National Security Guard-NSG has published Tender For Operation Repair And Maintenance Of Fire Fighting Equipments For The Year 2023 24 Sh Maintenance On Routine Basis. Submission Date for this Tender is 05-09-2023. Fire Fighting Consumable Tenders in manesar Haryana. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Preventive Maintenance of the Pumps Make KBL as per Pump List Attached. The agency will undertake the maintenance work of the pumps only through the OEM or OEM authorized dealer. |
2 | UP150/45 |
3 | CPHM 40/26 |
4 | DSM80/36 |
5 | DB32/26 |
6 | DB50/16 |
7 | DSM100/36 |
8 | DSM 125/40 |
9 | RKB 40/12 L5 |
10 | KDI 1348+ |
11 | KDI 2095+ |
12 | DB 40/26 |
13 | Scope of work covered under the preventive maintenance |
14 | One visit in year will be made by an OEM (KBL) service person with priorintimation. |
15 | One breakdown visits included under AMC. |
16 | Complete check-up of the Pump sets as per KBL standards. |
17 | Check free rotation of pumps. |
18 | Check tightness of casing bolts, Foundation bolts, and Grease MS Fasteners. |
19 | Oil levels, grease in bearings, Condition of bearing to be checked and replenished if required(Spare shall be provided by deptt) |
20 | Vibration, Noise, Bearing Temperature, Voltage, Speed and pressure to be measured and recorded. |
21 | Alignment of pump set to be checked and in case if required rectification to be carried out and readings to be recorded. |
22 | Coupling bushes, pins, rubber parts to be checked and to be replaced if required.(Spare shall be provided by deptt) |
23 | Mechanical seal condition to be checked and suitable recommendations to be made. |
24 | Service report will be generated afterevery visit recording data anddetails of above checks. |
25 | Overhauling Charges of the following Pump including Dismantling, Machining , Oiling , Greasing , Assembling & Installation at Site includingloading and unloading,to and fro transportation ofpump from NSG Campus Manesar to the workshop. The work will be done through the OEM or OEM-authorized dealer of the pumps, and the repair work will be given a three-month warranty by the OEM/authorized dealer. |
26 | UP150/45 or DSM80/36 or RKB40/12L5 or DSM100/36 or DSM125/40 |
27 | CPHM40/26 |
28 | DB32/26 or DB50/16 or DB40/26 |
29 | KDI 1348+ or KDI2095+ |
30 | Replacement of the following spare parts of the existing KBL Pump UP150/45 "Kirloskar" make main fire pump drive by electric motor 90KW/120HP capacitywith a new one if found defective, including testing, complete as required, including credit for old scrap material which will be retained by the contractor etc., complete as required. |
31 | Sleeve MOC-Bronze (17458CQ001012) |
32 | set of Gasket MOC- Non asbestos |
33 | O- ring MOC- Natural Rubber |
34 | Ball Bearing 2877 MOC-SS (X630900400000) |
35 | Wear Ring MOC-Bronze(1712021991012) |
36 | Rewinding of (from 12.5 HP up to 120 H.P. three-phase capacity) electrical motors including all necessary material and of the same characteristics as original with required size of super enamelled copper wire and F class insulation material including dismantling, removing of burnt wires, cleaning of slots, varnishing, assembling, greasing, testing etc. complete as required including credit for old scrap material which will be retained by the contractor etc., complete as required. The work will be done through the OEM or OEM-authorized dealer of the pumps, and the repair work will be given a three-month warranty by the OEM/authorized dealer. |
37 | Preventive Maintenance of the Air Compressor Make INGERSOLL RAND AIR COMPRESSOR. The agency will undertake the maintenance work of the Air Compressor only through the OEM or OEM authorized dealer. |
38 | INGERSOLL RAND AIR COMPRESSOR Model -2475 |
39 | Scope of workincludes 04 No preventive visit & 02 Nos breakdown visit in year |
40 | Replacement of the following spare parts of the existing INGERSOLL RAND AIR COMPRESSOR drive by electric motor 3.7KW/05 HP capacitywith a new one if found defective, including testing, complete as required, including credit for old scrap material which will be retained by the contractor etc., complete as required. The work will be done through the OEM or OEM-authorized dealer . |
41 | CRANKSHAFT ASSY WITHBRG FOR 2475 |
42 | BUSHING, CRANK PIN |
43 | ROD CONNECTING - 2475 242 |
44 | CYLINDER, 4¡± L.P. (2475) |
45 | CYLINDER, 2.5" H.P.(2420/2475) |
46 | PISTON & PIN ASSY 4 IN LP2475 |
47 | ASSEMBLY PISTON PIN HP2475 |
48 | PIN, PISTON 4" |
49 | PIN, PISTON 1/2" |
50 | VALVE, PLATE ASSY., LP. |
51 | VALVE, PLATE ASSY, HP |
52 | KIT COMPLETE OVERHAUL 2475 |
53 | RING PISTON 4 IN LP |
54 | RING PISTON SET 2.5HP |
55 | GASKET SET FOR 2475 |
56 | VALVE SAFETY 1/2 BSPT * 190 PSIG |
57 | ELEMENT FILTER F-LINE 10 MICRON |
58 | VALVE CHECK 3/4 BSPT X 3/8NPT |
59 | OIL CONTAINER 5 LTRS -T30 DISTINCT |
60 | Supply, installation, testing, and commissioning of addressable Manual Call Point Complete as requiredMake- Edward/Apollo/Siemens/ Notifier or equivalent |
61 | Supply, installation, testing, and commissioningof intelligent analog addressable photo thermal detector complete with mounting base complete as required Make- Edward/Apollo/Siemens/ Notifier or equivalent |
62 | Supply, installation, testing, and commissioning of intelligent addressable programmable sounder complete as requiredMake- Edward/Apollo/ Siemens/ Notifier or equivalent |
63 | Supply, installation, testing, and commissioning of addressable fire control module complete as required Make- Edward/Apollo/Siemens/Notifier or equivalent |
64 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinkler of rating 68 degree centigrade with required accessories(Pendant/upright sprinkler) |
65 | Supply, installation, testing, and commissioning of addressable horn cum Strobe Complete as required .Make- Edward/Apollo/Siemens/Notifier or equivalent |
66 | Supply, installation, testing, and commissioning of wall speaker 1.5/3/6 W Metal Box ceiling /wall speaker complete as required Make - Honeywell/Bosch/Ahuja or equivalent |
67 | Dismantling , Cleaning & Re-fixing intelligent detector , hooter , manual call fixing & respond indicators including checking, testing and connection etc. as required. |
68 | Supply installation testing commissioning of SMPS device compatible with two or four loop fire alarm panel make Est3 or equivalent including credit for old unserviceable SMPS which will be retained by the contractor etc., complete as required. as per direction of engg in charge . |
69 | Servicing , Commissioning and reprogramming of existed addressable fire alarm panelcompatible with EST3 etc.complete as required. |
70 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : 13.61.1 Two or more coats |
71 | Supplying & fixing transparent acrylic sheet 6mm in the existing fire hose cabinet with rubber beading including removing of existing glass/acrylic sheet if required and credit for old scrap material which will be retained by the contractor . |
72 | Supplying & fixing rubber beading of standard make in the existing acyclic/glass panes of the fire hose box as required . |
73 | The road crossings of power cablethrough trenchless boring. Trenchless boring using Manual/ Machine Moling techniqueat 0.75 metre below the ground level for following size pipes,including survey of under ground utilities,excavation of pits,moling with the hole size not exceeding 20% of the pipe dia,backfilling, compaction and restoration of the pits to original condition etc. as required. The rates for moling, as indicated are inclusive of excavation of pits, backfilling, compaction andrestoration of the pits to original condition. Any damages occurred to other utilities during the Moling operation shall be immediately notified and rectified by the contractor without any cost implication to the Department. The length of the Hole (excluding the sizes of the pits on both ends) shall be considered for the measurement of Moling length. However, intermediate pits will consider in the moling length. i)Upto 200 mm dia DWC HDPE / G.I. /PVC |
74 | Supplying and laying of following sizeDWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc.conforming toIS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. |
75 | 200 mm dia (OD-200 mm & ID-175 mm nominal) |
76 | Supplying and laying of following sizeDWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc.conforming toIS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
77 | 200 mm dia (OD-200 mm & ID-175 mm nominal) |
78 | Supply, installation, testing, and commissioning of an outdoor type totally enclosed, dust and vermin proof, pedestal mounted INSPECTION BOX/JUNCTION BOX of sufficient size but not less thanfront area 0.54sq mtr &500 mm (deep)made of 2 mm thick CRCA sheet steel, with front and back openable doors with locking arrangements on both sides, a tapered top (roof), including detachable cable gland plates made of 3 mm thick CRCA sheet steel,including pre paint treatment, phosphating and powder coating by approved Siemens grey paint, with 500 Amps of 4 strip aluminium bus bar, etc. as required. suitable for operation on a 433 volt, 50 Hz, 3 phase, 4 wire A.C. supply system, earthing stud, and danger notice plate fixed as required. The feeder pillar shall be supplied with a suitable mounting frame of 50 mm x 50 mm x 6 mm angle iron frame with 900 mm oflong legs. The 4 legs of the feeder pillar shall be erected on a suitable size 1:3:6 cement concrete (1 cement : 3 sand: 6 graded stones of 20 mm size) pedestal having 900mm of depth (600mm below ground & 300mm above ground) including plastering, complete as per specifications. (Drawings will be approved before fabrication.) |
79 | Supplying and Laying of one number aluminium conductor, XLPE Insulated, PVC sheathed, armoured power cable of 1.1 kV grade , confirming to IS : 7098 (Part-1) 1988 of following size in the existing RCC/ HUME/ METAL pipe as required. |
80 | 3.5 x 400 sq. mm |
81 | Supplying and Laying of one number aluminium conductor, XLPE Insulated, PVC sheathed, armoured power cable of 1.1 kV grade , confirming to IS : 7098 (Part-1) 1988 of following size direct in ground including excavation and refilling the trench etc. as required, but excluding sand cushioning and protective covering. |
82 | 3.5 x 400 sq. mm |
83 | Supplying and Laying of one number aluminium conductor, XLPE Insulated, PVC sheathed, armoured power cable of 1.1 kV grade , confirming to IS : 7098 (Part-1) 1988 of following size in the existing masonry open duct / along pole / loose for connections etc. as required. |
84 | 3.5 x 400 sq. mm |
85 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required |
86 | 3½ X 400 sq. mm (82mm) |
87 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
88 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
89 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
90 | P/F of DOL starter on the existing panel/wall(as per direction of Engg in charge) suitableupto 7.5 HP three phase induction motor model MK1Make L&T or equivalent BCH/Siemens/Havells including making incoming and outgoing connections with suitable size of thimbles testing etc. as required. |
91 | SITC Pressure Gauge mild steel bottom connectionmin range 0-14 Kg/cmsq including connection pipe and accessories complete in all respect (Make - H.Guru/FieBig) |
92 | SITC Pressure Gauge range 0-16 Kg/cmsq glycerine filled including connection pipe and accessories complete in all respect (Make - H.Guru/FieBig) |
93 | Dismantling the Undermentioned type ofValve from the site ,servicingi/c descaling the rusted components , cleaning & washing with acid ,lapping of matting seat & surfaces ,replacing the rubber components ,gland & packing , assembling & re-installing at same location with testing etc. required at site .(Item includes Transportation from Site to Workshop & vice-versa) |
94 | Fire Alarm (Gong) Valve Size 150 mm |
95 | Deluge Valve Size 100mm |
96 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) 40mm nominal bore |
97 | Supplying & fixing Air vent valve screw end size 3/8" DN10at casing of UP150/45 pump as required |
98 | SITC automatic battery charger 12V DC suitable to charge battery upto 150Ah with connection etc. required |
99 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. Make Denfoss/Indfos/Sitzer |
100 | Supplying and installation of 380 mm sweep, 1400 RPM heavy-duty, single phase, metallic exhaust fan Conforming to IS:2312 -1967in the existing opening, including making the hole to suit the size of the above fan and making good the damage, connection, testing, commissioning etc. as required.(HavellsTurbo force Heavy Duty Exhaust Fan or with similar specifications C&G / Orient / Usha / Almonard) |
101 | Making holes upto 400mm in RCC Beam /slab/wall withcore cutter for fixing exhaust fan purpose etc. and repairing ,finishingthe hole etc. all complete as per direction of engg in charge . |
102 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.(Group C) |
103 | Supply, installation, testing, and commissioning of integrated LED Batten luminaire, 1200 mm (nominal size) with a minimum system lumen output of 4000 lumen and with a minimum system luminous efficacy of 120 lm/W, made of aluminium housing having a colour temperature5500K - 6500 K, Average life L70B50: 50000 hours, THD = 15%, suitable for operation on 140-270V, 1F, 50Hz AC supply system, complete with all accessories, electronic driver, diffuser, directly on the ceiling/wall, including connections, earthing, etc. as required. |
104 | P/Fdoor locks in the existing Hydrant Panel Box i/c credit the cost of unserviceable item . |
105 | SITC of breakable glass of standard thickness & standard makein manual call points as required |
106 | Providing& fixing MS Plate of required size ,shape & thickness on existing strainer ,MS Tank & pipes etc. including cutting , welding & making it leakage proof etc. as required . |
107 | Providing, installation, testing & commissioning of water curtain nozzle 15/20 mm dia nickel chrome plated brass, BSPT, K-factor as per design consideration complete as required |
108 | Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required |
109 | 80mm dia |
110 | 150mm dia |
111 | 200mm dia |
112 | 250mm dia |
113 | Providing, laying, testing & commissioning of "C" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling or on pipe with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
114 | 100mm dia |
115 | 150mm Dia |
116 | Providing, installation, testing & commissioning of non-return valve of following sizeconforming to IS 5312 complete with rubber gasket ,GI Bolts ,nuts ,washers etc. as required |
117 | 250mm dia |
118 | Supplying, fixing, testing and commissioning of butterflyvalve of PN 1.6 rating with bronze /gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : |
119 | 80mm |
120 | 100mm |
121 | 200mm |
122 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
123 | Providing and fixing following switch gears, meters and accessoriesin existing cubicle panel/starter board including drilling holes in cubicle panel, making connections, etc. as required including credit for old scrap material which will be retained by the contractor etc., complete as required. |
124 | 3Pole,415V , Power contactor AC3 rating 18 A |
125 | 3Pole,415V , Power contactor AC3 rating 25A |
126 | 3Pole,415V , Power contactor AC3 rating 32A |
127 | 3Pole,415V , Power contactor AC3 rating 70A |
128 | 3Pole,415V , Power contactor AC3 rating 110 A |
129 | Overload thermal relay MN2 L&T 9-15A |
130 | Overload thermal relay MN2 L&T 14-23A |
131 | Overload thermal relay MN5 L&T 66-110A |
132 | Add on Block 2NO+2NC |
133 | Add on Block 1NO+1NC |
134 | Operating Handle Kit (handle + shaft + center bush + bush clip) CO5-(630-1000A) |
135 | Providing & fixing MSClamp suitable for existing fire extinguisher ( Dry Powder 06 kg / Water Spray 09 Ltr / CO2 type 4.5 Kg) |
136 | Dismantling existing fire extinguisher from the location ,evacuate the cylinder gas/powder as per IS-Standard, refilling the gas/powder ,weigh , pasting record stickers , cleaning the outer area properly & install with records at site as per direction of engg-in-charge (No extra amount paid for transportation for taking the extinguisher to & fro from the site to workshop) |
137 | 5kg/6kg -ABC type Fire Cylinder |
138 | 4.5Kg -CO2 type Fire Cylinder |
139 | Hydraulic pressure testing charge of following capacity existing fire extinguisher as per IS Code -2190 (Testing Report Should be submitto department ) |
140 | ABC type 9 litre / CO2 type 4.5 kg/Water spray type 9 litre |
141 | Dismantling the existing undermentioned fire extinguisher from the CO2 flooding system at Magazine site ,evacuate the cylinder gas as per IS procedure & environment safety norms for hazard gas ,carrying Hydraulic pressure testing as per IS code, refilling the same gas assame previous weight, pasting record stickers , cleaning the outer area properly & install & commissioning at the original location with complete connection ,submitting records . (The above work shall be carried through OEM or OEM Authorised dealer & No extra amount will pay for transportation for taking the extinguisher to & fro from the site to workshop) |
142 | CO2 Fire Extinguisher (Weight CO2 Gas -45 Kg ) |
143 | Nitrogen Gas (Pilot Cylinder) |
144 | Replacement of the following spare parts in the existing CO2 flooding fire-fighting system with a new one if found defective, including testing, complete as required, including credit for the old, unserviceable replaced spare part, which will be retained by the contractor, etc., complete as required. The above work shall be carried out through an OEM or OEM-authorised dealer. |
145 | Discharge Hose |
146 | Electro manual Pneumatic Valve for Nitrogen Cylinder |
147 | Credit for old unserviceable Item like Sluice valve ,NRV , pipe ,flange etc.i/c dismantle from the site & weighing in presence of deptt representative as required . |
148 | Credit for old unserviceable Item like copper from motors etc.i/c dismantle & weighing in presence of deptt representative as required . |
149 | Add 1.0633 multiplying factor for GST on DSR |