Tender For Special Repair By Providing Renovation Of Various Blocks In The Campus Of Shri Atal Bihari Vajpayee Government Medical College, Village Chhainsa Tehsil Ballabgarh Faridabad (Providing Lan And Fire Alarm System), Faridabad-Haryana

Public Works Department-PWD has published Tender For Special Repair By Providing Renovation Of Various Blocks In The Campus Of Shri Atal Bihari Vajpayee Government Medical College, Village Chhainsa Tehsil Ballabgarh Faridabad (Providing Lan And Fire Alarm System). Submission Date for this Tender is 29-08-2023. Alarm Systems Tenders in Faridabad Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

38878204
Corrigendum : Tender For Special Repair By Providing Renovation Of Various Blocks In The Campus Of Shri Atal Bihari Vajpayee Government Medical College, Village Chhainsa Tehsil Ballabgarh Faridabad (Providing Lan And Fire Alarm System)
Open Tender
Indian
Haryana
Faridabad
29-08-2023

Tender Details

Special Repair By Providing Renovation Of Various Blocks In The Campus Of Shri Atal Bihari Vajpayee Government Medical College, Village Chhainsa Tehsil Ballabgarh Faridabad ( Providing Lan And Fire Alarm System )

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 22-Aug-2023 Draft Corrigendum Other 29-08-2023

Key Value

Document Fees
INR 5000 /-
EMD
INR 193300.0 /-
Tender Value
INR 96.63 Lakhs /-

BOQ Items

Name of Work :SPECIAL REPAIR BY PROVIDING RENOVATION OF VARIOUS BLOCKS IN THE CAMPUS OF SHRI ATAL BIHARI VAJPAYEE GOVERNMENT MEDICAL COLLEGE, VILLAGE CHHAINSA TEHSIL BALLABGARH FARIDABAD (PROVIDING LAN AND FIRE ALARM SYSTEM)
Sl. No. Item Description
1Supply, Installation, Testing & Commissioning of Switch, Should be a L3 switch with 24x1G Base-T, ports and 4x1G/10G SFP+ slots, It should have 128 Gbps switching capacity and wire- speed architecture. Shouldsupportstackingofupto8switcheswith stacking bandwidth of 40Gbps. Switches in stack shall operate as one logical L3 switch . Stacking cables and associated accessories to be provided with switch. It should have internal Redundant Power Supply from day one. It should be architected to support real time applications like voice, video, data by having distributed architecture. Should be IPv6 logo ready, Standard ACLs on all ports, IPSourceGuard,DynamicARPInspection,IEEE 802.1x and DHCP snooping, SNMPv1, Switch / Switch’s Operating System should be tested forEAL2/NDPPoraboveunderCommonCriteria Certification/ FIPS-140-2 Certified, SupportmanagementusingCLI,GUIusingWeb interface. RoHS Compliant, IEEE802.1xsupport,IEEE802.3xfullduplexon 10BASE-T and 100BASE-TX ports, IEEE 802.1D Spanning-Tree Protocol, IEEE 802.1p class-of-service (CoS) prioritization, IEEE 802.1Q VLAN, IPv6 logo Ready, UL, EN60950, Operating Temperature: 0C to 45C, All Switches & Wi-Fi AP’s should be of same OEM complete with all labour and accessories upto the entire satisfaction of Engineer In Charge. Make: Extreme Networks / Alcatel Lucent / Allied Telesis
2Supply, Installation, Testing & Commissioning of24 Port Access SwitchPoE, Shall have 24x 1G Base-TPOE+ & 4x1G SFP Slots with PoE budget of 370w, Should support switching fabric of 56Gbps or more, Should support min forwarding rate of 10Mpps, Support 802.1D, 802.1S, 802.1w, Rate limiting, 16K MAC table, Support 802.1X Security standards, Support 802.1Q VLAN encapsulation, IGMP v1,v2 and v3 snooping, MLD snooping, up to 2096 active VLANs, Should support REP/ ERPS/equivalent for 50ms ring protection, Static routing, RIPv1/v2, Should Support 802.1Q Tagged VLAN, port based VLANs and Private VLAN, Should Support IEEE 802.1v VLAN classification by protocol and port, IEEE 802.1ac VLAN tagging, Should Support IEEE 802.1ad Provider bridges (VLAN stacking, Q-in-Q), Should Support PVST+ compatibility mode, Switch needs to have a console port for management via a console terminal or PC, SNMP V1, V2 and V3, Should support 4 groups of RMON and shall support single IP management of up to 20 switches, Should have accessibility using Telnet, SSH, Console access, easier software upgrade through network using TFTP etc. Configuration management through CLI, GUI based software utility or using web interface, SD/USB interface, Support SNMPv6, Telnetv6 and SSHv6, DHCPv6 relay, DHCPv6 client, NTPv6 client and server, Support NTP/SNTP, PTP, SDN Open flow v1.3 ready, Should support ACLs, VLAN ACL"s, other specification as per DNIT in Pdf.
3Supply, Installation, Testing & Commissioning of24 Port Non PoE Access SwitchPoE, Shall have 24x 1G Base-T & 4x1G SFP Slots, Should support switching fabric of 56Gbps or more, Should support min forwarding rate of 10Mpps, Support 802.1D, 802.1S, 802.1w, Rate limiting, 16K MAC table, Support 802.1X Security standards, Support 802.1Q VLAN encapsulation, IGMP v1,v2 and v3 snooping, MLD snooping, up to 2096 active VLANs, Should support REP/ ERPS/equivalent for 50ms ring protection, Static routing, RIPv1/v2, Should Support 802.1Q Tagged VLAN, port based VLANs and Private VLAN, Should Support IEEE 802.1v VLAN classification by protocol and port, IEEE 802.1ac VLAN tagging, Should Support IEEE 802.1ad Provider bridges (VLAN stacking, Q-in-Q), Should Support PVST+ compatibility mode, Switch needs to have a console port for management via a console terminal or PC, SNMP V1, V2 and V3, Should support 4 groups of RMON and shall support single IP management of up to 20 switches, Should have accessibility using Telnet, SSH, Console access, easier software upgrade through network using TFTP etc. other specifications as per DNIT in PDF.
4Supply, Installation, Testing & Commissioning ofA PIndoore, Access Points proposed must include radios for 2.4 GHz and 5 GHz with 802.11ax Wave 2. Shall have min 1x5Ghz IEEE 802.11ax and 1x2.4Ghz radios Wi-Fi6 (802.11ax) bidirectional MU-MIMO, An access point must include a standard OEM provided Mounting brackets for mounting on Celling or Rooftop. Access point must support spectrum intelligence across 20,40MHz-wide channels to combat performance problems due to wireless interference. Access point must have an1G/2.5G/5G Base-T PoE+ port, Must support 4x4 MU-MIMO 2.4GHz Internal antennas, 4x4 MU-MIMO 5GHz Internal antennas, Access point must support a minimum of 3.4 Gbps user throughput including both the radios.other specifications as per DNIT in PDF.
5Supply, Installation, Testing & Commissioning ofWireless Controller, WLAN Controller should be software based installed in a workstation, As Per technical Specification, It should have minimum 40 AP licenses or more from day 1, complete with all labour and accessories upto the entire satisfaction of Engineer In Charge. Make: Extreme Networks / Alcatel Lucent / Allied Telesis
6Supplying and drawing of UTP 4 pair CAT 6A LAN Cable in the existing surface/ recessed steel/PVC conduit as required. 4 Pair CAT6 Unshielded, Twisted Pair (U/UTP) Cable 305 mtr per Box. Blue/Yellow in colour conforming to the following standards like ANSI/TIA 568 C.2, EN50173, IEC 11801 2nd ED, 700Mhz etc. in Cat 6 U/UTP LCS2 cable with 23AWG. (As per HSR 2021 item no. 23.23.10) Make : CORNING/ R&M /PANDUIT / SIEMON
7Supplying, installing, testing and commissioning of 24 port Cat 6A patch panels available with block of four equipped with tool less IO, Rack Mountable. 19" Modular Patch Panel, loaded CAT6A U/UTP 24 port LCS2 rack mountable to be compatible in 4nos of 6 X RJ 45 Tool less connector U/UTP unit in a block complete with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer -incharge of work. Make : CORNING/ R&M /PANDUIT / SIEMON
8Supplying, installing, testing and commissioning of Cat 6A , Tool less Information outlet for Voice/Data. Cat6A U/UTP built in crimping hands-free, minimum 5 times reconnection possibilities. LCS2 Toolless RJ45 Information outlet where insertion test (in & out) must be 2500 times (I/O) along with front side Label holded and transparent shutter for category white in colour, including front plate and anodised GI box in concealed manner of adequate sizes,including all fixing accessories complete with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer -in-charge of work. Make : CORNING/ R&M /PANDUIT / SIEMON
9Supplying and fixing following Modular base & cover plate includinganodised GI box in concealed manner of adequate sizes,including all fixing accessories complete with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer -in-charge of work. Make : CORNING/ R&M /PANDUIT / SIEMON
10Supplying, installing, testing and commissioning of following length of Cat - 6a patch cord. 4 Feet : CAT6A UTP 23 AWG Patch Cord - 1 mtr - Rack End. Factory crimped LCS2 Patch cord. Make : CORNING/ R&M /PANDUIT / SIEMON
11Supplying, installing, testing and commissioning of following length of Cat - 6a patch cord. 7 Feet : CAT6A UTP 23 AWG Patch Cord - 2 mtr - Rack End. Factory crimped LCS2 Patch cord. Make : CORNING/ R&M /PANDUIT / SIEMON
12Supplying and fixing of PVC Cable Manager finger duct type complete the job in all respect upto the entire satisfaction of Engineer-in-charge of work. Make : CORNING/ R&M /PANDUIT / SIEMON
13SITC of 42RU, 800w x 1000d, 19" Comms equipment rack with front 19" rails and dual 8 to 12-outlet PDUs, and mesh-screen front and rear lockable doors, ventilated top cover with cable glands complete the job in all respect upto the entire satisfaction of Engineer-in-charge of work Make: HiveNetwork / Comrack / Netrack
14SITC of 15RU, 800w x lOOOd, 19" Comms equipment rack with front 19" rails and dual 8 to 12-outlet PDUs, and mesh-screen front and rear lockable doors, ventilated top cover with cable glands complete the job in all respect upto the entire satisfaction of Engineer-in-charge of work Make: HiveNetwork / Comrack / Netrack
15SITC of 12U,19" Outdoor Network rack with front 19" rails and dual 12-outlet PDUs, and mesh-screen front and rear lockable doors, ventilated top cover with cable glands complete the job in all respect upto the entire satisfaction of Engineer-in-charge of work Make: HiveNetwork / Comrack / Netrack
16SITC of2.5 sq mm 3 Core Power cable for all Services to complete the job in all respect upto the entire satisfaction of Engineer-in-charge of work
17Supplying and fixing of following sizes of PVC conduit medium/heavy along with accessories in surface / recess including painting in case of surface conduit or cutting the wall and making good the same in case of recessed conduit as required. Suply & erection ofPVC conduit pipe 25 mm dia ISI marked(Medium) recessed in wall/ ceiling etc. including cost ofPVC bends, inspection boxe and all other material equired to complete the job in all respect upto the entire satisfaction of Engineer-in-charge of work. (As per HSR 2021 item no. 23.7.6.2)
18Suply and erection of PVC pipe of 32 mm dia ISI marked ( Medium ) recessed in wall / ceiling etc. including the cost of PVC bends , inspection boxes , iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-charge of work. (As per HSR 2021 item no. 23.7.6.3)
19Supply Installation Testing & Commissioning of online 30 KVA UPS for60 minutes backup and in Redundancy Mode with all accessories required to do so. As per specification & at site of work in line with the Engineer in Charge. Make: Eaton / APC / Emerson/ Aar Kay
20Supply Installation Testing & Commissioning of Dual WAN Gigabit VPN router with basic firewall security features, 900 mbps throughput for TCP, uSER Datagram Protocol (UDP) traffic, Dynamic web filtering : Cloud based, morethan 80 categories, morethan 450 milion domains classified, VPN IP security. QOS, Doal stack, should support routing and NAT (Network address Translation), Port forwarding etc. complete in all respect upto the entire satisfaction of Engineer - in - Charge of the work. Make: Cisco/ Alcatel Lucent/ Extreme/ Allied
21Supply Installation Testing & Commissioning of Gigabit SFP module SM/ MM complete in all respect upto the entire satisfaction of Engineer - in - Charge of the work. Make: Cisco/ Alcatel Lucent/ Extreme/ Allied
22Supply Installation Testing & Commissioning of Gigabit media converter for WAN router to ISP including all accessories to complete the job in all respect upto the entire satisfaction of Engineer - in - Charge of the work. Make: Dlink/ Cisco/ Netgear
23FIRE ALARM SYSTEMSITC of Micro processor based 2 wire fault tolerant, networkable type fire alarm / detection control panel ( having nos. of 2 loops to suit minimum 20% extra over the nos. of fire detectors. The panel shall be able to give location of all fire / fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON/OFF respective control module when ever any alarm is triggered. The panel shall have rectifier, loop cards, minimum 160 character L C D unit/ 5.7’’TFT to indicate Fire / Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in allrespects. The Panel Shall be sheet Steel power coated, sealed to IP30. The Panel shall have 20 Zones with individual LED Indicators, expandable to 80LED Indicators. The Panel shall have 3 Serial Ports. The panel shall have a built in power supply and battery charger along with maintenance free 24 AH,2 x 12 volt SMF lead acid batteries capable of running for a minimum of 24 hours with battery charger complete as required. And conforming to BS5839 standards and Duly Approved by EN 54/UL/VDS/ as per specifications complete in all respect up to the entire satisfaction of Engineer-in – charge of workMakes : BoschFPA 5000 Series, Notifier NFS 3030 and Cerberus PRO by Siemens / Edward EST-3.
24SITC of Public Address System in Rack: consisting of the following480W Amplifier to suitable size Make : BOSCH / HONEYWELL / EDWARD /Heinrich - 01 No.Selector & all facility for announcement of different floor - 01 SetInterface unit for integration of main fire alarm panel with public address system = 01 No.
25Supply, Installation, Testing & commissioning ofCelling Mount Speaker with Plastic Mount or without mount as per site requirement for operation 6 Watts Make Honeywell/ BOSCH/Heinrich
26SITC ofaddressable Heat detector with fixed andrate of raise feature including mounting base with LED etc. complete as required.Each Detector should have 2as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005 .Detector should monitor Electromagnetic interference and report to the panel - current and average values. EMC safety for detector shall be 50 V/m.Shall be EN54/ VDs/UL certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector) Makes: Bosch / Siemens Cerberus / Notifier/ Edwards
27SITC of addressable multisensor detector with a combination of Opticaland Thermalincluding mounting base, auto addressing feauture asrequired.Detetctor should have 2 as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005 .Detector should monitor Electromagnetic interference and report to the panel - current and average values. EMC safety for detector shall be 50 V/m.Shall be EN54/ VDs/UL certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module after 20 devices) Makes: Bosch / Siemens Cerberus / Notifier/ Edwards
28SITC of intelligent Analog Addressable type Manual Call Point having Surface or flush mounting option fully compliat to EN 54 having Rotary Decade switches for addressing with back box for mounting as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Makes: Bosch / Siemens Cerberus / Notifier/ Edwards
29SITC of Addressable Loop powered sounder with strobe / flasher complete with mounting base as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Makes: Bosch / Siemens Cerberus / Notifier/ Edwards
30SITC of Analog Addressable type Active Repeater fire alarm panel with Backlit LCD Display, having controls for reset, mute, Accept, Silence alarms and self test conforming to BS5839 standards and Duly approved by EN54/UN54/VDS with all labour and material required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Makes: Bosch / Siemens Cerberus / Notifier/ Edwards
31SITC of Glow Type EXIT Sign Board photo luminescent of size 300 mm x 250 mm x 1.5 mm rigid sheet signage containing Zink Sulphate as bare chemical class – 1 material PSPA fixed on 3 mm acrylic sheet on both side showing marking (running man, Arrow and Exit) and hanged with the ceiling with chain and fastener including cost of labour & material required to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work MakePES/Giolite/OMEX
32SITC of Addressable Monitor Module for monitoring of a line with EOL resistor/ Potential free contact/ voltage monitoring shall be EN54/UL/VDS approved. (In case of 2 monitoring features in one module (points) each point shall be consider separately for payment).Make: Bosch / Siemens Cerberus / Notifier/ Edwards
33SITC ofAddressable Control Relay Module with flexible network structures with a maximun switching current of 1A @ 30V DC. Shall beEN54/UL/VDS CertificationMake: Bosch / Siemens Cerberus / Notifier/ Edwards
34SITC of UL/EN54/LPCB listed and FM Approved Line Isolator for Isolating the section of circuit in case of short in the addressable Loop wiring Make: Bosch / Siemens Cerberus / Notifier/ Edwards
35SITC of minimum 1000 Mtr. Range Siren generatorprovided at the roof of the building with separate power suppl, relay etc. with all accessories required to complete the job in all respect up to the entire satisfaction of engineer incharge. Make: National/Kheraj
36Supply & erection of FIRE EXTINGUISHERS duly hang on wall with necessary hook complete in all respect (Make: Safex/Minimax/ Ceasefire) ABC Dry power type fire Extinguishers of 5 kg. capacity
37Co2 type fire extinguishers of 4 Kg capacity
38Supply and erection of PVC Insulated and FRLS Round Sheathed Multi Core Bright Annealed Bare Copper Conductor Heavy Duty Industrial Flexible Cables for Voltage Grade 1100 Volts conforming to IS: 694:2010 complete in all respect upto the entire satisfaction of Engineer in charge of the work 2 core PVC unsheathed copper size 1.5 sq mm
39Supply and erection of PVC conduit pipe ISI marked (Medium) recessed in wall /ceiling etc. including cost of PVC bends, inspection box and all other material required to complete the job in all respect to the entire satisfaction of Engineer-in-Charge of work. (As per HSR 2021 item no. 23.7.6.2)25 mm dia
40SITC of 22 U Standard rack to place all Av equipment and all other material required to complete the job in all respect upto the entire satisfaction of Engineer-in-charge of work. Make Valrack, Comrack,Hive Networks
41SITC of battery backup for controllers ( 5 KVA UPS on line with 1 hours backup ) and all other material required to complete the job in all respect upto the entire satisfaction of Engineer-in-charge of work. Make APC/ LIEBERT EMERSON/Microtek/ Aar Kay
42SITC of controller unit 6-zone system pre-amplifier 160 inbuilt amplifier with single or dual channel operation. Two input channels for call stations , Universal input for microphone/line, with speech optimized tone control , Three inputs for BGM selection and music optimized tone control , Front panel zone selection for BGM and call station zone selection for calls, S/N (flat at max volume) >63 dB (mic); >70 dB (line), S/N (flat at min volme/muted) >75 dB, CMRR >40 dB (50 Hz - 20 kHz),Line input 3 x, Master output 1 x, Frequency response 50 Hz to 20 kHz (+1 / -3 dB) complete in all respect Make: BOSCH /Heinrich / Honeywell
43SITC of Booster amplifier 480 watts Frequency response: 60 Hz to 15 khz (+1/3db), Inputs :XLR & phone jack , Input 1, Input 24, Impendence :20kG, Sensitivity : 1 V balanced , S/N >: >85 dB complete in all respect Make: BOSCH /Heinrich / Honeywell
44SITC of Stylish 6-zone call station, Six zone selection keys, allcall key and momentary PTT-key for calls Selectable gain, speech filter and limiter for improved intelligibility LED indications for zone selection, fault and emergency state Voltage range 18 - 24V Nominal sensitivity 85 dB SPL (gain preset 0dB) Gain preset +6 / 0 / -15 dB Equivalent input noise level 25 dBSPLA Frequency response 100Hz - 16kHz complete in all respect Make: BOSCH /Heinrich / Honeywell
45SITC of Horn Loudspeaker 15 watts . Max power 22.5 W, Rated power (PHC) 15 W ( 15,7.5,3.75 W) ,Sound pressure Level rated power 103dB ( At 1kHz,Iw,Im), Effective frequency range (-10dB) 500Hz to 5KHz ,Opening angle (at 1 kHz/4kHz,-6 dB), Rated voltage 100 V . Rated impedance 667ohm. Ambient temperature range -25 to +55 C .Connection 4 wire cable, 50 cm long complete in all respect Make: BOSCH /Heinrich / Honeywell
46SITC of Cabinet Speaker Max Power - 9 W ,Rated power (PHC) -6 W(6-3-1.5), Sound pressure level at rate power /1 w ,(at1kHz,1m) (at 1 kHz, 1 m) - 96dB/ 90dB,Effective frequency range (-10 dB) - 200-15000 Hz,Opening angle (at 1 kHz/4 kHz, -6 dB),In degrees - 150/70,Rated voltage - 100 V,Rated impedance - 1667 Make: BOSCH /Heinrich / Honeywell
47Supply, installation, testing & commissioning of 17 U Standard rack to place all Av equipment Make Valrack, Comrack,Hive Networks.