Tender For Repair / Maintenance And Replacement Of Fire Pumps, Fire Pipe Lines, Fire Hydrant And Allied Works For Fire Fighting And Fire Alarm System For Tech And Residential Area At Deal Under Ge ( I ) Rnd Dehradun, dehradun-Uttarakhand

Military Engineer Services-MES has published Tender For Repair / Maintenance And Replacement Of Fire Pumps, Fire Pipe Lines, Fire Hydrant And Allied Works For Fire Fighting And Fire Alarm System For Tech And Residential Area At Deal Under Ge ( I ) Rnd Dehradun. Submission Date for this Tender is 11-09-2023. Alarm Systems Tenders in dehradun Uttarakhand. Bidders can get complete Tender details and download the document.




Tender Notice

39068670
Corrigendum : Tender For Repair / Maintenance And Replacement Of Fire Pumps, Fire Pipe Lines, Fire Hydrant And Allied Works For Fire Fighting And Fire Alarm System For Tech And Residential Area At Deal Under Ge ( I ) Rnd Dehradun
Open Tender
Indian
Uttarakhand
dehradun
11-09-2023

Tender Details

Repair / Maintenance And Replacement Of Fire Pumps, Fire Pipe Lines, Fire Hydrant And Allied Works For Fire Fighting And Fire Alarm System For Tech And Residential Area At Deal Under Ge ( I ) Rnd Dehradun

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 30-Aug-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 06-09-2023
2 06-Sep-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 11-09-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 15000.0 /-
Tender Value
INR 7.50 Lakhs /-

BOQ Items

NAME OF WORK : REPAIR/MAINT AND REPLACEMENT OF FIRE PUMPS, FIRE PIPE LINES, FIRE HYDRANT AND ALLIED WORKS FOR FIRE FIGHTING AND FIRE ALARM SYSTEM FOR TECH AND RESIDENTIAL AREA AT DEAL UNDER GE (I) R&D DEHRADUN
Sl. No. Item Description
1Disconnecting,removing the water, electric connections and taking out carefully the old existing defectiveelectric motor, 7.5 HP of booster pump / centrifugal pump of any description and in any position, dismantling and strip opening of the motor, removing the old existing burnt windings, cleaning the slots & rewinding of the electric motor 12.5 HP, operating on 415 V, 3 Phase, 50 Hz AC supply with existing gauge super enameled copper wire, including insulating material such as illuminous paper, Letherized paper, cotton tape, glass sleeves insulating varnish etc for powering multistage booster pumps/ centrifugal pumps & testing at workshop and transportation to site & refixing on existing platform complete, all as specified and directed.
2All as per item No. 1here in above but motor of capacity 25.0 HP complete, all as specified and directed.
3M&L for Disconnection electrical and water connection of the 12.5/21 HP centrifugal pump and transported to work shop opening carefully and replacement of bushes, gland packing, ball bearing, rubber gasket nut and bolt etcand fixing the require new parts excluding Item No (a) to (d) complete supply and repair and complete re-fixing its in original position and making out all electrical and water connection and testing complete all as specified. Note :- Rate includes transportation of motor from the place of installation for repairing and reinstalling the same on existing foundation & testing & commisioning.
4Supply only shaft suitable for centrifugal pumps
5Supply only GM impeller suitable for centrifugal pumps
6Supply only MS coupling suitable for centrifugal pumps
7Supply only bearing suitable for centrifugal pumps
8Disconnecting, removing the water, electric connectionsand taking out carefully defective booster/centrifugal pump of capacity 105 HP, DSM model of Make Kirloskar,, three phase, 415 V, AC supply and carrying out necessary repairs and replacement of bearing bush, gland plate, impeller, nuts and bolts etc, any trasportation to workshop if required, Repair to bearing housing with metling and turningand fixingthe same in position and testing on full load complete, all as specified and directed.
9Dismantling and opening of spare parts for servicing of water cooled DG set of following capacity coupled with alternator, Maintenance and servicing mechanically and electrically, including cleaning, oiling /greasing,removing & replacement of defective / unserviceable parts with new parts,i.e diesel filter /oil filter /Air filter /fan belt /fuel pipe/ engine oil pipe /Engine Oiletc as required at site and manufacturer"s instructions and checking of valves & nozzles etc, reassembling the parts of capacity 105 HP/ 75 KW DG set at position ensuring proper alignmentconnecting to existing system and making DG set perfectly operational and testing at site connected load to the entire satisfaction complete all as specified and directed. Notes:-(i) The quoted rates of the contractor includes for fixing the serviceable parts in position and replacement of unserviceable parts with new parts.The new replaced parts shall bemeasured and paid for separately under appropriate item of Sch `A’ as `supply only ‘ but quoted rates are inclusive of replacement of small/minor parts such as nuts, bolts, washers, locking nuts, small springs, `O’ rings, screws/gaskets/ packing /studs etc. (ii) Engine oil shall be drained out carefully, collected by the contractor in his own suitable containers and stored properly for checking serviceability including cleaning of oil sump by pouring kerosene oil complete, all as specified and directed. (iii) Fresh engine oil for DG sets shall be supplied by the contractorand cost of engine oil andfilling is deemed to be included under the rates quoted by the contractor for above item.
10Supply, installation, testing and commissioning in replacement of UNSV Stainless steel 63mm dia short size branch pipes with 15/20 mm dia nozzles with 63mm instantaneous coupling ISI marked (IS: 903) complete all as specified and directed.
11Disconnecting and taking out carefully old unserviceable valve and Supply & fixingfire hydrant valve 63mm dia single headed including flanges, nut, bolt, washers etc complete all as specified & directed.
12Taking out or downdefective Fire hydrant valve from main line andopening carefully old defective Fire hydrant valveof any description and in any position for and including servicing, over-hauling / greasing etc, and replacement of old unserviceable / worn out parts and reassembling the Fire hydrant valve after repair and refixing the same & testing after installation complete all as specified and directed. Note:- (i) Spare part will be measured and paid for separately as supply onlyunder appropriate items of Schedule ‘A’
13Supply only Gun Metal hydrant coupling suitable for existing Fire Hydrant valve
14Supply only Wheel suitable for existing Fire Hydrant valve
15Supply only Gland nut of gun metal suitable for existing Fire Hydrant valve
16Supply only Rubber packing for coupling suitable for existing Fire Hydrant valve
17Supply, fixing, testing and commissioning in replacement of UNSV of wall mounting swinging type First aid firehose reel with drum, hanging bracket,Thermoplastic rubber (first aid hose) as per IS 1258520 mm dia 30 mtr length to with stand 20 kg per Sq cm working pressure fitted with gunmetal nozzle and shut off valve of any size complete all as specified. The hose reel shall be conforming to IS 884-1985 includingfor 25 mm dia MS pipe connection from riser to hose reel sockets,nipples,elbows,valve etc. Drum shall be fixed on adjoining wall through anchor fasteners/cement concrete hook or MS stand as per site requirement and the rate for fixing/hanging items in the rates quoted(for internal hydrant and one each an either side of stage)including taking down the existing one complete and depositing to MES store yard complete all as specified and directed.
18Disconnecting and taking out carefully old unserviceable hose box and Supply & fix hose box made of 18 gauge MS sheethaving a minimum size 800mmx600mmx250mm and a maximum size of 1200mmx600mmx250mm with double door with 4mm thick glasses and door frame made of 16 gauge MS sheet painted fired out side and brilliant white inside yard complete all as specified & directed.
19Disconnecting and taking out carefully old unserviceable pressure gauge and Supply & fix water pressure gauge 4" dia range 0-14Kg per cm square, complete all as specified.
20Supply and fixing of 4 mm plain glass along with Rubber Beating etc change in FHC complete all as specified and directed.
21Disconnecting and taking out carefully old unserviceablesluice valve and supply & fixing sluice valve 150 mm dia with stainless steel spindle CI body class I ISI marked PN 1.6 both end flange and drilled and fixed by means of bolts, nuts and washers including providing rubber insertion of suitable thickness for 150mmmm dia size, complete all as specified and directed.
22All as per item no 17 here in abovebut 100mm dia
23All as per item no 18 here in abovebut 80 mm dia
24Disconnecting and taking out carefully old unserviceable MS pipe and Supply & laying in trenches MS pipe ERW including specials, nominal dia 150 mm dia size including welding, complete all as specified and directed.
25All as per item No. 20here in above but 100mm dia
26All as per item No. 20here in above but80 mm dia
27Disconnecting and taking out carefully old unserviceable butterfly valve and supply & fixing butterfly valve 150 mm dia both end flange and drilled and fixed by means of bolts, nuts and washers including providing rubber insertion of suitable thickness, complete all as specified anddirected.
28All as per item No 23 here in abovebut 100mm dia
29All as per item No 23 here in abovebut 80 mm dia
30Supply, installed, jointing and testing in replacement of unserviceable non return valvesofsize 100 mm bore cast iron both ends flangedcomplete all as specified and directed. Notes:- (i) The cost of Earth work, joints & jointing materials of thenon return valve shall be deemed to be included in the quoted rates.
31Supply, installed, jointing and testing in replacement of unserviceable Foot Valve of size 150 mm (6”) dia.of cast iron both ends flanged conforming to IS 4038, complete all as specified and directed.
32Taking out or downdefectivesluice valve of size 150 mm borefrom main line andopening carefully old defective sluice valve of any description and in any position for and including servicing, over-hauling / greasing etc, and replacement of old unserviceable / worn out parts and reassembling the sluice valve after repair and refixing the same & testing after installation complete all as specified and directed. Note :- (i)The cost of Earth work, joints & jointing materials washers, gaskets ,necessary welding,nut,bolts ,washerand minor parts shall be deemed to be included in the quoted rates but Replacement of the defective parts i.e. stainless steel spindle of Sluice valve shall be measured and paid for separately as supply onlyunder appropriate items of Schedule ‘A’
33All as per Srl item No. 28 here-in-before but size 100 mm bore
34All as per Srl item No. 28 here-in-before but size 80 mm bore
35Supply only stainless steel spindle, heavy duty, threaded, with and including one gun metal check unit suitable for sluice valves of size 150 mm boreany descriptiondismantled/fixedunder appropriate items ofSch `A`
36All as per Srl item No. 31 here-in-before but size100 mm bore
37All as per Srl item No.31 here-in-before but size80 mm bore
38Excavation in trenches in any type of soil not exceeding 1.5 metre deep and not exceeding 1.5 mtr width and getting out soil including forming bottom surface to required slope/gradient forlaying cables/pipes etc.all as specified and directed by Engineer-in-Charge including removing cable protection covers/ bricks & stacking serviceable bricks for reuse and disposal of unserviceable covers within 50 m all as directed. Note : (i) Excavation shall be made carefully in order to avoid damage of existing cables and brick protection. (ii) The excavation work may be carried out in short lengths for locating fault in under ground cables at different locations
39M&L for Returning, filling in including spreading, leveling, watering and well ramming in layers of25 cm thickafter the cables etc. are laid, jointed and tested complete all as specified and directed.
40M&L for Removal of surplus excavated soils not exceeding 50 Mtr distance and depositing where directed by Engineer-in-Charge at a level not exceeding 1.5 m above the starting point complete all as specified and directed.
41Disconnecting and taking out carefully old unserviceable flange and supply and fixing/joint MS flange including welding with MS pipes, nut, bolts, washers etc of the following sizes:-
4280 mm dia
43100 mm dia
44Cutting to cast iron pipes of 100 mm bore before laying in position for insertion of new tees, branches, bend and new connection etc complete all as specified and directed.
45All as per Srl item No.38 here-in-before but 80 mm dia
46Supply & fixing cast iron fittings flange and socketed / all socketed / all flanged type such as bend upto 150mm bore (any type radious and angle) tapers any type (straight, bend, increasing, descreasing or double socket etc), Tee piece single branch, "Y" junction, double branch cross (all sockets or socket and spigot) collors, caps and plugs as in repairs, excavation earth work shall be measured and paid seperately.
47M &L for Construction ofbrickmasonry valve pit of size 750mm x 750mm x 750mm (Internal dimensions) with one brick thick wall in cement mortar 1:4 on 100 mm thick PCC1:3:6 Type C2 (using 40 mm graded broken stone aggregate as in foundation lean concrete, PCC 1:2:4 type B-1 coping and 10 mm thick cement plaster in CM(1:4) internally and externally with WPC upto 15 cm below ground level and proveding 40 x 40 x 6 mm angle iron frame all round the fixed point by means of 4 Nos hold fast 150 mm long made out of flat iron 40 x 6 mm embedded in PCC block (1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) of size 250 x 200 x 150 mm including provision of hinges welded with angle iron frame and MS cover 3 mm thick,and suitable locking arrangement including 65 mm dia pad lock and applying two coat of synthetic enamel paint over a coat of red oxide primer on steel surfaces including necessary excavation and earth work in soft/loose/complete all as specified and directed.
48M&L for rendering 10mm thick in CM (1:4)on fair faces of brick masonry including finishing the surfaces even and smooth without using extra cement complete, all as specified and directed.
49M&L for providing cement concrete 1:2:4 type B-0 (using 12.50 mm graded crushed stone aggregate) as in copings, holdfast and the like including weathering, slightly rounded or chamfered angles and throating as directed with and including necessary form work complete, all as specified and directed.
50M&L for Brick work with sub class ‘B’ bricks, straight or curved on plan exc 6 mtr mean radius, old size brickbuilt in Cement Mortar (1:4), for manholes complete all as specified and directed.
51Demolition of brick or stone boulder masonary in cement motor or cement lime motor including all quions areches piller atc but excluding ashlar faring dressed stone work and precast concrete articles complete all as specified and directed.
52Disconnecting and taking out carefully old unserviceable cable and Supplying, laying, jointing and testing cable XLPE insulated IS 7098 (Part-I)-1988 marked, screened, PVC sheathed, Unarmoured electric power cable (heavy duty) with Copperconductor for working voltage upto and including 1100 Volts, cross sectional area 6 Sqmm 2 coresize of cables laid in trenches/fixed on pole/wall / passed through pipe complete all as specified and directed.
53Disconnecting and taking out carefully old unserviceable conduit and supply, laying and jointing rigid non metallic PVC conduit of following sizes exclucive of boxes but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts saddles pipe hooks etc.
5425 mm dia
5520 mm dia
56Disconnecting and taking out carefully old unserviceable manual call point and supply and fixing manual call point for hooters/siren etc complete all as specified and directed.
57Disconnecting and taking out carefully old unserviceable locking arrangemet and supply and fixing locking arrangement along with lock at fire hose box etc complete all as specified and directed.
58Supply and fixing CO2 fire extinguisher of capacity 4.5 KG for Sub Stns and pump houses complete all as specified and directed.
59Supply and fixing and testing in replacement of unserviceable Gate valve/Globe valve and Supply, fixing, jointing and testing, of gun metal globe or gate valve with iron wheel head, both ends screwed for iron pipe, conforming to IS 778 complete, all as specified and directed for following bore of pipes :- (Make: Sant/Bir/ Leader/Upadhaya)
6025mm bore
6150mm bore
62Taking up and Down from each floor andexisting location Refilling of fire extinguisher of the following type size and capacity.Fixing existing / new location including pvc sleeve screw etc any requirement for fixing the extinguishers. After refilling the extinguishers testing report will be submited to the Engineer -in- charge. (Note --- Cost of Tansport from site to plant and back shall be included in quoted rates)
63Fire extinguisher Co2 type 4.5 Kg Capacity
64Fire extinguisher Mechnical Foam (Stored Pressure) type 9 Ltr Capacity
65Fire extinguisher ABC (Stored Pressure) powder type 6 Kg capacity
66Supplying &fixing Co2 type 4.5 kgs capacity Fire Extinguisher, assembled from brand new Explosives approved cylinders, complete with screw-down type valve, internal discharge tube, one metre high pressure rayon braided hose, discharge, horn, Bearing ISI Mark IS: 2878. Co2 Cylinder as per IS: 7285 CCE approved ‘ISI’ Valve as per IS: 3224. Co2 Gas as per IS: 15222. internal discharge tube IS: 738. Discharge duration, 10-18 secs. Filled weight of extinguisher, 17 kgs. Tested to 250 kgf/cm2. Make - Minimax / Safex / Safegaurd
67Supplying &fixing ABC type Stored Pressure 6 kgs capacity Fire Extinguisher, fabricated from MS sheets, fitted with brass forged squeeze grip valve assembly incorporated with pressure gauge, initial charge of 5 kgs. ABC Powder(MAP 50%) and pressurized with nitrogen gas. M.S. Body as per IS : 513 Forged Brass valve as per IS: 6912. Bearing ISI Mark IS: 13849. Make - Minimax / Safex / Safegaurd
68Supplying &fixing Mechnical Foam AFFF (Stored Pressure ) 9 Ltr capacity Fire Extinguisher, fabricated from MS sheets, fitted with brass forged squeeze grip valve assembly incorporated with pressure gauge and pressurized with nitrogen gas. M.S. Body Epoxy Polyester Powder Coating and AFFF as per IS 4989 ,Hydraulic test pressure 35 kg/cmm2 and Extinguisher as per IS: 15683 Make -- Minimax / Safex / Safegaurd
69S&F M.S Framed work as in base & foundation of centrifugal pump set with and including preparation of new steel surfaces of any description and applying two coat of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
70Taking out old rusty MS base frame incl dismentling the pump & moter, breaking PCC foundation complete all as per the site requirement complete all as specified and directed.
71M&L for preparation of old steel / M.S pipe surfaces nex. 10 CM width & girth and applying one coat of synthetic enamel paint complete all as specified and directed.
72M&L for preparation of old steel / M.S pipe surfaces ex. 10 CM width & girth of fire fighting station and applying one coat of synthetic enamel paint complete all as specified and directed.
73Supply, fixing, jointing and testing in replacement of electrically operated Electronic Hooterenclosed in MS enclosures of suitable size with and including preparation of new steel surfaces of any description and applying two coat of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. Make --- Agni Devices / ASE / Daksh
74Supplying and fixing testing and commissioning of Mainfire indicating panel, with 8 number of Zones complete vise-versa, necessary controls, LEDindicators, auxillary power supply, test, accept & reset, push buttons, local hooter and provision for passing on the signal to thepanel, battery back-up for 24 hours normal and 30 min. alarm condition etc. as required. This is to be fixed instilt floor. and facilities strictly as per IS 2484 complete all as specified and directed.
75Supply, fixing, testing Nozzle withshut off valve including 25 mm clipco clamp for Hose Reelof any size complete all as specified and directed. Make - Minimax / Safex / Safegaurd
76Supply, fixing, testing and commissioning of 2 x 1.5 sq.mm. solid core copper conductor PVC sheathed Armoured Cable for Hooter, MCP to Fire Alarm Panel
77Writing letters or figures on Existing FHC (Black, Romon, Italic or Indian) with paint not exc 30cm height complete all as specified and directed.