All India Institute Of Medical Sciences-AIIMS has published Tender For Supply Installation Testing And Commissioning Of Fire Pump System And Fire Protection System For Hostels, Auditorium, Service Buildings At Aiims Campus Raipur. Submission Date for this Tender is 11-09-2023. Fire Protection System Tenders in raipur Chhattisgarh. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump). (a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-"F" insulation, conforming to IS-325.(c) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required.(d) Suitable cement concrete foundation duly plastered and with anti vibration pads. |
2 | 900 lpm at 35 m Head |
3 | 450 lpm at 35 m Head |
4 | Supply, Installation , Testing & Commissioningof Electrical Motor control panel of size 1.25 mtr x 1.20 mtr x 0.3 mtr depth with suitable copper busbar for Terrace Pumps of cubical construction , feeder piller type double door floor/Wall mounted, fabricated out of 2mm thick CRCA sheet, compartmentalized with hinged lockble doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with solid aluminum strip/ single core PVC insulated FRLS copper conductor cable , having suitable mounting for switchgears and accessories and internal control & power wiring with suitable rating PVC insulated FRLS copper conductor, earth terminals, numbering etc. complete in all respects, suitable for operation on 415V, 3 phase 50 HZ. AC supply with enclosure protection class IP 42 with suitable rating copper busbar as required. Incoming a) MCCB, 4pole 100A,10KA with adjustable thermal magnetic release and ICS=10KA upto 433V=1 No b) Digital Ammeter (0-100A),96mm sq. CT operated with selector switch with 3 nos CTs of ratio 60/5A,10VA burden c) Digital voltmeter (0-500V) 96mm sq. with selector switch and HRC control fuses-1 set d)phase indicator RYB LED with control fuses-1 set Outgoing e)fully automatic star delta starter suitable for Terrace pump current sensing type single phase preventer complete with all accessories and wiring etc. as required-2set f)Selector switches for Auto manual operation, and ON/OFF/Trip indications-2set g) MCCB TP,63A,10KA -2set. |
5 | Providing & fixing ofpressure switch in M.S. pipe line including connection etc. as required. |
6 | Supplying, installation, testing & commissioning sector panel suitable for following zones, complete with visual indications for short circuit fault, open circuit fault, fire condition and all other standard facilities as per IS:2189 with mimic diagram for all area/zone covered along with battery arrangement for power backup complete with all connections, interconnections as required. |
7 | 4 Zone |
8 | FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL) |
9 | Supplying, installation, testing & commissioning of heat detector operating at 54ºC/57ºC with rate of rise cum fixed temperature (dual thermistor) type with mounting base complete with all connection etc. as required. |
10 | Supplying, installation, testing & commissioning of smokedetector with builtin LED and mounting base complete with all connections etc. as required. |
11 | Supplying,installation,testing&commissioningofmanualcallboxesofMS constructionin surface/recesswithstainlesssteelchain&hammerassembly complete with glass and push button etc. as required. |
12 | Supplying, installation, testing & commissioning response indicator on surface/recess MS box having two LEDs metallic cover complete with all connections etc. as required. |
13 | Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required. |
14 | CABLING & WIRING |
15 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. |
16 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required. |
17 | Supply, Fixing and commissing ofburden type Stainless Steel dial type pressure gauge with brass isolation valve and pipe. (For each internal Fire hose cabinet)Dial diameter 100 mm, calibration 0-15 kg. |
18 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with matching flanges rubber, insertion nuts, bolts and washers,gaskets conforming to IS 13095of following sizes. |
19 | 50 mm dia |
20 | 80 mm dia |
21 | 100 mm dia |
22 | 150 mm dia |
23 | Supply, Fixing and commissing of single acting air valve of 25 mm dia as per IS : 14845 including 25 mm dia Ball valve and all fitting etc. as per the requirement. |
24 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with matching flanges, rubber insertion, nuts bolts and washers etc of following sizes. |
25 | 80 mm dia |
26 | 150 mm dia |
27 | Providing, laying, testing & commissioning of "C" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
28 | 40 mm dia |
29 | 50 mm dia |
30 | 80 mm dia |
31 | 100 mm dia |
32 | 150 mm dia |
33 | Supply, Installation Testing and Commissioning 4Cx6 Sqmm copper armourd cablefor pump set connection along with complete acessories as required. |
34 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors,suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. |
35 | 100 mm width X 50 mm depth X 1.6 mm thickness |
36 | Brick work with clay flyash F.P.S. (non modular) brick of class designation 7.5 in superstructure above plinth level up to floor five level in : |
37 | Cement mortar 1:6 (1 cement : 6 coarse sand) |
38 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. |
39 | In stringers, treads, landings etc. of stair cases, including use of chequered plate wherever required, all complete |
40 | Extra for providing and mixing water proofing material in cement per bag of plaster work in proportion recommended by the manufacturers. |
41 | 12 mm cement plaster finished with a floating coat of neat cement of mix : |
42 | 1:4 (1 cement: 4 fine sand) |
43 | Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. |
44 | In cement mortar |
45 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
46 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. |
47 | 32 mm nominal dia Pipes |
48 | 50 mm nominal dia Pipes |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy