Tender For Comprehensive Main, Repair Of Various Ac Plants, Summer And Winter Appliance At Mh Under Ge (East) Jalandhar Cantt, jalandhar-Punjab

Military Engineer Services-MES has published Tender For Comprehensive Main, Repair Of Various Ac Plants, Summer And Winter Appliance At Mh Under Ge (East) Jalandhar Cantt. Submission Date for this Tender is 12-10-2023. HVAC Tenders in jalandhar Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

39684500
Corrigendum : Tender For Comprehensive Main, Repair Of Various Ac Plants, Summer And Winter Appliance At Mh Under Ge (East) Jalandhar Cantt
Open Tender
Indian
Punjab
jalandhar
12-10-2023

Tender Details

Comprehensive Main, Repair Of Various Ac Plants, Summer And Winter Appliance At Mh Under Ge (East) Jalandhar Cantt

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 05-Oct-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 12-10-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 72000.0 /-
Tender Value
INR 36 Lakhs /-

BOQ Items

Name of Work : Comprehensive main, repair of various AC Plants, summer and winter appliance at MH under GE (East) Jalandhar Cantt (Tender ID No 2023_MES_619090_1)
Sl. No. Item Description
1Material and labour for de-scaling of condenser unit50 TR AC central type with copper tubes by removing nuts & bolts, side cover plates, water connection and filling up of de-scaling chemical in condenser and manually cleaning of copper tubes with using Nylon brush of superior quality, iron rod for removing of complete scaling from tubes and water circulation through condenser including replacement of rubber gasket, tightening side cover plates and making necessary connectionscomplete all as specified and as directed. (OT AC Plant in MH)
2Material and labour forservicing of Air handling unit5000/8000 CFM of central AC plant by removing filters, assembling filters and testing for the following parts. (a)Inspectfilters, removing and cleaning by using vaccum cleaner and refix same. (b) Clean cooling coil, fins byusing caustic soda and water pressure method and applying Grease for all motors, check and adjust belt tension if required, check condition of blower shaft, impeller and bearings, check tightness of all electrical terminations, clean water line strainers, check proper balancing system , check for noise and vibration. (c)Check healthy operation of controls and safety devices.
3Attending breakdown(except periodical maintenance) by skilled Ref Mechanic for any type AC plant/cold store of capacity 5 TR to 50 TR, diagnosing the fault, repair/ replacement of unserviceable parts including carrying out minor repairs such as changing of small pieces of wires, tightening of loosen electric connections ,nuts, bolts screws, or switches, disconnecting andre-fixing of LT cables etc as required to make the system functional in any time by deploying sufficient technician alongwith with helper including necessary T&P complete all as specified and directed. Notes : (a) Replacement of major items shall be measured and paid for separately under respective items.(b) Number of complaints may vary day to day and shall be on required basis. Contractor shall quote their rates accordingly. (c) Breakdown complaintsshall be collectedfrom complaint cell or by telephonically from duty staff/JE E/M/Engineer-in-Charge.(d) In case of failure on the part of contractor for attending any breakdown within 4 hours a penalty shall be imposed @ Rs.2000/- per complaints and recovered from his dues
4Taking down the old discharge/suction/oil pressure sensor and Supply and fix new discharge pressure sensor testing and commissioning 0-5 PSI 50 TR compressor complete all as specified and directed
5Material and labour for disconnecting electric motor 10HPand transporting to workshop, dismantling the same and taking out rotor assembly removing burnt winding coil of stator, cleaning the complete stator and rotor with carbon tetra chloride solution, rewinding the stator coil with super enamelled copper conductor of proper size/gauge as per existing, inserting the new re-winded coils of stator dulyvarnishing and insulated with superior quality insulation material, replacement of old connection lead with superior quality PVC copper cable with stranded copper conductor from motor to connection plate, replacement of ball bearing, reassembling the motor, shifting to work site and connecting with the system, testing on full load complete all as specified and as directed by Engineer-in-Charge
6All as per srl item No 5.00 here-in-before but of 7.5 HP electric motor.
7All as per srl item No 5.00 here-in-before but of 5 HP electric motor.
8All as per srl item No 5.00 here-in-before but of 3 HP electric motor.
9All as per srl item No 5.00 here-in-before but of 2 HP electric motor.
10All as per srl item No 5.00 here-in-before but of 1 HP electric motor.
11All as per srl item No 5.00 here-in-before but of 250 to 500 watt, single phase electric condenser fan motor.
12Dismantling the mono block pump set with motor any make, upto10 HP capacity servicing by cleaning lubricating and by replacing of ball bearing gland bolt, nut and washers, terminal connector, machining of shaft, gasket, gland rope, mounting bolts, reassembling, refixing with bed and testing complete all as specified and directed
13Taking down blower with motor of AHU/Package type AC any capacity, servicing by cleaning, lubricating, machining of shaft, replacement of ball bearing mounting bolts, reassembling and testing complete all as specified and directed
14Taking down condenser fan motor from outdoor condenser unit of any capacity, servicing by cleaning, lubricating, machining of shaft, replacement of ball bearing mounting bolts, reassembling and testing complete all as specified and directed
15Replacement of Fan blade of condenser fan motor of suitable size all as specified and directed
16Material and labour for check for any refrigerant leaks through flare joints, valve glands or any of the loc in refrigerant system which requires leak detector device, soap solution, halide torch or electronic leak detector and arresting leakages including necessary welding, brazing works binding with teflon tape as required at site and topping upthe gas for required suction & discharge pressurefor50 TR central type AC Plant complete all as specified and as directed. Note : Refrigerantshall be measured and paid separately.
17Material and labour for charging Nitrogen Gas in 50 TR capacity centralAC plant maintaining pressure 350 Psi for checking of Gas leakage and removing water vapour choked in line, flushing out the complete system including gas leakage and detection with halide torch/ soap foam solution in system including gas welding flushing and making good the pipe line to make the system leak proof complete all as specified and as directed.
18Material and labour for vaccumising the plant by using vaccum pump up to (-) 30 PSIG pressure and hold the same under vaccum pressure upto 24 hours including necessary welding and brazing if required complete all as specified and directed for 50 TRAC plant .
19Supply and charging refrigerant Gas R-22 forAC plant of various capacities includingmaintaining proper pressure after filling of Gas complete all as specified or as directed by Engineer-in-Charge.
20Supply and charging refrigerant Gas R-407 AC plant of various capacities includingmaintaining proper pressure after filling of Gas complete all as specified or as directed by Engineer-in-Charge.
21Supply and charging refrigerant Gas R-410 AC plant of various capacities including maintaining proper pressure after filling of Gas complete all as specified or as directed by Engineer-in-Charge.
22Supply and filling in fresh compressor oil N-68 for compressor of AC plant of various capacities to ensure the development of required oil pressure complete all as specified or as directed by Engineer-in-Charge. Make :- Indian oil/ Bharat Petroleum/ Servo Note :- Compressor oil shall be supplied in company sealed containers only
23Supply, install, testing and commissioning of chiller control unit with display board complete set suitable for 50 TRcentral type AC plant as per existing pattern and make it functional all as directed and directed. Make : Softhard or equivalent as approved by GE
24Supply, install, testing and commissioning ofPackage type AC control unit with display board complete set suitable for 15/22 TRmultiunit AC plant as per existing pattern and make it functional complete all as specified and directed
25Supply and fixing in replacement in replacement of water pressure gauge 4” dia, range 0 to 100 Psi complete all as specified or as directed by Engineer-in-Charge. Make:- Fiebig/Guru/york
26Supply and fixing in replacement of V- belt B-68 to B-94 heavy duty complete all as specified or as directed by Engineer-in-Charge. Make:- Fenner/Dunlop or equivalent
27Supply and fixing in replacement in replacement of V- belt A-30 to A-45 heavy duty complete all as specified or as directed by Engineer-in-Charge. Make:- Fenner/Dunlop or equivalent
28Supply and fixing in replacement in replacement ofthermostatexpansionvalvesuitableforACplant50trcapacitycompleteall as specified and directed. Make:- Sporlan/ Danfoss/ Renutrol or equivalent.
29Supply and fix in replacement Finned strip heater made of GP sheathing having terminals at one end and two holes for horizontal installation of capacity 3 KW in Air Conditioningplant installed at various locations complete all as specified or as directed. Make:- Daspass/Lazer/Usha
30Supply and fixing Pre filter 100% washable synthetic non woven supported by aluminium mesh on one side & HDEP mesh on other side of size 610x305x50mm having dust filtration level 5 micron 95% efficiencyas per existing type, make and size complete all as specified and as directed
31Supply and fixing Pre filter 100% washable synthetic non woven supported by aluminium mesh on one side & HDEP mesh on other side of size 610x610x50mm having dust filtration level 5 micron 95% efficiencyas per existing type, make and size complete all as specified and as directed.
32Supply and fixing Pre filter 100% washable synthetic non woven supported by aluminium mesh on one side & HDEP mesh on other side of size 450x510x50mm having dust filtration level 5 micron 95% efficiencyas per existing type, make and size complete all as specified and as directed.
33Supply and fixing Pre filter 100% washable synthetic non woven supported by aluminium mesh on one side & HDEP mesh on other side of size 420x510x50mm having dust filtration level 5 micron 95% efficiencyas per existing type, make and size complete all as specified and as directed.
34Supply and fixing HEPA (High-Efficiency Particulate Air) filter of size 24"x24"x12" constructed withgalvanised steel frames box type having dust filtration level 0.3 micron 99% efficiencyas per existing type, make and size complete all as specified and as directed. Make for srl item No. 30.00 to 34.00 : Mechmaark/Spectrum/American Air filters
35Servicing/Maintenance of packaged type AC of capacity 2x5.50/2x10TR TR such as cleaning of fine filter with water, checking Gas and gas leakage, cleaning of condensing coil/cooling coil with water for better performance of AC plant, cleaning and greasing of condensing blower motor, AHU blower motor and booster blower motor, cleaning of condensers unit, checking tightening of all electrical connections complete all as directed.
36Servicing/Maintenance of packaged type AC of capacity 2x15/3x15 TR/3x22 TR such as cleaning of fine filter with water, checking Gas and gas leakage, cleaning of condensing coil/cooling with water for better performance of AC plant, cleaning and greasing of condensing blower motor, AHU blower motor and booster blower motor, cleaning of condensers unit, checking tightening of all electrical connections complete all as directed.
37Material and labour for preparation of old painted surfacesof AC plant central type of capacity 3x 50 TR including all motors, condensers, pumps, MS Pipes of various sizes, cooling tower and LT electric panel board installed at Heat stroke plant roompainting with super enameled paint of approved quality with spray gun two coats incl preparation of surfaces and scraping old paint, filling cavities complete all as specified and as directed
38Replacement of PVC honey comb fills (drift eliminators) suitable size of central type AC plant all as specified and directed
39Material and labour for disconnectingcompressor of cap 7.5 TR of package type ACand transporting to workshop, dismantling the same and taking out motor assembly removing burnt winding coil, cleaning the complete stator and rotor with carbon tetra chloride solution, rewinding the stator coil with super enameled copper conductor of proper size/gauge as per existing, inserting the new re-winded coils of stator dulyvarnishing and insulated with superior quality insulation material, replacement of minor parts if required, reassembling the compressor, shifting to work site and connecting with the system, testing complete all as specified and as directed by Engineer-in-Charge. Note : Refrigerantshall be measured and paid separately.
40Supply and fixing in replacement connecting and testing of compressor scrolled sealed unit of capacity 5.5 TR performer,forPackaged AC plant/cold storeincludinggas charging and testingcomplete all as specified and as directed. Make- DANFOSS/ KIRLOSKAR/ TECUMSEH/ COPELAND. Note : Refrigerantshall be measured and paid separately.
41Supply and fix Single phase preventor having voltage unbalance and phase reversal protection complete all as specified and directed. Make GIC/L&T or other equivalent approved make
42Replacement of electronic timer 240v, 50 Hz, 3-30 sec for star delta starter complete all as specified and directed. Make L&T or equivalent
43Supply and fixing in replacement of PCB in the existing Packed unit/ Cold room AC Plant including necessary control wiring as required. Model No - 22 TR PMN MPD Twin complete all as specified and directed Make - Softhard Automation Pvt Ltd or in equivalent
44Supply and fixing in replacement of PCB in the existing Packed unit/ Cold room AC Plant including necessary control wiring as required. Model No - 15 TR PMN MPD Twin complete all as specified and directed. Make - Softhard Automation Pvt Ltd or in equivalent
45Supply and fixing in replacement Contactor MNX, 32 amp 3 pole, coil voltage as per existingcomplete all as specified and as directed. Make - Siemens/BCH/L&T/Schneider.
46Supply and fixing in replacement Contactor MNX, 45 amp 3 pole, coil voltage as per existingcomplete all as specified and as directed. Make - Siemens/BCH/L&T/Schneider.
47Supply and fixing in replacement Contactor MNX, 25 amp 3 pole, coil voltage as per existingcomplete all as specified and as directed. Make - Siemens/BCH/L&T/Schneider.
48Supply and fixing in replacement toggle 5 Amp switch two way brass handle as per sample complete all as specified and directed
49Supply and fixing in replacement of pressure switchLP/HP cut out M15 as per sample complete all as specified and directed. Make- Danfoss/indfoss
50Supply and fixing in replacement compressor shaft oil seal of50 TR complete all as specified and directed. Make-Voltas or equivalent
51Servicing of cooling tower of capacity 100 TR plant by replacement of blocked/broken nozzles, Cooling tower fan and motor, cleaning descaling of complete fins including replacement of broken fin, cleaning water tray, valves, piping etc and testing complete all as specified and directed.
52Supply and fixing in replacement Main contactor Type 3TF 46 complete all as specified and directed Make - Siemens/BCH/L&T/Schneider.
53Supply and fixing in replacement Main contactor Type 3TF 34 complete all as specified and directed Make - Siemens/BCH/L&T/Schneider.
54Supply and fixing in replacement over load Relay 6 to 10 Ampcomplete all as specified and directed Make -Siemens/BCH/L&T/Schneider.
55Supply, fixing, connecting, and testing condenser fan motor of outdoor air-cooled condensers of AC plant/cold storecapacity 5.5 TR/7.5TR/11TR as per existing type and size including taking out of unserviceable motor complete all as specified and directed.
56Supply, fixing, connecting, and testing evaporatorfan motor of cold store capacity 5.5TR/8.5 TRas per existing type and size including taking out of unserviceable motor complete all as specified and directed.
57Supply, fixing, connecting, and testing molecular drier cum strainer on line type of size 3/8" x 3/8" make Danfoss in AC plant capacity 5.5/7.5/11 TR as per existing type and size including taking out of unserviceable drier complete all as specified and directed.
58Servicing/Maintenance of walk-in cooler of capacity 9000 ltr with PUF panel cabin such as checking Gas and gas leakage, cleaning of condensing coil with water for better performance of cold store, cleaning and greasing of condensing blower motor, cooling fan motors, Cleaning and washing of complete indoor and outdoor unit and PUF cabin, cleaning of condensers unit, checking tightening of all electrical connections complete all as directed.
59Servicing/Maintenance of Cold store of capacity 2x5.5 TR/8.5 TR such aschecking Gas and gas leakage, cleaning of condensing coil with water for better performance of cold store, cleaning and greasing of condensing blower motor, cooling fan motor, cleaning of condensers unit, checking tightening of all electrical connections complete all as directed.
60Supply and fixing rolled mild steel work in joist, channel, angle, or tee sections, fixed independently, without connecting plates etc., cut to within 20mm of the length indicated, quality confirming to GDE Fe-410-S for cooling tower repair and pump mounting base complete all as specified and as directed.
61Supply and fixing in replacement Flanged butterflyvalve for MS pipe heavy grade 150mm dia bore all as specified and directed.
62Supply and fixing in replacement Flanged butterflyvalve for MS pipe heavy grade 100mm dia bore all as specified and directed.
63Material and labour for cold water pipe insulation with resin bonded fibre glass wool roll of density 24 kg/Cum, with factory laminated aluminium vapour barrier, 40MM thickness of insulation complete all as specified and directed
64Supply and fixing in replacement of factory made steam generator of capacity 9KW, 415 volt suitable for central type AC plant complete with automatic humidity control unit, control wiring including dismantling existing and fixing new steam generator alongwith all fixing accessories like pipe fittings etc completeall as specified and directed. Make : RAPID COOL or equivalent as approved by GE
65Supply and fixing in replacement GI pipe medium grade 20mm dia laid in floor/ wall including necessary GI fittings complete all as specified and directed
66Supply and fixing in replacement brass ball valve suitable for 20mm GI pipe complete all as specified and directed
67Supply and laying electricalinsulating mat class ‘B’ conforming to IS 15652-2006 (ISI marked) of 2.5 mm thick and 1 mtr width and roll of 10mtr, working voltage 11 kV, dielectric strength 45 complete all as specified and directed. Make : Jyoti/Vardhman or equivalent
68Supply and laying electricalinsulating rubber mat class ‘B’ conforming to IS 5424 (ISI marked) of 15 mm thick of size 1mx2m, suitable for HT/LT switch gearscomplete all as specified and directed. Make : Jyoti/Vardhman or equivalent
69Supply and fixing informatory board of size 1200x900 mm frame made out of MS square tube of size 25mmx25mm, 1.6 mm thick and front side covered with coloured flex sheet duly printed with required information all asspecified and directed. Dept will provide the details of writing letter and colour of sheet and letters to board.
70Supply and fixing Danger notice board for 433 volt of standard size and pattern for electric sub stncomplete all as specified and directed.
71Supply and fixing in replacement electric siren 220 volt, 5 KM range complete all as specified and directed. Make : Lifeguard or equivalent
72Supply and fixing fire ball fire extinguisher 150mm dia suitable for electric equipment with stand complete all as specified and directed. Make : Lifeguard or equivalent
73Supply, installation and testing of AMF panel indoor type suitable for DG set 100 KVA with factory made type weather proof, vermin proof fully ventilated both side opening and fabricated out of 2mm thick CRCA sheet and mounting channel having copper bus bar three phases and one neutral of suitable capacity, fixed on insulator by coloured heat shrinkable sleeves and housed in specified including powder coated internally externally the entire steel surfaces, all the cover shall have fully locking arrangement. fully internally wired with suitable size of thimbles and internally wiring of suitable size all as specified and directed, comprising with following parts :- (a) Under voltage relay 415V AC for main supply (b) Under voltage relay 415V AC for DG supply (c) AC meter 230 V, 2 NO+2 NC (d) DC meter 12V (e) Control MCB SP 16A (f) Control MCB SP 6A (g) Automatic battery charger 12V (h) LED indicating light for main and DG (j) LED indicating light for main battery charger (k) Digital voltmeter (0-500V) with selector switch (l) Digital Ammeter (0-500A)with selector switch with suitable CT (m) DC Volt meter 15/30V (n) DC Ammeter 0-15A (o) Trickle/ Boost switch (p) Auto/ Manual switch
74(q) Plus button start & stop with element (r) Power contactor 200A 3 pole 415V for DG (s) Power contactor 200A 3 pole 415V for Main (t) MCCB 200A 25KA, 3 pole for main and DG supply (u) Control Relay (v) Overload Relay (w) Overload Relay 2.5-4A (x) Any other material required, but not mentioned will be included in the item rate
75Material and labour in replacement earthing complete for Transformers/ LT Panels with galvanised steel earth plate electrode 60cmx60cmx6mm thick buried directly in ground vertically at a depth not less than2.25 metres below normal ground level with top edge of the plate at a depth not less than 1.5 metres belownormalgroundlevel,connected with and including GI strip 32mm x 6mm in andincluding GI pipe 40mm bore medium grade as protection pipe (from top of earth plate up to the body of equipment) by means of GI bolts, nuts, check nuts and washers of GI and thimbles, earth plate surrounded by packed layers of charcoal dust and common salt 15cm thick, all around includingtop and bottom and watering pipe 20mm bore of GI pipe light grade with funnel and wire mesh, PCC chamber of size 300 x 300 x 300mm (top of chamber minimum 15 cm above the normal ground level (1:3:6) using 20mm graded stone aggregate and RCC cover (1:2:4) type B-I using 20mm graded crushed stone aggregate and angle iron frame including necessary excavation/ earth work in any type of soil/rock, test point of GI strip and as shown in Electrical plate No. 3 of SSR Part-I (2009) testing on completion complete all as specified.(cost of protection pipe up to 7.5metres from earth electrode will be included in the unit rate quoted by the contractor) complete all as specified and directed
76Material and labour for Earth continuityconductor or main earth leadfixed on wall on batten or recess or chases or burried in groundor drawn in conduit / pipe or fixed to pole or any other indicatedas required on ground for 25x6 mm aluminium strip complete all as specified and as directed.
77Material and labour for servicing of wireless patient call bell 24/30 bed system and make it functional all as specified and directed.
78Supply and fixing in repairs high voltage alkaline battery (12V)complete all as specified and directed
79Supply and fixing Wireless Bed UnitWith Socket withScrews &, Mounting Plate,all as specified and directed.
80Supply and fixing Wired Handset With L Type Jack complete all as specified and directed
81Material and labour for servicing of AC"s split type of capacity 1.5 / 2.0 TR inner & outer unit of any make, cleaning of outdoor condenser unit, indoor unit cooling coil, with chemical solution c-shine or equivalent and high pressure water jet pump, greasing to condenser fan, checking, tightening all electrical connections, washing of air filter, oiling and tightening of all nut, bolts, etc complete all as directed
82Taking down window type AC 1.5/2 TR and Material and labour for servicing of AC’s of any make, cleaning of condenser coil andcooling coilswith chemical solution c-shineor equivalent and high pressure water jet pump, greasing to condenser fan, checking, tightening all electrical connections, washing of air filter, oiling and tightening of all nut, bolts etc completeall as directed
83Material and labour for replacement of compressor sealed unit suitable for air conditioner window/split type of capacity 1.5 TR in outdoor unit including taking out old unserviceable compressor, cleaning flushing, vaccumizing the system, recharging of gas in adequate quantity, soldering/ brazing of suction, discharge and charging line complete all as specified and directed. Make:- Kirloskar/ LG/ Toshiba/ Hitachi/ Gujral/ Carrier/Tecumseh/ Usha Shri Ram/Emerson/Copeland.
84All as per srl item No. 82.00 here-in-before but suitable for air conditioners of capacity 2.0 TR.
85Supply,replacement, connecting and testingof double shaft blower motor 240 volts single phase suitable for window type AC 1.5/2 TR as per existing type and size complete all as directed. Make: Khaitan/ Universal/ CG./ Carrier/ Voltas/ Sidwal.
86Supply, replacement, connecting and testing of outdoor condenser blower motor with fan blades motor suitable for1.5/2 TR split AC 240 volts single phase, all as directed. Make: Khaitan/ Universal/ CG./ Carrier/ Voltas/ Sidwal
87Supply, replacement, connecting and testing of indoorblower motor suitable for 1.5/ 2 TR split AC 240 volts single phase, all as directed. Make: Khaitan/ Universal/ CG./ Carrier/ Voltas/ Sidwal.
88Supply, replacement, connecting and testing of indoorblower suitable for 1.5/ 2 TR split AC 240 volts single phase, all as directed.
89Supply and fixing in replacement of blower drum as per sample suitable for 1.5/2 TR Window AC all as directed
90Supply and fixing in replacement of temperature sensor as per existing type and size suitable for 1.0/1.5/2 TR window/splitAC complete all as specified and directed.
91Supply and fixingin replacement of starting/running capacitor conforming to IS specification suitable for 1.0/1.5/2 TR window/split AC complete all as specified and directed. Make: Havells/ Unistar/ Asian/ EPCOS/ Sarda
92Material and labour for charging of refrigerant gas in window typeAC 1.5 Ton capacity including vaccumizing, leakage test and rectification of leakages etc complete all as directed
93All as per item No 91.00 here-in-before but for split type AC of capacity 1.5 TR
94All as per item No 91.00 here-in-before but for split type AC of capacity 2.0 TR
95Supply and fixing in replacement evaporative cooling unit of split type AC of capacity1.5 Ton including cooling coils, PCB plate and display, remote control, cooling fan motor with blade, blower drum, complete with all accessories suitable for AC"s of make Voltas/ Blue Star/ Samsung/ L.G complete including taking out old unit including cutting, brazing and testing all as specified and directed.
96All as per item No 94.00 here-in-before but for capacity 2.0 Ton all as specified and directed.
97Repair/servicing of Electronic PCB Board for non inverter AC of any make all as specified and directed.
98Repair/servicing of Electronic PCB Board for inverter AC of any make all as specified and directed.
99Supply and fixing in replacement universal remote for any make/type of AC all as specified and directed.
100Supply and fixing in replacement flair nut all as specified and directed
101Supply and fixing in replacement service valve for any make type of AC all as specified and directed
102Supply and fixingin replacementPCB remote plate DC operation suitable for hot and cold operation of AC Window/split type 1.5 /2 TR of any complete with remote all as specified and directed.
103Supply and fix single pole and neutral sheet metal enclosure with two pin and earth plug and socket complete with and including single pole MCB 16 Amps.
104Supply and fixing in replacementof copper pipe for suction line including heavy duty insulation with wrapping with packing brown tape suitable for AC split type of capacity 1.5/2 TR including cutting and soldering, brazing etccomplete all as specified and directed.
105Supply and fixing in replacementof copper pipe for discharge line including heavy duty insulation with wrapping with packing brown tape suitable for AC split type of capacity 1.5/2 TR including cutting and soldering, brazing etccomplete all as specified and directed.
106Supply and fixing in replacementofheavy duty insulation with wrapping with packing brown tape suitable for AC split type of capacity 1.5/2 TR including cutting and soldering, brazing of copper pipe if requiredcomplete all as specified and directed.
107Supply and fixing in replacement condensing coil unit of split type AC of capacity 1.5 Ton including condenser coil copper, with cooling fins, condenser blower motor with blades, PCB plate with complete wiring, including compressor, testing and commissioning of Make Voltas/ Blue Star/ Samsung/ L.G complete including taking out to old unit including cutting, brazing and testing all as specified and directed
108All as per item No 106.00 here-in-before but outdoor unitof capacity 2.0 TR.
109Supply and fixing in replacement PVC drain pipe ofsize 2m long complete all as specified and directed
110Supply and fixing in repair cooling/condenser coil set made out of copper pipe and fins suitable for AC window mounted type of capacity 1.5/2 TR all as per existing type and size including cutting soldering and testing complete all as specified
111All as per item No 109.00 here-in-before but for split AC 1.5/2 TR
112Supply and fixing in repair capillary and filter suitable for AC window/ Split type of capacity 1.5/2 TR including cutting, soldering, brazing etc complete all as specified and directed.
113Supply and fixing in repair expansion valve suitable for AC window/ Split type of capacity 1.5/2 TR including cutting, soldering, brazing etc complete all as specified and directed.
114Supply and fixing in repair reversible valve 4 way with plunger AC 200/240 volts 50 c/s as per existing make and type suitable for AC split/window type of capacity 1.5 / 2.0TR including repair/ modification to remote plate, cutting, soldering, brazing complete including charging if gas required to maintain the required pressure complete all as specified and directed. Note: Cost of all modification required including charges in wiring connections and gas cycle system are deemed to be included in item rate nothing shall be paid extra.
115Material and labour for servicing of voltage stabilizer of capacity 4/5 KVA by opening up and checking the fault, replacing necessary spares and make it functional all as specified and directed.
116Material and labour for servicing of voltage stabilizer of capacityupto 3 KVA by opening up and checking the fault, replacing necessary spares and make it functional all as specified and directed.
117Supply and fixing in replacement of voltage stabilizer copper wounded for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 270 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 15 A with digital display complete all as specified and directed. Makes: V-Guard/Blue Star/ Logicstat
118All as per item No. 116.00 here-in-before but for 12 A.
119Material and labour for PVC insulated and sheathed, flexible wire with multi stranded copper conductor wire of size 3 core, 1 sqmm, ISI marked complete all as specified and directed.
120Material and labour for PVC insulated and sheathed, flexible wire with multi stranded copper conductor wire of size 3 core, 1.5 sqmm, ISI marked complete all as specified and directed.
121Material and labourin replacement PVC insulated and sheathed, round flexible wire with multi stranded copper conductor wire of size 3 core, 2.5 sqmm, ISI marked complete all as specified and directed.
122Taking down old unserviceable sealed compressorand Supply and fixing ofnewcompressor sealed unit suitable for water cooler 150/150 Ltrs capacity including cleaning, vaccumizing, gas charging of adequate quantity and testing on load complete all as specified and directed. Make: USHA / Sriram /Emerson / Kirloskar/ Carrier/ Tecumseh.
123All as per description of Srl item No 121.00 here-in-before but sealed unit compressor suitable for water cooler capacity 60/120 Ltrs
124All as per description of Srl item No 121.00 here-in-before but sealed unit compressor suitable for water cooler capacity 40/80 Ltrs
125Supply and replacement of water tap brass CP with inner/outer threads push type or with rotary knob of size 15 mm dia as per existing type and size complete all as specified and directed.
126Supply and replacement of water stop cock brass CP with inner/outer threads of size 15 mm dia as per existing type and size complete all as specified and directed.
127Supply and fixingin replacement of thermostat switch suitable for water coolers complete all as specified and directed. Make : Danfoss/ Renutrol/ Indfoss or equivalent
128Supply and fixingin replacementof starting relay suitable for water coolers of capacity 150 Ltrs/120 Ltr/80Ltr complete all as specified and directed. Make :- Danfoss/Renutrol/ Indfoss or equivalent.
129Supply and fixingin replacement of starting/running capacitor suitable for water coolers 150 ltrs/120 Ltr/80Ltr complete all as specified and directed. Make :- USHA/UNIVERSAL/ HAVELLS/EPCOS/ sarda or equivalent.
130Supply and fixingin replacement of overload protector suitable for water cooler of capacity 150/120/80 Ltrs complete all as specified and directed. Make :- Danfoss/Renutrol/ Indfoss or equivalent.
131Taking down old and unserviceable sealed compressor and supply and fixing new sealedcompressor unit for refrigerator of capacity 230/310/360 Ltrs includingcleaning, vaccumizing, gas charging of adequate qtyin the unit and soldering/ brazing of suction and discharge and charging line complete all as specified and directed. Make: Kirloskar/ LG/ Voltas/ Godrej/ Hitachi/ Toshiba/ Carrier/Tecumseh/Emerson/CopelandDanfoss.
132All as per item No 130.00 above but for Refg of capacity 165/175/185/180/215 Ltr .
133Taking down old and unserviceable sealed compressor and supply and fixing new sealedcompressor unit for deep freezer of capacity 405 Ltrs includingcleaning, vaccumizing, gas charging of adequate qtyin the unit and soldering/ brazing of suction and discharge and charging line complete all as specified and directed. Make:Kirloskar/ LG/ Voltas/ Godrej/ Hitachi/ Toshiba/ Carrier/ Tecumseh/ Emerson/ Copeland/ Danfoss
134All as per item No 132.00 above but for deep freezerof capacity 200 Ltr .
135Supply and fixing of starting relay with over load protector kit complete as per existing size and type complete all as specified and directed Make :- Danfoss/ Renutol/ Indfoss or equivalent.
136Material and labour for repair/servicing of PCB of double door Refrigerator invertor type all as directed.
137Material and labour in replacement PCB of double door Refrigerator invertor type including necessary wiring to make it functional all as specified and directed
138Material and labour for charging refrigerant gas of existing type in refrigerator of capacity 165 to 360 Ltr including vaccumizing, leakage test and rectification of leakage etc complete all as specifiedand directed.
139All as per item No 137.00 above but for deep freezerof capacity 200 Ltr/405Ltr .
140Supply and fixing in replacement cooling motor with fan, Any sweep suitable to operative on AC,220/240 volts, 50 c/s complete with frame square all as per existing size/type suitable for deep freezers or water cooler all as specified and directed
141Supply and fixing in repair ofsolar water heating element 3 KW Single phase, 230 Volts, ISI marked as per existing type and size complete all as specified & directed.
142Supply and fixing in repairs cylindrical type hot water tank of capacity 1000 Ltrs made food grade stainless steel 304,1.6 mm thick, layered with a galvanized steel shell on the outsidedulyinsulated with 50mm thick PUF of 40 kg / cum density with a standard screw-inport for electrical backup heating element suitable nipple for inlet, outlet, overflow water connection , or any other item required as per site condition including cladding as per existing design complete all as specified and directed.
143Material and labour for fabrication of tray made of GI sheet of size matching to split AC outdoor unit 1.5/ 2 Ton complete with necessary provn of drain and fixing on the outdoor unit stand all as specified and directed
144Material and labour re-painting of desert cooler internally and externally complete with shutters including removing of old paint and preparing surfaces for repainting and applying two coats of synthetic enamel paint by using spray gun complete all as specified and directed.
145Material and labour re-painting of desert cooler water tank internally only including removing of old paint and preparing surfaces for repainting and applying two coats of synthetic enamel paint by using spray gun complete all as specified and directed.
146Material and labour for replacement of outer body of desert cooler as per existing type and size of standard size made of 24 gauge GI sheet and tank of 1mm thick sheet min, suitable for room cooler of capacity 5000 Cum/Hr duly painted complete internally and externally with two coats of super enamelled paint over a coat of red oxide primer all as specified and directed.
147Supply & replacement of fan motor copper wound of capacity 1/8 HP, 1400 RPM, three speed suitable for desert cooler with selector switch complete all as specified and directed. Make: Universal/ Khaitan/ CG
148Supply & replacement ofsubmersible water pump of capacity 18 watt, single phase, 220 V for desert cooler with connecting wire complete all as specified and directed. Make: Universal/ Khaitan /CG
149Supply and replacement Wood wool pad at site for desert cooler any size / cap complete all as specified and directed.
150Supply and fixing in replacement Starting capacitor 4.0 mfd heavy duty suitable for desert cooler complete all as specified and directed. Make: Usha/ Tibeon/ Keltron/ Asian/ Havells/ EPCOS or equivalent.
151Supply and fixing in replacement Top plug 5 Ampall as specified and directed. Make: Anchor/Havells/Cona/SSK.
152Supply and fixing in repair MCB single pole 6-32 Amps, 10 KA all as directed.
153Material and labour for refixing of condensed water pipe line of any size including necessary clamps, joint repairing with solutions and make it leak proof all as directed
154Supply and fix in replacement for UPVC plumbing pipe for drain pipe of ACs condensed waterfixed complete to walls, ceilings or in floors etc. of size 25mm dia, Sch 40 along withsockets, Tees, Bends, Elbows, wall clamps,necessary joining material other accessories required for fixing of pipe with wall/floor all as specified and directed
155Taking down existing Split AC 1.5/2.0 TR indoor unit and outdoor unit complete by disconnecting refrigerant suction and discharge lines, opening nuts and bolts taking out brackets of indoor and outdoor unit from walls, taking out Voltage stabilizer from wall, reinstall in same place after necessary repair work or shifting to another department within Military Hospital"s premises without damaging the AC"S all as specified and directed
156Supply and fixing in replacement Brackets for fixing split AC 1.5/2.0 TR indoor and outdoor unit with walls made of MS duly powder coated factory made with bolts, nuts and washers and 04 Nos of fastenerscomplete all as specified and directed
157Supply and fixing in replacement Floor Standfor fixing split AC 1.5/2.0 TR out door unit made of MS duly powder coated factory made withbolts, nuts and washers and 04 Nos fastenerscomplete all as specified and directed
158Material and labour for shifting of window type AC 1.5 / 2.0 TR by taking out AC from one room and shifting it to another room/department within Military Hospital"s premises and fixing it at place where directed by department all as specified and directed.
159Material and labour for cleaning/descalingofgeyser of capacity 25/35/50 ltr of any make, with chemical solution, checking, tightening all electrical connections, tightening of all nut, bolts, etc completeall as directed
160Taking down geyser any capacity by disconnecting hot and cold water connection and refixing the geyser with new fasteners all as specified and directed
161Taking down geyser of capacity 25 ltrs by disconnecting hot and cold water connection and supply and fixing new geyser 25 ltr cap with fasteners all as specified and directed
162Supply and fixing in replacement geyser inner water tank S/S suitable for Geyser Capacity 50 Ltrs as per existing shape and type complete all as specified & directed.
163Supply and fixing in replacement geyser inner water tank S/S suitable for Geyser Capacity 25/35 Ltrs as per existing shape and type complete all as specified & directed.
164Supply and fixing in replacement geyser assembly brass CP type 9/6/8 hole as per existing type and size complete all as specified & directed
165Supply and fixing in replacement multifunction safety valve for geyser any capacity complete all as specified & directed
166Supply and fixing in replacement gasket for geyser any capacity complete all as specified & directed
167Supply and fixing in repairsgeyser heating element triangle/ cup type 2.0 KW complete all as required /existing at site all as specified and directed
168Supply and fixing in repairsthermostat adjustable type suitable for geyser 25/35/50 Ltr capacity complete all as specified and directed
169Supply and fixing in repairs hot & coldflexible water connection, 600mm long suitable for geyserscomplete all as specified and directed
170Supply and fixing in repairs hot & coldflexible water connection, 450mm long suitable for geyserscomplete all as specified and directed Note: for item No. 77.00 to 169.00 (a) The above mentioned items will be replaced based on day to day complaints and no extra cost will payable for attending complaints. Contractor will quote the rate accordingly. (b) Number of complaints may vary day to day. Contractor shall quote his rates accordingly. (c) In case of failure on the part of contractor for attending complaints a penalty shall be imposed and recovered as specified in Particular Specifications. (d) Contractor shall ensure that the deployed electrician & helper will carry all T&P, live mobile phone while on duty and will be on contact with JE/ Engineer-in-Charge without any extra cost payable to contractor. (e) Contractor shall be responsible for collection of all ON LINE, off line/ telephonic complaints and handing over the same to complaint cell after rectification duly signed by user with details of stores fixed after attending/ completion of the job on the same day. (f) Contractor shall handover min 40% of these items after commencement of workto concerned JE-in-Charge which will be issued for fixing on the basis of day to day complaints. The recovery of Rs 1500 per day shall be levied in case of default
Disclaimer :