Electrical BSR 2022.
7Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS "C " class (Heavy) pipes conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applicationsincluding cutting, screwing, welding etc. & forged steel fittings like elbows, tees, tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger and nuts bolts including cutting hole and chase in brick or RCC walls/ slab and making good the same. complete with painting of one coats of Red Oxide and two or more coats of synthetic enamel paint of requiredshade complete as required. (Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs.). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
8200 mm dia, 6.0 mm thick
9250 mm dia, 6.35 mm thick
10Supply and fixingduct insulation with 50 mm thick Expanded Polystyrene Thermocol (ESP) sheet of density 24 kg/cu.m after applying two coats of cold setting adhesive (CPRX Compound) and binding sheet with chicken wire mesh and applying 26 G aluminium cladding complete as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
11Supplying and Fixing of PN 1.6Butterfly Valve (Wafer Type) with S.G Iron Disc and confirming to IS:13095 complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets,etc as required of following sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
12200mm dia Gear Operated
13250mm dia Gear Operated
14Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
15240.0 Sq. mm
163.5 core
17Supply, Fabricating & installing following sizes of perforated Powder coated MS cable tray with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
18225mm x 50mm x 1.6mm
19Providing & fixing Stainless Steel pressure gauge with dial of 150 mm dia size and range 0 to 20 kg/sq.cmwith 3 / 8 " BSP bottom entry , Ball valve , SS Syphon tube all fittings etc, dulycalibrated before installation in MKS and FPS units, Accuracy Level +/- 1% including Making Drilling in Existing MS PipeEtc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .