Military Engineer Services-MES has published Tender For Special Repair To Fire Alarm System At Various Locations And Installation Of Antistatic Discharge System At Missile Testing Lab At Air Force Station Jaisalmer. Submission Date for this Tender is 30-09-2023. Fire Alarm Systems Tenders in jaisalmer Rajasthan. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 21-Sep-2023 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 28-09-2023 |
2 | 29-Sep-2023 | Due Date Extended | Admin Corrigendum Date Extend | 30-09-2023 |
Sl. No. | Item Description |
1 | Supply, install &testingof analog addressable type self acclimatising multi sensing certified to EN-54 (photo+ heat/smoke) detector with standard mountingbase LED Address switch complete with junction box for mounting on surface/ false ceiling complete with necessary fixing accessories including taking down existing complete all as specified and directed. |
2 | Supply, install &testing of analog addressable type Rate of risecumfixed temperature with standard mountingbase LED Address switch complete with junction box for mounting on surface/ false ceiling/ below false ceing complete with necessary fixing accessories complete all as specified and directed |
3 | Supply, install &testing inrepairs of addressable multi crieteria detector combining 4 fire signatures (smoke + heat+co+ IR) with standard mountingbase LED Address switch complete with junction box for mounting on surface/ false ceiling/ below false ceing including taking down existingcomplete with necessary fixing accessories all as specified and directed |
4 | Supply, install &testingof analog addressable type Self acclimatising multi sensing (photo+ heat)detector with standard mountingbase LED Address switch complete with junction box for mounting on above false ceiling with response indicator on false ceiling with matchingscrews complete with junction box complete with necessary fixing accessories including taking down existing complete all as specified and directed |
5 | Dual LED type response indicatorfincluding including taking downcomplete all as specified and directed |
6 | Supply, install &testingof Addressable dual action pull station with address switch andall mounting accessoriescomplete withjunction box for mounting on surface including taking down existing complete all as specified and directed |
7 | Supply, install &testingof floor wardenstation complete with fireman"s phone jack module with address switch housed in suitable RED enclosure for recessed wall mounting and with latch type or key lock door to the descretion of the consultant with all mounting accessories including taking down existing complete all as specified and directed. |
8 | Supply and install &testingof Addressable Control Module with Address switch and all mountingaccessories complete with junction box for mounting onsurface for sounders and strobes including taking down existing complete all as specified and directed . |
9 | Supply and install in repairs Wall mounted sounder with Strobe Lights with 110 cd complete with junction boxes and accessories for mounting on surface including taking down existing complete all as specified and directed. |
10 | Supplyinstall and testingof addressable monitor module with address switch and all mounting accessories complete with junction box for mounting on surface including taking down existing complete all as specified and directed. |
11 | Supply and installof Addressable Relay Module with Address switch and all mounting accessories complete with pilot relay for Tripping of third party equipment suitable for switching 5A/ 15 A current throughthe relay contact including taking down existing complete all as specified and directed. |
12 | Supply and installof Fault Isolator Module complete with junction box for mounting on surface including taking down existing complete all as specified and directed |
13 | Ceiling mounted voice evacuation speaker having power taps up to 2 W and frequency response of 400 to 4000 Hz for voice Evacuationincluding taking down existing complete all as specified and directed |
14 | Supply and install in repairs wall mounted voice evacuation speaker having power taps up to 2 W and frequency response of 400 to 4000 Hz for voice Evacuationncluding taking down existing complete all as specified and directed |
15 | Supply, install &testingofMicroprocessor based 6 loop capacity Networkable Analogue Addressable type fire Alarm control panel with display and fully functional QWERTYtype keypad comprising ofthe following: (a) The panel shall be equiped with each loop having a maximum loading of 159 detectors and 159 devices in one loop. (b) Fouraccess levels flash EPROM 240 volts AC supply automatic battery charger 24 volts sealed lead acid batteries sufficient for 24 hours normal working and for 2 hours during an emergencyconditions as required. (UL 9th Edition approved) (c) The panel shall have a provn of having high speed network communicationm module with single mode fibre optic connectivity (100 mbps baud rete). (d) The panel shall support peer to peer communication between multiple nodes onthis single mode fibre optic backbone. CPU2-3030D-01 No, SBB-C4-01 No, ADDR-C4-01 No, CA-2-1No, DPA-2B-01No, TELH-1-1 No, BP2-4-1No, AMPS-24E-1 No, CHS-4L-1 No, DP-1B-1 No, LCM-320-2 Nos, LEM-320-2 Nos, DVC-EM-1 No, DVD-KD-1 No, ATD-1 No. (e) Supply of Integrated Digital Voice Command Centre with 2 way Fire Fighters Communication system and shall be capable of supervision of all the speaker circuits. Note: The DVC shall have and integrated 8 channel digital audio command centre with acapacity to connect upto 32 Digital audioamplifiers distributed across various floors of the building on a digital audio loop with zone control function and otheraccessories required to complete the system. DVC shall be capable to select any zone to relayvoice evacuation message from thefire commandstation including taking down existing microprocessor complete all as specified and directed. |
16 | Supply install & testingof Fire fighter telephone instrument including taking down existing complete all as specified anddirected |
17 | Supply install testingof Floorwise serial outlying annunciator (Repeaters) with 640 CharacterBacklit LCD display and fixed fun ction keys and soft keyscomplete all as specified and directed by Eng In Charge. Note: The serial Annunciator shall repeat the signals from the FACP including taking down existingcomplete all as specified anddirected |
18 | Supply install andtesting in repairs of digital audio amplifier capable of processing one of 8 audio channels and total of 50 W at 70.7 VRMS output along withnecessary enclosures. The shall be fully monitored for fault and alarm reportin g. The proposed digital amplifiersshall not be rail mounted/ dependent on fire panel CPU for operation complete as specified and comprising of the following: DAA-5070E-09 Nos, BDA-70V-8 Nos, EQBB-D4-2 Nos, EQDR-D4-2 Nos complete all as specified anddirected |
19 | PVC insulated , multistranded Zero halogen low smoke fire survival FRLS cable 2 twisted pair 1.5 sqmm copper conductor in conduit confirming to IS 694 and ISI marked cable complete all as specified and directed |
20 | PVC insulated FRLS 6Core 1.5 sqmm multistranded copper conductor cable in conduit confirming to IS 694 and ISI marked cable complete all as specified and directed |
21 | Rigid non metallic PVC conduit 25 mm diainclusive ofboxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube endsand fixing accessories such as couplers lock nutssaddles pipe hooks as etc required complete all as specified and directed |
22 | Analog Addressable Type Manual Call Point having Surface or flush mounting Option fully complaint to EN54 having Rotary Decade Swicthes for Addressing from 01-99 complete with Back Box for Mounting Complete as required conforming to BS5839 Standards and Duly Approved by EN54/LPCB including taking down existing complete all as specified and directed .Make : Honeywell Morley,Siemens , |
23 | Addressable Type Loop Powered Sounder complete with Mounting Base as required conforming to BS5839 Standards and Duly Approved by EN54/LPCBincluding taking down existing complete all as specified and directedMake : Honeywell Morley , Siemens, Gent |
24 | Supply install & testing 2 Loop Micro processor based 1 wire fault tolerant loop, required loop networkable type(each loop accessing99 detectors and 99 modules ) fire alarm/detection control panel.The panel shall be able to givelocation ofall fire/fault conditions of addressable units via the address codes.Further, the panel must be able to automatically switch ON /OFF respective control modulewhen ever any alarm is triggered.The panel shall have rectifier, Loop cards, 80 character LCD unit to indicate Fire/Fault Signal with addresses. The Panel Shall be Sheet Steel Painted, sealed to IP30. The panel have provision to integrate with PA System . The panel shall have a built in power supply and battery charger along withmaintenance free 24 AH, 2x 12 volt SMF dry batteries capable of running for a minimum of 48 hours with battery charger complete as required including taking down existing and conforming to BS5839 Standards and Duly Approved byEN54/LPCB. GSM Auto dialer intigration required. Make:Honeywell Morley,/ Gent,/Siemens |
25 | Battery charger along withmaintenance free 24 AH, 2x 12 volt SMF dry batteries capable of running for a minimum of 48 hours with battery charger suitable for fire alarm control panel microprocessor based including taking down existing complete all as specified and directed |
26 | Electric siren system, AC, 415 V, 50 HZ, including necessary foundation and protection from rain water of range 2 Kmsinstalled at roof ofBldgfincluding taking down existing complete all as specified and directed |
27 | Supply, fixing and connecting in repairs conventional optical smokeDetectors Complying with and type certifiedcomplete with standard base for conventional detector including taking down existing complete all as specified and directed |
28 | Supply, installation, commisioning and testing in repairs 02 zone conventional fire alarm control panel with features such as non latching zones, false alarm management, EN 54-2, EN 54-4 LPCB approved including taking down existingcomplete all as specified and directed. |
29 | Supply, installation, commisioning and testing in repairs 04 zone conventional fire alarm control panel with features such as non latching zones, false alarm management, EN 54-2, EN 54-4 LPCB approved including taking down existing complete all as specified and directed. |
30 | Supply, fixing and connecting in repairs conventional type manual call point resettable including taking down existingcomplete all as specified and directed. |
31 | Supply, fixing, connecting and testing conventional wall sounder including taking down existing complete all as specified and directed. |
32 | Copper strip 20 x 3.15mm with saddles and fixing screw etc for roof conductors and down conductors above ground and connected to existing earthingcomplete all as specified and directed |
33 | Antistatic flooring 3 mm thick vinyl for electrostatic discharge as per manufactures specification complete including scraping down the existing surface to finished lwvel appropriate for laying of the ESD surface complete all as specified and directed. |