Bridge Ropeway Tunnel and Other Infrastructure Development Corporation of Uttarakhand Limited-BRIDCUL has published Tender For Electrification, Dg, Cctv, Solar System, Fire Alarm, Fire Fighting And Hvac System Works At 50 Bedded Ccu At Medical College Srinagar (Pauri Garhwal) Under Pm-Abhim. Submission Date for this Tender is 01-09-2023. CCTV System Tenders in Pauri Garhwal Uttarakhand. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 25-Aug-2023 | date extension | Date | 01-09-2023 |
Sl. No. | Item Description |
1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
2 | Group c |
3 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
4 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
5 | Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 2 Nos 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
6 | Wiring for circuit/ submain wiring alongwith earth wire with thefollowing sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit asrequired. |
7 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
8 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
9 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
10 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
11 | 4 X 16 sq. mm + 2 X 6 sq. mm earth wire |
12 | Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit |
13 | 2 Pair |
14 | 4 Pair |
15 | TV cable in existing conduiting:Supply & drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in existing surface/ recessed steel/ PVC conduit as required. |
16 | Supplying and fixing of following sizes of steel conduit alongwith accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. |
17 | 20 mm |
18 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
19 | 20 mm |
20 | 25 mm |
21 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
22 | 5/6 A switch |
23 | 15/16 A switch |
24 | 3 pin 5/6 A socket outlet |
25 | 6 pin 15/16 A socket outlet |
26 | Telephone socket outlet |
27 | TV socket outlet |
28 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. |
29 | 1 run of cable |
30 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). |
31 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
32 | Supplying and fixing of modular Blanking plate on the existing modular plate & switch box including connections but excluding modular plate etc. as reqd. |
33 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. |
34 | 1 or 2 Module (75mmX75mm) |
35 | 3 Module (100mmX75mm) |
36 | 4 Module (125mmX75mm) |
37 | 6 Module (200mmX75mm) |
38 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
39 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
40 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
41 | Supplying and fixing brass batten/ angle holder including connection etc. as required. |
42 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, LED Fixtures, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
43 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. |
44 | Supplying and fixing extra down rod of 10 cm length G.I. pipe, 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
45 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. |
46 | Upto 450 mm sweep |
47 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. |
48 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. |
49 | GROUP C |
50 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
51 | 12 way , Double door |
52 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
53 | 4 way (4 + 12), Double door |
54 | 6 way (4 + 18), Double door |
55 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
56 | Single pole |
57 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
58 | 63 A |
59 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
60 | 40 A |
61 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
62 | 40A |
63 | Supplying & Fixing of following rating four pole (three phase and neutral) 415 volts, Residual Current Circuit Breaker (RCCB), having a sensitivity current upto 300 milli-amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
64 | 25A |
65 | 40A |
66 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
67 | Supplying and fixing 30 A/32A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 A/32A "C" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
68 | Providing and fixing M.V. danger notice plate of 200x150mm ,made of mild steel at least 2mm thick ,vitreous enameled white on both sides ,and with inscription in single red colour on front side as required. |
69 | Cable Trays |
70 | Supplying, fabricating and installing following size of perforated pre painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joints with connectors, suspended from the ceiling with M.S. suspenders including bolt & nuts, painting suspenders as required. |
71 | 150 mm width X 50 mm depth X 1.6 mm thickness |
72 | Supplying, fabricating and installing following size of perforated pre painted M.S. cable trays bends with perforation not more than 17.5%, in convenient sections, joints with connectors, suspended from the ceiling with M.S. suspenders including bolt & nuts, painting suspenders as required. |
73 | 150 mm width X 50 mm depth X 1.6 mm thickness |
74 | Supplying, fabricating and installing following size of perforated pre painted M.S. cable trays tees with perforation not more than 17.5%, in convenient sections, joints with connectors, suspended from the ceiling with M.S. suspenders including bolt & nuts, painting suspenders as required. |
75 | 150 mm width X 50 mm depth X 1.6 mm thickness |
76 | Supplying, fabricating and installing following size of perforated pre painted M.S. cable trays cross members with perforation not more than 17.5%, in convenient sections, joints with connectors, suspended from the ceiling with M.S. suspenders including bolt & nuts, painting suspenders as required. |
77 | 150 mm width X 50 mm depth X 1.6 mm thickness |
78 | Providing and fixing 16 mm M.S. Fan clamps of standard shape and size in existing R.C.C. slab, including cutting chase, anchoring clamp to reinforcement bar, including cleaning, refilling, making good the chase with matching concrete, plastering and painting the exposed portion of the clamps complete. |
79 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
80 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
81 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
82 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
83 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
84 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
85 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
86 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
87 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. |
88 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) |
89 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) |
90 | Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required. |
91 | Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required. |
92 | cable laying |
93 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
94 | Upto 35 sq. mm |
95 | Above 95 sq. mm and upto 185 sq. mm |
96 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
97 | Upto 35 sq. mm |
98 | Above 95 sq. mm and upto 185 sq. mm |
99 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe/existing open trence/as required. |
100 | Upto 35 sq. mm |
101 | Above 95 sq. mm and upto 185 sq. mm |
102 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface and overhead as required. |
103 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
104 | Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) |
105 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV |
106 | 3½ X 120 sq. mm (45mm) |
107 | 3½ X 185 sq. mm (45mm) |
108 | 4 X 10 sq. mm (25mm) |
109 | Erection of metallic/octagonalpole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. |
110 | Above 8.0 metre and upto 10.0 metre |
111 | Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc. as required. |
112 | 100 mm dia |
113 | 150 mm dia |
114 | Supplying and laying of following size DWC HDPE pipe ISI markedalong with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting,jointing etc.direct in ground (75 cm below ground level) includingexcavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
115 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
116 | INTELLIGENT FIRE ALARM SYSTEM |
117 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. |
118 | Two Loop Panel. |
119 | Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required |
120 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
121 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. |
122 | Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required |
123 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
124 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. |
125 | Supplying, installation, testing & commissioning of fire fighter telephone handset complete as required. |
126 | Supplying, installation, testing & commissioning of fire fighter phone jack complete as required. |
127 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required |
128 | Supply, Installation, Testing and Commissioning of ongrid Solar Photovoltaic Power Plant conforming to MNRE specifications as amended, consisting of Mono/Poly Crystalline silicon solar cells, net metering facility, necessary protections, earthing, mounted on Aluminium/GI structure of suitable strength with following components complete as required:- a) Solar Photovoltaic Module of capacity 330 Wp or above, manufactured in India, conforming to IS 14286/IEC 61215, IS/IEC 61730-Part-1, IS/IEC 61730-Part-2. Solar Photovoltaic Module conversion efficiency shall not be less than 16.5%. PV modules used in solar power plants/ systems must be warranted for their output peak watt capacity, which should not be less than 90% at the end of 10 years and 80% at the end of 25 years. b) Power Conditioning Unit (PCU) of 350-800 V DC Input voltage range and 400 V AC, three phase, 4 wire, 50Hz +/- 2.5 Hz, output voltage suitable to generate AC Power with efficiency not less than 97%, total harmonic distortion less than 3% and suitable for ambient temperature from 0 to 50 degree C. The PCU shall adjust the voltage and frequency level to suit the Grid Voltage Frequency. c) Data Monitoring System complete with accessories. d) Fixing of Array junction box & Main junction box with IP 65 protection and termination arrangement for incoming and outgoing cable along with glands, lugs and other accessories etc. as required. e) Lightning and surge voltage protection. f) Connections & Interconnections by supplying & fixing required size XLPE insulated copper conductor 1.1 kV grade armoured power and control cables between solar modules, main power cable to grid supply PCU unit along with supplying & fixing of necessary channel/conduit lugs and other accessories etc. as required. |
129 | VRF SYSTEM |
130 | OUTDOOR UNIT |
131 | Supply Installation, Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating, having all hermetically sealed inverter type Scroll Compressor(s), minimum two compressors for above 14 HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R 410 A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5. |
132 | INDOOR UNIT - CASSETTE |
133 | Supply, installation, testing and commissioning of following minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, cord less remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. |
134 | 1.6 TR |
135 | INDOOR UNIT - HIGH WALL TYPE |
136 | Supply, installation, testing and commissioning of following minimum capacity VRV/VRF High wall type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, cord less remote control, drain pan, necessary accessories etc., suitable for operation on 230 V ± 10%, 50 Hz, single phase AC supply, complete as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. |
137 | 1.65 TR |
138 | 2.0 TR |
139 | INDOOR UNIT - DUCTABLE TYPE |
140 | Supply, installation, testing and commissioning of following minimum capacity and external static pressure VRF/VRV ceiling mounted ductable type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration isolators, drain pan, other necessary supports etc., suitable for operation on single phase AC supply 230 V ± 10%, 50 Hz complete as required. The unit shall have automatic force shut down provision in case of fire on receiveing signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. |
141 | Low static ductable units (minimum 25 pascal external static pressure) |
142 | 1.6 TR |
143 | High Static Ductable units (minimum 110 pascal external static pressure) |
144 | 8.0 TR |
145 | COPPER REFRIGERANT PIPING |
146 | Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : |
147 | 9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation |
148 | 12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation |
149 | 15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation |
150 | 19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation |
151 | 22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation |
152 | 25.4 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation |
153 | 28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation |
154 | DRAIN PIPING |
155 | Providing and fixing Chlorinate Polyvinyl Chloride (CPVC) pipes having thermal stability for hot & cold water supply including all (CPVC) plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This including jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of engineer in charge |
156 | 25 mm outer dia pipes. |
157 | DUCTING, GRILLS, DIFFUSER AND INSULATION |
158 | Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes,hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. |
159 | Thickness 0.8 mm sheet |
160 | Thickness 1.0 mm sheet |
161 | Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. |
162 | Thickness 0.8 mm sheet |
163 | Supply, installation, testing and commissioning of Motorized (ON-OFF Type) duct mounted GI volume control damper with enthalpy sensor and necessary control wire (minimum 1.5 sq. mm) for integration within AHU room. |
164 | Damper |
165 | Actuator |
166 | Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications. |
167 | Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required. |
168 | Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core. |
169 | Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core. |
170 | Supply, installation, testing & commissioning of thermal insulated flexible duct of following sizes duly supported at regular interval as per site requirement etc. complete as required as per specifications. |
171 | 200mm Dia |
172 | Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications |
173 | Fire Damper |
174 | Actuator |
175 | Supply and fixing of acoustic lining of supply air duct and plenum with 25 mm thick resin bonded glass wool having density of 32 kg/m³, with 25 mm X 25 mm GI section of 1.25 mm thick, at 600 mm centre to centre covered with Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminum sheet fixed to inside surface of ducts with cadmium plated nuts, bolts, stick pins, CPRX compound etc. complete as required and as per specifications. |
176 | Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class “O”) insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required. |
177 | 19 mm |
178 | 25 mm |
179 | SUB-HEAD I : FIRE FIGHTING SYSTEM |
180 | PUMPS |
181 | Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required : |
182 | Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. |
183 | Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-"F" insulation, conforming to IS-325. |
184 | M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. |
185 | Suitable cement concrete foundation duly plastered and with anti vibration pads. |
186 | 1620 lpm at 56 m Head |
187 | Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. |
188 | 1620 lpm at 56 m Head |
189 | Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520. Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-"F" insulation, conforming to IS : 325. M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. |
190 | 180 lpm at 56 m Head |
191 | CONTROL PANELS |
192 | Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required : |
193 | INCOMING 250A, 50kA 4 Pole MCCB, Ics=100% Icu rating Digital Voltmeter 0-500V with selector switch Digital Ammeter (0-250 A) with selector swtich & CTs etc.LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 300A OUTGOING ( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) Main Fire Pump 125 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 60 HP pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. Jockey Pump 63 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. DIESEL ENGINE CONTROL Control for diesel engine comprising -Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication, Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter. All standard relays and accessories for automatic operation of diesel engine System Controller. Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification |
194 | PIPES & ACCESSORIES |
195 | Providing, laying, testing & commissioning of "C" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
196 | 25 mm dia |
197 | 32 mm dia |
198 | 40mm dia |
199 | 50 mm dia |
200 | 65 mm dia |
201 | 80 mm dia |
202 | 100 mm dia |
203 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required : |
204 | Single headed Gunmetal |
205 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : |
206 | 100 mm dia |
207 | Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required : |
208 | 40 mm dia |
209 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete required. |
210 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : |
211 | Gun Metal |
212 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required; -20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 -20 mm nominal internal dia gun metal globe valve & nozzle. -Drum and brackets for fixing the equipmets on wall. -Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. |
213 | 30 mtrs |
214 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : |
215 | Gun Metal |
216 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required. |
217 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. |
218 | Pendent Sprinkler |
219 | Upright Sprinkler |
220 | Horizontal side wall sprinkler |
221 | Concealed sprinkler |
222 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. |
223 | Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. |
224 | 100 mm dia |
225 | 150 mm dia |
226 | Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required : |
227 | 100 mm dia |
228 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. |
229 | 700 mm |
230 | 1000 mm |
231 | 1200 mm |
232 | Providing and placing on terrace (at all floor levels) Polyethylene water storage tank ISI : 12701 marked with cover and suitable locking arrangement amd making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank |
233 | SUB HEAD B - NON SCHEDULE ITEMS |
234 | LIGHTING FIXTURES |
235 | Supply of 20 Watt LED Linear Metal Construction commercial batten fitting with fuse protection suitable for Polycarbonate diffuser & aluminium heat sink complete suitable for both surface & suspended Mounting, complete in all respect 2200 system lumens PF>0.95, THD<10%, CRI>80, Sheet Thickness 0.8mm, Average Life 40000hrs @L70 with fixing clamps, nut, bolts and fixing arrangement with both side ofexisting MS pipe (in case of hanging )complete accessories all respectand as directed by engineer in charge., Make PRIMA WARM WHITE ALUMINIUM CIRCLE |
236 | Supply of2" * 2" panel light30 watt/3600 lumenssuitable for Polycarbonate diffuser & aluminium heat sink complete suitable for recessed Mounting, complete in all respect 3600 system lumens PF>0.95, THD<10%, CRI>80, Sheet Thickness 0.8mm, Average Life 40000hrs @L70 with fixing clamps, nut, bolts and fixing arrangement with both side ofexisting MS pipe (in case of hanging )complete accessories all respectand as directed by engineer in charge., Make SYSKA COOL DAY LIGHT ALUMINUM SQUARE LED IS:10322 |
237 | Supply of Downlighter 15 wattsuitable for Polycarbonate diffuser & aluminium heat sink complete suitable SURFACE Mounting, complete in all respect 2000 system lumens PF>0.95, THD<10%, CRI>80, Sheet Thickness 0.8mm, Average Life 40000hrs @L70 with fixing clamps, nut, bolts and fixing arrangement with both side ofexisting MS pipe (in case of hanging )complete accessories all respectand as directed by engineer in charge., Make Led Surface Ceiling Light-IS:10322 KE Warm White Aluminium Circular LED surface ceiling Light KER |
238 | Supply of TubeLight 24 watt/2400 lumenssuitable for Polycarbonate diffuser & aluminium heat sink complete suitable for Surface Mounting, complete in all respect 2400 system lumens PF>0.95, THD<10%, CRI>80, Sheet Thickness 0.8mm, Average Life 40000hrs @L70 with fixing clamps, nut, bolts and fixing arrangement with both side ofexisting MS pipe (in case of hanging )complete accessories all respectand as directed by engineer in charge., Make SYSKA LED BATTEN24W |
239 | Supply of TubeLight 10 watt/1150 lumenssuitable for Polycarbonate diffuser & aluminium heat sink complete suitable for Surface Mounting, complete in all respect 1150 system lumens PF>0.95, THD<10%, CRI>80, Sheet Thickness 0.8mm, Average Life 40000hrs @L70 with fixing clamps, nut, bolts and fixing arrangement with both side ofexisting MS pipe (in case of hanging )complete accessories all respectand as directed by engineer in charge., Make GYYNC LED BATTEN10W |
240 | Supply of 10W LED BULKHEAD (MEKE LEDGEAR PLASTIC LED BULKHEAD) |
241 | Supply ofPROPELLAR TYPE AC VENTILATION EXHAUST FAN AS PER 2312 |
242 | Supply, installation, testing and commissioning of following ennealed tinned electric grade copper conductor PVC insulated and PVC sheathed jelly filled armoured telecommunication cable as per specifications.make finolex |
243 | 10 pair armoured riser cable of 0.60 mm dia copper conductor |
244 | 20 pair armoured riser cable of 0.60 mm dia copper conductor |
245 | Supply and installation, testing and commissioning following size FABIO Mild steel Telephone Junction Box make telephone tag block in lockable 16 gauge sheet medium duity PVC enclosure complete as required. |
246 | 10 pair Krone type tag block |
247 | 16 pair FABIO type tag block |
248 | Supply and Erecting modular type computer jack RJ 45 with screwless connector approved make with mounting plate and box with wiring connections complete. D-LINK RJ45 |
249 | Supply of following sizes of XLPE insulatedAluminum Armoured cable, overall PVC sheathed 1.1 KV grade cables conforming to relevant IS code and technical specifications. |
250 | 4CX16 SQMM AL ARMOURD CABLE |
251 | 3.5CX50 SQMM AL ARMOURD CABLE |
252 | 3.5CX95 SQMM AL ARMOURD CABLE |
253 | 3.5CX150 SQMM AL ARMOURD CABLE |
254 | Supply of following sizes of XLPE insulatedCopper Armoured cable, overall PVC sheathed 1.1 KV grade cables conforming to relevant IS code and technical specifications. |
255 | 2CX 2.5 SQMM Cu ARMOURD CABLE |
256 | Supply of LED streetlightfitting not more than 45WSESSP LED STREET LIGHT having System Efficacy >120 lm/W, system output >3600Lumens,THD<10%,PowerFactor>0.95,CRI>70,CCT 5700,Full IP66 ( with out Glue) protectedsinglepiecediecastaluminium housing having toughned glass/PC with Impact resistance IK07. LED driver should be Fully metal body Potted & Encapsulated . BIS compliant driver should sustain440V Stress Voltage protection for 8 Hrs., High Cut off : 325V(+/- 15V) and should have feature of Auto Restart. Driver shall have 4KV Surge protection and feasibility of 10KV external SPD housed in Luminiare and confirming standard IEC60598. Including suitable size GI pipe bracket clamps, nut, bolts and washers complete all as directed. Make : SESSPLED STREET LIGHT FORM GEM APP. |
257 | Supply of 9.0 Mtr Height Galvanized Iron OctagonalPoles having uniformly tapered polygonal shape throughout the length with straightLongitudinal welding in a single shaft. There shall not be any circumferential welding. Dimensions:Top Dia.: 70mm, Bottom Dia.: 135mm, Thickness 3mm &Base plate 275*275*16 mm. Dimension of Foundation Bolts - Length 600mm, Dia. 24mm &04 Nos. Bolts manufactured from special steel along with nuts, washer, anchor plates & Templates. SingleArm of 0.5 Mtr. Shall be provided along with – MAKE GEM ITEM SALESMART STREET LIGHT POLE |
258 | LT PANELS |
259 | MAIN LT PANEL- -Supplying, fixing, testing & commissioning of 415V ,3Phase 50Hz, 4wire system,sheet steel clad,dust & vermin proof cubical & outdoor type floor mounted, free standing Main Distribution Board with IP - 42 protection, compartmentalized design and fabricated out of 2mm/1.6mm CRCA sheet steel complete with aluminium Bus Bars, Providing & Fixing of base plate /channel, P/F the following Switchgears,complete with earth Bus Bar throughout the length of the panel,terminal arrangement for incomings/outgoings cables and also outgoing terminations for various sizes of cables,the incoming and outgoing feeders shall be accommodated in a modular multi-tier arrangement,adequate size bus duct/cable alley, Sign writing,Painting,Earthing,Numbering,Danger plate etc. Complete as requried,numbering, danger plate etc. complete as required as per specification and drawing. All MCCBs Shall be Ics=100%Icu. Make: Legrand(Adlec) or eqivalent as per approved make list and as direction by engneer in charge. PTTA Panel |
260 | INCOMER: |
261 | 1 nos. 630A415V, Ics=50KA, 4P MCCB with TM release having adjustable O/L, S/C protection. |
262 | 1 nos.Digital type multi function meters (V+A+Hz) with cast resin CTs 200/5A. |
263 | 1 Set of phase indicating lamp with MCB |
264 | BUSBAR |
265 | 800A TPN Bus bar of aluminimum alloy. |
266 | OUTGOINGS |
267 | - 250 A, TPN,36KA, MCCB – 1 N.o. |
268 | - 200 A, TPN,36KA, MCCB – 1 N.o. |
269 | - 160 A, TPN,36KA, MCCB – 1 N.o. |
270 | - 125 A, TPN,36KA, MCCB – 4 N.o. |
271 | - 63 A, TPN,10KA, MCCB – 9 N.o. |
272 | - 40 A, TPN,10KA, MCB – 4 N.o. |
273 | - 63 A, DP,10KA, MCB – 3 N.o. |
274 | CAPACITOR SECTION |
275 | SECTION –1 |
276 | INCOMER |
277 | 250 A, 3 Pole, MCCB with U/V release and shunt release with a minimum of 5 NO and 5NC auxiliary contacts and with following :- |
278 | METERING & CONTROLS |
279 | - breaker ON/OFF/TRIPindicating lamps with control fuses. |
280 | - shunt trip coil |
281 | Automatic Power Factor |
282 | correction system with following : |
283 | 1 number solid state Binary mode |
284 | automatic power factor sensing and |
285 | correction relay complete in all |
286 | respects ( 6 stages) |
287 | The APFCR relay will be from the DUAL SOURCE MULTIFUNCTION METER FROM TRINITY- MODEL- "POWER CUBE".The relay will have different set points for the mains supply & generator supply. |
288 | LT Power Capacitor Banks along with contactors and HRC fuses as detailed below: |
289 | 2 number TP Contactors of 63 A Capacity with MCB – 25 kVAR |
290 | 1 number TP Contactors of 63 A Capacity with MCB – 20 kVAR |
291 | 4 number TP Contactors of 40 A Capacity with MCCB – 10 kVAR |
292 | 3 number TP Contactors of 32 A Capacity with MCCB – 5 kVAR |
293 | GROUND FLOOR PANEL |
294 | INCOMER FROM MAIN LT PANEL |
295 | 125A TPN ,50KA, MCCB |
296 | METERING & INDICATION |
297 | 1 sets of phase indicating lamps |
298 | 1 sets of Voltmeter (0-500V) with VSS each with 3 nos. 2A SP MCBs each |
299 | 1 Sets of Breaker ON-OFF-TRIP, |
300 | BUS BAR as per SLD:- |
301 | 1 Sets of 150A, TPN Aluminum bus bars with colour coded sleeves. |
302 | OUTGOINGS |
303 | - 63 A, TPN,10KA, MCB – 2 N.o. |
304 | - 40 A, TPN,10KA, MCB – 3 N.o. |
305 | - 32 A, TPN,10KA, MCB – 4 N.o. |
306 | FIRST FLOOR PANEL |
307 | INCOMER FROM MAIN LT PANEL |
308 | 125A TPN ,50KA, MCCB |
309 | METERING & INDICATION |
310 | 1 sets of phase indicating lamps |
311 | 1 sets of Voltmeter (0-500V) with VSS each with 3 nos. 2A SP MCBs each |
312 | 1 Sets of Breaker ON-OFF-TRIP, |
313 | BUS BAR as per SLD:- |
314 | 1 Sets of 150A, TPN Aluminum bus bars with colour coded sleeves. |
315 | OUTGOINGS |
316 | - 63 A, TPN,10KA, MCB – 3 N.o. |
317 | - 40 A, TPN,10KA, MCB – 3 N.o. |
318 | - 32 A, TPN,10KA, MCB – 3 N.o. |
319 | SECOND FLOOR PANEL |
320 | INCOMER FROM MAIN LT PANEL |
321 | 125A TPN ,50KA, MCCB |
322 | METERING & INDICATION |
323 | 1 sets of phase indicating lamps |
324 | 1 sets of Voltmeter (0-500V) with VSS each with 3 nos. 2A SP MCBs each |
325 | 1 Sets of Breaker ON-OFF-TRIP, |
326 | BUS BAR as per SLD:- |
327 | 1 Sets of 150A, TPN Aluminum bus bars with colour coded sleeves. |
328 | OUTGOINGS |
329 | - 63 A, TPN,10KA, MCB – 2 N.o. |
330 | - 40 A, TPN,10KA, MCB – 5 N.o. |
331 | - 32 A, TPN,10KA, MCB – 3 N.o. |
332 | THIRD FLOOR PANEL |
333 | INCOMER FROM MAIN LT PANEL |
334 | 125A TPN ,50KA, MCCB |
335 | METERING & INDICATION |
336 | 1 sets of phase indicating lamps |
337 | 1 sets of Voltmeter (0-500V) with VSS each with 3 nos. 2A SP MCBs each |
338 | 1 Sets of Breaker ON-OFF-TRIP, |
339 | BUS BAR as per SLD:- |
340 | 1 Sets of 150A, TPN Aluminum bus bars with colour coded sleeves. |
341 | OUTGOINGS |
342 | - 63 A, TPN,10KA, MCB – 5 N.o. |
343 | - 40 A, TPN,10KA, MCB – 2 N.o. |
344 | - 32 A,DP,10KA, MCB – 2 N.o. |
345 | MAIN UPS PANEL |
346 | INCOMER FROM MAIN LT PANEL |
347 | 2*63A TPN ,50KA, MCCB |
348 | METERING & INDICATION |
349 | 1 sets of phase indicating lamps |
350 | 1 sets of Voltmeter (0-500V) with VSS each with 3 nos. 2A SP MCBs each |
351 | 1 Sets of Breaker ON-OFF-TRIP, |
352 | BUS BAR as per SLD:- |
353 | 1 Sets of 150A, TPN Aluminum bus bars with colour coded sleeves. |
354 | OUTGOINGS |
355 | - 63 A, TPN,10KA, MCB – 4 N.o. |
356 | - 40 A, TPN,10KA, MCB – 10 N.o. |
357 | - 40 A,DP,10KA, MCB – 4 N.o. |
358 | EXTERNAL LIGHTING PILLAR- OUTDOOR TYPE -Supplying, fixing, testing & commissioning of 415V ,3Phase 50Hz, 4wire system,sheet steel clad,dust & vermin proof cubical & outdoor type floor mounted, free standing Main Distribution Board with IP - 42 protection, compartmentalized design and fabricated out of 2mm/1.6mm CRCA sheet steel complete with aluminium Bus Bars, Providing & Fixing of base plate /channel, P/F the following Switchgears,complete with earth Bus Bar throughout the length of the panel,terminal arrangement for incomings/outgoings cables and also outgoing terminations for various sizes of cables,the incoming and outgoing feeders shall be accommodated in a modular multi-tier arrangement,adequate size bus duct/cable alley, Sign writing,Painting,Earthing,Numbering,Danger plate etc. Complete as requried,numbering, danger plate etc. complete as required as per specification and drawing. All MCCBs Shall be Ics=100%Icu. Make: Legrand(Adlec) or eqivalent as per approved make list and as direction by engneer in charge. PTTA Panel |
359 | INCOMER FROM MAIN LT PANEL |
360 | 1*63A TPN ,10KA,MCCB |
361 | METERING & INDICATION |
362 | 1 sets of phase indicating lamps |
363 | 1 sets of Voltmeter (0-500V) with VSS each with 3 nos. 2A SP MCBs each |
364 | 1 Sets of Breaker ON-OFF-TRIP, |
365 | BUS BAR as per SLD:- |
366 | 1 Sets of 100A, TPN Aluminum bus bars with colour coded sleeves. |
367 | OUTGOINGS as per SLD |
368 | 40 A,TP,10KA, Contactor -1 outgoings |
369 | Timer |
370 | 10/16/25 A,SP,10KA, MCB,- 18outgoings |
371 | NOTE: |
372 | Any Item necessary for the completion of the systembut not mentioned in the BOQ shall be included by the supplier |
373 | HT SUB STATION WORKS |
374 | SITC of 11 KV, 630 Amp Outdoor type HT RMU. The RMU Should consist on one no of Load break switch (LBS) as incomer and one VCB as outgoing. The RMU should be type tested according to IEC 62271-100, 200 & 102, IACAFL, 21 kA for 1 sec, IP class 54, IP 67 for Tank. The rated voltage should be 12 kV, impulse withstand voltage of 75 kVp, Power frequency withstand voltage of 28 kV, rated short time current of 21 kA for 3 sec. The RMU should have SF6 gas insulation, robotic welding of gas tank. The RMU should be suitable for outdoor application. Themanufacturer should have service centre in the state of uttarakhand. |
375 | Supply,Installation, testing & Commissioning of double pole structure suitable for 11 KV HT system as per CEA & UPCL norms & comprising of the following ,but not limited to it for completion of works . RSJ pole of 9 mtrs length of size 175 X 90 mm complete with suitable MS base plate welded at bottom base plate - 2 nos.MS channel of size 100 X 50 mm , length 4 mtrs (approx.)11 KV AB switch - 1 set , 11 KV Horn gap fuse unit - 1 set , 11 KV Lightning Arrestor , 11 KV Disc Insulator , 11 KV pin insulator 6 swg copper wire for jumperingSupply and erection of stay set complete with necessary foundation , excavation, and refilling of earth etc. as required. Concrete foundation for RJS poles burried upto a depth of 1830mm in ground in a pit of size 450 X 450 mm in CC 1:3:6 along with 200 mm copping above ground inclusive of earth work.Necessary Nut , Bolts, Clamps, operating handle for AB switch , clampingwelding etc. complete as required. Painting the RSJ poles complete with two coat of red oxide and two coats of GI enamel paints complete as required. |
376 | Supply, installation, testing and commissioning ofoutdoor TYPE, OIL type transformer with copper winding having a continuous rating of 200 kVA, 11kV/415 +/- 1% V, 3 phase, 50 Hz, DY-11 vector group,The transformer shall have cable end box for indoor termination of HT cable on HT side and Cable Box for indoor terminationon LT side, complete in all respects including standard accessories. It is To be installed on Top of two pole structure with proper iron angle channel support as required.Compliance to BEE Standards AND BIS Standards (IS 1180). SERVOKON DISTRIBUTION TRANSFORMER |
377 | Supply OF UNDERGROUNDHT CABLES |
378 | Supply of HT (UE)AL XLPE Cable of size 3 C X 120 sq mm havells make |
379 | Bullet cameras-PRIZOR 5MP |
380 | Supply, installation, testing and commissioning of IP based, 4 MP, FULL HD WDR IR bullet CAMERA - 40 MTRS, colour indoor verifical dome camera, 3.6 MM FIXED LENS, 1/3 ", 4 Mega Pixel PS CMOS Image Sensor, WDR (120 dB), Day/ Night (ICR), IR Range of 40 Mtrs, IP67 and all ancillary equipments and all accessories. |
381 | CP PLUS MAKE - |
382 | Network Video Recorder |
383 | Supply, Installation, Testing and Commisioning of 32 CHANNEL NETWORK VIDEO RECORDER, H.264/MJPEG dual codec decoding,Max 256 Mbps incoming bandwidth, HDMI/ VGA simulation video output, support 8 SATA HDD"s upto 32 TB, 1 ESATA up to 16 TB, supports multi brand network cameras.Each NVR shall have a storage capacity so as to recorda backup for 15 days at 4 CIF @ 25FPS.NVR should have system expandibility feature of at least 20% of current requirement, redundant fan and power supplies, outputs TCPIP network feature & server software monitor outputs. The NVR should be networkable via IP protocol & should be able to connect to a web based system for remote viewingvia web system. Vendor should submit the storage / HDD Calculation. |
384 | CP PLUS MAKE -CCTV BUNDLE TOOLKIT |
385 | Supply, Installation, Testing and commisioning of32" inches LCD monitor PRIZOR BASIC |
386 | Design, supply, Installation, testing & commissioning of the following: 20 KVA/16KW UPS System, 415V, 50Hz. Input and 3Ph.+ N, 50Hz. Output, High performance industrial grade UPS, Advance IGBT rectifier and IGBT PWM Inverter fully digital signal processor (DSP) base with following key features – NUMAX ONLINE UPS |
387 | Ø Input Performance of UPS |
388 | · “ ZERO Impact on Source (SEB/DG)” |
389 | · IGBT PWM Rectifier |
390 | · Current harmonics - < 3% (iTHD) |
391 | · Input PF – 0.99 |
392 | · Sequential Start up of UPS Systems (smooth change over to DG set) |
393 | · Wide voltage & frequency Tolerance (320V -480V & 45hz. To 55Hz.) |
394 | · Normal UPS operation during Input Phase sequence change |
395 | Ø Output Performance of UPS |
396 | · IGBT PWM Inverter, Short circuit proof. |
397 | · More output active power (rated @ 0.9 PF,20KVA = 16KW) |
398 | · Delta-Star Isolation Transformer |
399 | · Thermal over rated inverter design, more over load capacities, suitable for industrial loads. (110%, 125% & 150% - 60/10/1 Minute) |
400 | · Output Voltage 415V +/- 1% (Regulation) |
401 | · Out put Voltage wave form distortion at 100% non-linear loads (distorting Industrial loads)-< 3%(,1% at Linear Loads) |
402 | · Inbuilt Static bypass and manual maintenance bypass. |
403 | · On-line battery health monitoring (batteries always ready to work) |
404 | · Emergency Power Off (EPO), Energy back feed protection. |
405 | · Communication Options – UPS/ Power status can be monitored through user friendly software. |
406 | · Interface through – 2 Nos. RS232 Ports, SNMP, Potential Free contacts. |
407 | Sealed Maintenance Free (SMF) for minimum 15 Minute back up with each 20KVA UPS at full load complete with powder quoted battery racks, interconnecting links. |
408 | DG set |
409 | Supply,Installation, testing & Commissioning of 200 KVA Silent DG set comprising of SuitableEngine coupled to 415V200 KVA Stamford make alternator both mounted on common Base frame with AMF PANEL and other standard accessories i.e. Fuel tank, Batteries with leads complete in all respects and as per details mentioned below: RISHABH POWER GENERATOR DG SET |
410 | DETAILED SPECIFICATIONS |
411 | DIESEL ENGINE: |
412 | 12 cylinder, 4 stroke cycle, Water cooled developing REQUIRED BHP at 1500 RPM under NTP conditions of BS:5514. The engine shall be provided with electrical starting arrangement & shall give the electrical output of 200 KVA/ 160 KW at 0.8 power factor, 415 V at the alternator terminal. |
413 | Other accessories of the engine would be as under: |
414 | COOLING SYSTEM |
415 | ù Radiator/ HE Cooled |
416 | ù Engine mounted Water pump |
417 | ù Thermostats |
418 | ù Corrosion Inhibitor |
419 | ù Self contained piping |
420 | ù Outboard after coolers |
421 | FUEL SYSTEM |
422 | ù PT fuel pump |
423 | ù Injectors |
424 | ù Fuel filters – Paper element type |
425 | ù Self contained piping |
426 | LUBRICATING SYSTEM |
427 | ù Oil pump |
428 | ù Strainer |
429 | ù Lub oil cooler-Plate type |
430 | ù Oil filter – Paper element type |
431 | ù Bypass filter |
432 | ù Self contained piping |
433 | AIR INTAKE SYSTEM |
434 | ù Dry type Paper Element filters |
435 | ù Air intake manifold with necessary connections |
436 | ù Turbo charged after cooled |
437 | ù Restriction Indicator |
438 | EXHAUST SYSTEM |
439 | ù Exhaust manifold |
440 | ù Stainless steel flexible connections suitably optimized to reduce noise. |
441 | ù Silencers – Hospital Grade |
442 | GOVERNING SYSTEM |
443 | ù Electronic Digital Governor |
444 | STARTING SYSTEM |
445 | ù Starter, 24V,DC |
446 | ù Battery charging Alternator |
447 | ù With in-built Regulator |
448 | SAFETY SYSTEM(Engine Protection – Trip) |
449 | ù Low lub oil pressure |
450 | ù High water temperature |
451 | ù Over speed |
452 | ù Low Coolant oil level (alarm) |
453 | OTHER SYSTEM |
454 | ù Flywheel |
455 | ù Flywheel housing |
456 | POWER COMMAND GENSET CONTROLS |
457 | The controller should be a microprocessor based with following features. |
458 | · Digital AVR – Digital voltage regulation. |
459 | · Digital Electronic Governing and Smart Starting. |
460 | · Genset Monitoring – Monitors status of all critical engine & alternator functions |
461 | · Engine Metering |
462 | · AC Alternator Metering. |
463 | · AC Bus/ Utility Metering. |
464 | · Engine Protection. |
465 | · AC Alternator Protection. |
466 | · AC Utility Protection. |
467 | · Fault Codes & Description on HMI. |
468 | · Data Logging |
469 | · Configurable inputs and outputs. |
470 | · Modbus Interface (RS485RTU). |
471 | · AmpSentryprotection – for true alternator overcurrent protection. . |
472 | · Digital frequency synchronization & voltage matching. |
473 | · Isochronous load share. |
474 | · Digital Power Transfer Control. |
475 | ALTERNATOR: |
476 | Output- 200 KVA |
477 | Power factor -0.8 |
478 | Rated Generating Voltage -415 Volts |
479 | Voltage regulation +/- 0.5 % all load between no load to full load |
480 | factor0.8 to unity |
481 | Frequency 50 Hz |
482 | Speed 1500 RPM |
483 | Class of insulation - H type |
484 | Winding connection -Star connection (all six leads will be brought out of stator frame) |
485 | Overload capacity - 10% for one hour in any 12 hours of operationwithout exceeding temperature rise limits |
486 | Bearings -Single bearing |
487 | Enclosures - Drip proof & screen protected IP-23 |
488 | The alternator shall be of self-excited, self regulated, self ventilated in brushless design, provided with suitable automatic voltage regulator and shall conform to BS:2613 or BS : 5000 and shall give rated output at NTP conditions. |
489 | ESSENTIAL ACCESSORIES: |
490 | BASE FRAME: |
491 | One no. MS Fabricated adequately machine Channel Common Base Frame with lifting facility, pre-drilled foundation holes suitable for permanent installation on concrete foundation for direct grouting or on anti-vibration mountings which will be suitable to receive the offered engine and alternator duly coupled through a flexible coupling. |
492 | FUEL TANK: |
493 | One no. Daily fuel tank of Standard capacity for each DG set made out of 2 mm thick MS sheet |
494 | BATTERIES: |
495 | For electrical control circuit of 24 volt DC, 2 Nos. batteries of 12 volts 160 Ah each with battery leads for electrical starting of each DG Set. |
496 | SOUND ATTENUATED SYSTEM |
497 | THICKNESS OF SHEET - 16-G |
498 | High class sheet metal fabricated enclosure for reducing the noise level of DG set & also acts as a weather proof housing. Genset will be a integral part of acoustic enclosure and whole construction will be on multi-fold sheet channels & ISMC sections. Enclosure construction is fully bolted keeping in view the major service requirements all doors are provided with specially designed hinges and lockable handles, Battery, Fuel tank is housed inside the enclosure. |
499 | ACOUSTIC MATERIALS |
500 | Rock wool in the form of slabs of 100 mm thickness and 64 KG/Metric cube density (Specification of Rock wool conforms to IS 8183). |
501 | Further to increase the life of Acoustic material resin coated fibre glass cloth is provided on exposed surface of Rock wool slabs and the panels are supported by perforated sheets. |
502 | VENTILATION |
503 | Acoustic enclosure is designed in such a way that there are no hot pockets around engine and it is provided with suitable designed engine radiator which does not allow the temperature to rise more than 70C above ambient temperature. |
504 | To achieve optimal output and minimum sound level from the DG set, suitable openings with acoustic hoods are provide for increasing the inflow of air required for combustion & forced ventilation. Air intake system as per the recommendations and engine requirement are provided. |
505 | ù Acoustic hoods with noise splitters provided to block and reduce the sound leakage. |
506 | ù The sound control system designed to suppress the sound level to 75 db maximum at 1 metres distance in open free field environment as per ISO 8528 part 10. |
507 | SILENCER |
508 | Specially designed Critical Grade silencer is provided. Silencer & engine exhaust outlet, Connected with flexible SS below. |
509 | VIBRATION ISOLATION |
510 | To avoid transfer of vibration from genset to enclosure & surrounding specially designed vibration isolators to be used. |
511 | Providing and fixingFire Extinguishers completewith all accessories aspermanufacturer"s specifications. |
512 | a) Water CO2 nozzle type.(IS:15683), 2018 version-2 |
513 | b) Mechanical Foam (AFFF) complete as required capacity - 9 ltr , 15683- 2006 & ISO - 9001 |