Public Works Department-PWD has published Tender For Extension Of Fire Detection System And Fire Fighting Sprinkler System At Newly False Ceiling Area At Dr Bsa Hospital Rohini Delhi. Submission Date for this Tender is 10-08-2023. Flame Detectors Tenders in rohini Delhi. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories : |
2 | Pendent Sprinkler / Upright Sprinkler |
3 | Providing, laying, testing & commissioning of "C" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required. |
4 | 25 mm |
5 | 32 mm |
6 | 40 mm |
7 | 50 mm |
8 | 65 mm |
9 | 80 mm |
10 | 100 mm |
11 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating withbronze/ gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : |
12 | 50 mm |
13 | 65 mm |
14 | 80 mm |
15 | 100 mm |
16 | Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets,center bracket, stockbar of following sizes complete as required. |
17 | 1000 mm |
18 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required : |
19 | Single headed Stainless steel |
20 | Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required : |
21 | Single headed Stainless steel |
22 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : |
23 | Stainless Steel |
24 | Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required. |
25 | Supplying, installation, testing & commissioning response indicator on surface/recess MS box having two LEDs metallic cover complete with all connections etc. as required. |
26 | Supplying, installation, testing & commissioning of manual call box of ABS type in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required. |
27 | Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in A.B.S. box with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required. |
28 | Supplying, installation, testing & commissioning talk back slave station in surface/recess suitable for operation on simplex mode complete with P.T.T. knob & speaker/microphone enclosed in a M.S.(16 SWG)/ ABS box with break glass in front etc. complete as required. |
29 | Providing and fixing in position the industrial type pressure gauge complete as required. |
30 | Supplying, installation, testing & commissioning sector panel suitable for following zones, complete with visual indications for short circuit fault, open circuit fault, fire condition and all other standard facilities as per IS:2189 with mimic diagram for all area/zone covered, complete with all connections, interconnections as required. |
31 | 6 Zone |
32 | 10 Zone |
33 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. |
34 | Supplying and fixing of water mist type fire extinguisher ISI marked confirming to IScapacity 9 Ltr complete with delivery hose horn, squeeze grip releasevalve, locking arrangement, bracket with two screw and sleevei/c providing j hook for fixing etc as required. |