Tender For Development Of 60.34 Hact. ( 234.07 Hact. ) Of Land At Sector-41 ( Part ) In Rohini Ph-V.Sh:Sitc Of Street Light Network On 30 & 60 Mtr. Wide Road., rohini-Delhi

Delhi Development Authority-DDA has published Tender For Development Of 60.34 Hact. ( 234.07 Hact. ) Of Land At Sector-41 ( Part ) In Rohini Ph-V.Sh:Sitc Of Street Light Network On 30 & 60 Mtr. Wide Road.. Submission Date for this Tender is 01-08-2023. Land Development Tenders in rohini Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

38801036
Tender For Development Of 60.34 Hact. ( 234.07 Hact. ) Of Land At Sector-41 ( Part ) In Rohini Ph-V.Sh:Sitc Of Street Light Network On 30 & 60 Mtr. Wide Road.
Open Tender
Indian
Delhi
rohini
01-08-2023

Tender Details

Development Of 60.34 Hact. ( 234.07 Hact. ) Of Land At Sector-41 ( Part ) In Rohini Ph-V.Sh:Sitc Of Street Light Network On 30 & 60 Mtr. Wide Road. ; 1 Supply, Erection, Testing And Commissioning Of Hot Dip Galvanized Octagonal Steel Pole Of 11 Mtr. Height Made Out Of 3 Mm Thick Sheet Pcd 320 Mm, Having Bottom 200 Mm A / F & Top 100 Mm A / F With Built In Connector Box Of Size 500 Mm X 120 Mm With Ring Of Minimum 250 Mm Width Made Of 3 Mm Thick Sheet On Window Cover For Antitheft Arrangement At 2500 Mm Height From Base Plate, M.S Base Plate Of Size 320 Mm X 320 Mm X 20 Mm Thick, Triple Overhang G.I Bracket Made Of 3.60 Mm Thick M.S Pipe With 400 Mm Long Top Galvanized M.S Tube Of Suitable Dia. To Accommodate The Fittings, On Existing Rcc Foundation I / C S / F Of 4 Nos. M-24 X 750 Mm Long ( 150 Mm Top Threaded Portion ) , G.I Foundation Bolts ( L Type ) & Nuts ( En 8-Grade ) With 3 Nos. And2 Nos. Washer Along With 2 Nos. Templates / Anchor Plate Of Size 320 Mm X 320 Mm X 4 Mm Thick, Making Connections, Interconnections With Suitable Size Of Copper Wire With Thimble / Lugsin The Connector Box, Earthing, Marking, Numbering Of Pole Etc. Complete As Per Drawing & Technical Specifications Attached Including Following Accessories Mounted On Inbuilt Control Box Having Flush Cover With 2 Nos. Mounting Strips With Tapped Holes:- A ) 6 Mm Thick Phenolic Laminated Sheet / Bakelite Sheet Inside The Window Mounted On The Existing Mounting Strips Inside The Flush Door. B ) S / F Of 40 Amp Terminal Block Suitable For 16 Sq. Mm Conductor- 4 Nos. & Shorting Links-5 Nos. On Din Channel I / C P / F Din Channel Of Suitable Length- 2 Nos. On Existing Laminated Sheet. C ) Terminal Suitable For 6-Swg G.I. Wire / 1.5 Sq. Mm Wire. D ) 6 Amp, Sp Mcb, 10 Ka, ‘C’ Series – 3 Nos. Including Mounting On Din Channel, Earth Stud 2 Nos. Welded At Suitable Height I / C Washers & Nuts Etc. E ) Suitable Arrangement For Saddling Of Incoming / Outgoing Cables I / C Lugs / Thimbles Etc. As Required. 2 Supply, Erection, Testing And Commissioning Of Hot Dip Galvanized Octagonal Steel Pole Of 11 Mtr. Height Made Out Of 3 Mm Thick Sheet Pcd 320 Mm, Having Bottom 200 Mm A / F & Top 100 Mm A / F With Built In Connector Box Of Size 500 Mm X 120 Mm With Ring Of Minimum 250 Mm Width Made Of 3 Mm Thick Sheet On Window Cover For Antitheft Arrangement At 2500 Mm Height From Base Plate, M.S Base Plate Of Size 320 Mm X 320 Mm X 20 Mm Thick, Double Overhang G.I Bracket Made Of 3.60 Mm Thick M.S Pipe With 400 Mm Long Top Galvanized M.S Tube Of Suitable Dia. To Accommodate The Fittings, On Existing Rcc Foundation I / C S / F Of 4 Nos. M-24 X 750 Mm Long ( 150 Mm Top Threaded Portion ) , G.I Foundation Bolts ( L Type ) & Nuts ( En 8-Grade ) With 3 Nos. And2 Nos. Washer Along With 2 Nos. Templates / Anchor Plate Of Size 320 Mm X 320 Mm X 4 Mm Thick, Making Connections, Interconnections With Suitable Size Of Copper Wire With Thimble / Lugsin The Connector Box, Earthing, Marking, Numbering Of Pole Etc. Complete As Per Drawing & Technical Specifications Attached Including Following Accessories Mounted On Inbuilt Control Box Having Flush Cover With 2 Nos. Mounting Strips With Tapped Holes:- A ) 6 Mm Thick Phenolic Laminated Sheet / Bakelite Sheet Inside The Window Mounted On The Existing Mounting Strips Inside The Flush Door. B ) S / F Of 40 Amp Terminal Block Suitable For 16 Sq. Mm Conductor- 4 Nos. & Shorting Links-5 Nos. On Din Channel I / C P / F Din Channel Of Suitable Length- 2 Nos. On Existinglaminated Sheet. C ) Terminal Suitable For 6-Swg G.I. Wire / 1.5 Sq. Mm Wire. D ) 6 Amp, Sp Mcb, 10 Ka, ‘C’ Series – 2 Nos. Including Mounting On Din Channel, Earth Stud 2 Nos. Welded At Suitable Height I / C Washers & Nuts Etc. E ) Suitable Arrangement For Saddling Of Incoming / Outgoing Cables I / C Lugs / Thimbles Etc. As Required. 3 Providing And Laying In Position, M25 Reinforced Cement Concrete Foundation Of Size 750 Mm Long X 750 Mm Wide And 1800 Mm Deep I / C Excavation Of Earth, Refilling, Providing Cutting, Bending And Placing In Position Reinforcement Of Cold Twisted Bar Of 12 Mm Dia. 1900 Mm Long ( Approx. ) -8 Nos. And Reinforcement Ring Of Cold Twisted Bar Of 8 Mm Dia. 2900 Mm Long ( Approx. ) -10 Nos. ( With 150 Mm Spacing ) I / C Centering & Shuttering As Required Positioning Of Foundation Bolts And Providing 63 Mm ( Od ) -2 Nos. Dwc Pipe 1 Mtr. Long Each For Cable Entry And Exit Etc. Complete As Required. 4 Providing And Laying In Position, M25 Reinforced Cement Concrete Foundation Of Size 1000 Mm Long X 600 Mm Wide And 1800 Mm Deep I / C Excavation Of Earth, Refilling, Providing Cutting, Bending And Placing In Position Reinforcement Of Cold Twisted Bar Of 12 Mm Dia. 1900 Mm Long ( Approx. ) -8 Nos. And Reinforcement Ring Of Cold Twisted Bar Of 8 Mm Dia. 3200 Mm Long ( Approx. ) -10 Nos. ( With 150 Mm Spacing ) I / C Centering & Shuttering As Required Positioning Of Foundation Bolts And Providing 63 Mm ( Od ) -2 Nos. Dwc Pipe 1 Mtr. Long Each For Cable Entry And Exit Etc. Complete As Required. 5 Supply, Installation, Testing And Commissioning Of 210 Watt Led Street Light Fitting Made Up Of Pressure Die Cast Aluminium Housing ( Ip-66 Protection And Ik07 Impact Resistance ) Complete With All Accessories Including Making Connection Etc. Complete As Required And As Per Technical Specification Attached. Led Street Light Fixture Of Not More Than 210 Watt And Lumens Output Not Less Than 27100 Rating. 6 Supplying And Drawing Of 3 X 1.5 Sq. Mm Size Of 1.1 Kv Grade Frls Pvc Insulated Copper Conductor Single Core Cable In The Existing Surface / Recessed Steel Conduit As Required. 7 Supplying Of Following Sizes Of Xlpe Aluminium Conductor Armoured Power Cable Of 1.1 Kv Grade As Per Technical Specification Attached. 4 X 16 Sq. Mm 8 Supplying Of Following Sizes Of Xlpe Aluminium Conductor Armoured Power Cable Of 1.1 Kv Grade As Per Technical Specification Attached. 3.5 X 35 Sq. Mm 9 Laying Of One Number Pvc Insulated And Pvc Sheathed / Xlpe Power Cable Of 1.1 Kv Grade Of Following Size Direct In Ground Includingexcavation, Sand Cushioning, Protective Covering And Refilling The Trench Etc. As Required. Note:- Excavation Shall Also Include Pacca Cutting Wherever Applicable As Per Site Requirement And Nothing Extra Shall Be Paid On This Account. 10 Supplying And Laying Of Following Size Dwc Hdpe Pipe Isi Marked Along With All Accessories Like Socket, Bend, Couplers Etc. Conforming To Is 14930, Part Ii Complete With Fitting And Cutting, Jointing Etc. Direct In Ground ( 75 Cm Below Ground Level ) Including Excavation And Refilling The Trench But Excluding Sand Cushioning And Protective Covering Etc., Complete As Required. 63 Mm Dia. ( Od-63 Mm & Id-51 Mm Nominal ) Note:- Excavation Shall Also Include Pacca Cutting Wherever Applicable As Per Site Requirement And Nothing Extra Shall Be Paid On This Account. 11 Supply, Boring And Laying Of Hdpe Dwc Pipes ( Isi ) Marked Of The 90 Mm Dia. Size Confirming To Is:4984 With Pressure Rating Of 6Kg / Sq.Cm By Trench Less Technology With No Dig. Method By Making Bore Hole In Horizontal Direction Across The Road With Boring Equipment I / C Jointing, Cleaning, Rodding Of Pipe Performing Mandrel Test Providing Suitable Covers On Mouth Of Pipes, Excavation Of Pits Of Required Size & Depth And Laying Of Cables In The Pipe Etc. Complete As Required. 12 Laying Of One Number Pvc Insulated And Pvc Sheeted / Xlpe Power Cable Of 1.1 Kv Grade Of Following Size In The Existing Rcc / Hume / Metal / Dwc Pipe As Required. Up To 35 Sq. Mm 13 Overhead Laying Of 4 X 16 Sq. Mm Xlpe Aluminium Conductor Armoured Power Cable Of 1.1 Kv Grade With Fixing Of Cable On Street Light Pole By Shackle Insulator I / C Clamp, Rod, Nuts And Bolts Etc. For Support Of Insulator On The Pole And Connection To The Existing Led Fitting By Ipc Connector I / C Connection, Testing Etc. Complete As Required. 14 Providing And Fixing 200 A Rating And 36Ka Breaking Capacity Fpmccb ( Ics= Icu ) With Thermomagnetic Release And Terminal Spreaders Inside A Suitable Size Hot Press Moulded Smc Junction Box Of Inside Size 350 Mm X 270 Mm X 190 Mm, Side Hinged Door Type With Provision For 3 Phase Cable Entry, Exit & External Bracket For Fixing On Wall Including Drilling Holes, Making Connections, Testing Etc. Complete As Required. 15 Supply Installation, Testing & Commissioning Of Floor Mounted Free Standing Type L.T. Cubicle Main Feeder Pillar Duly Compartmentalized ( Outdoor Type ) Made Out Of 2 Mm Thick Ms Crca Sheet, 7-Tank Process Powder Coated With 4 Nos. X 600 Mm Long Legs Made Of M.S Angle Iron Of Size 40 Mm X 40 Mm X 5 Mm Thick Along With Frame & Legs Suitably Grouted In Foundation I / C Connection Inter Connection Of The Accessories Mounted There On With Suitable Size Of Copper Wire / Strip With Thimble / Lugs, Earthing The Body Of The Feeder Pillar I / C Supplying & Fixing Of The Following Items And As Per Technical Specification Enclosed. A ) 100 A, 36Ka, Fpmccb ( Ics= Icu ) -1 No ( Incomer ) . B ) Volt Meter ( 0-500V ) 96 Sq. Mm With Selector Switch- 1 Set, C ) Ammeter ( 0-100A ) 96 Sq. Mm With Selector Switch & 100 / 5 Amp Ratio Cts- 1 Set D ) Indication Lamp ( Ryb ) With Control Hrc Fuse With Fuse Fitting- 1 Set, E ) 63 A, 16Ka, Fpmccb ( Outgoing Circuit ) ( Ics= Icu ) - 3 Nos, F ) 6 Amp Sp Mcb-1 No., G ) 3 Pole Power Contactor Of Ac-3 Rating 100 Amp. -1 No., H ) Astronomical Time Switch-1 No., I ) Auto / Manual Toggle Switch-1 No., J ) 100 Amp, 4 Strip Aluminium Busbar-1 Set, K ) Danger Notice Plate-1 No., L ) 6 Pin 15 A Switch & Socket Outlet-1 Set M ) Led Lighting Inside The Feeder Pillar, Note:- Pcc ( 1:2:4 ) Foundation Height Of 750 Mm Duly Plastered & Finished Having Top Outer Edges 30 Cm Beyond All Round The Edges Of 40 X 5 Angle Iron Frame Shall Be Made Asper Site Requirement For Which Nothing Extra Shall Be Paid. 16 Supplying And Making End Termination With Brass Compression Gland And Aluminium Lugs For Following Size Of Pvc Insulated And Pvc Sheathed / Xlpe Aluminium Conductor Cable Of 1.1 Kv Grade As Required. 4 X 16 Sq. Mm ( 28 Mm ) 17 Supplying And Making End Termination With Brass Compression Gland And Aluminium Lugs For Following Size Of Pvc Insulated And Pvc Sheathed / Xlpe Aluminium Conductor Cable Of 1.1 Kv Grade As Required. 3½ X 35 Sq. Mm ( 32 Mm ) 18 Earthing With G.I. Earth Pipe 4.5 Meter Long, 40 Mm Dia. Including Accessories, And Providing Masonry Enclosure With Cover Plate Having Locking Arrangement And Watering Pipe Etc. With Charcoal / Coke And Salt As Required. 19 Providing And Fixing 25 Mm X 5 Mm G.I. Strip In 40 Mm Dia. G.I. Pipe From Earth Electrode Including Connection With G.I. Nut, Bolt, Spring, Washer Excavation And Re-Filling Etc. As Required. 20 Providing And Fixing 25 Mm X 5 Mm G.I. Strip On Surface Or In Recess For Connection Etc. As Required. 21 Providing And Fixing 6 Swg Dia. G.I. Wire On Surface Or In Recess For Loop Earthing Along With Existing Surface / Recessed Conduit / Sub Main Wiring / Cable As Required. 22 Supplying And Making Cable Route Marker With Cement Concrete 1:2:4 ( 1 Cement : 2 Coarse Sand : 4 Graded Stone Aggregate 20 Mm Nominal Size ) Of Size 60 Cm X 60 Cm At The Bottom And 50 Cm X 50 Cm At The Top With A Thickness Of 10 Cm Including Inscription Duly Engraved As Required.

Key Value

Document Fees
Refer document
EMD
INR 165796.0 /-
Tender Value
INR 82.89 Lakhs /-

BOQ Items

Name of Work: D/o 60.34 Hact. (234.07 Hact.) of land at Sector-41 (part) in Rohini Ph-V. SH:SITC of Street Light Network on 30 & 60 mtr. wide road.
Sl. No. Item Description
1Supply, erection, testing and commissioning of HOT dip galvanized octagonal steel pole of 11 mtr. height made out of 3 mm thick sheet PCD 320 mm, having bottom 200 mm A/F & top 100 mm A/F with built in connector box of size 500 mm x 120 mm with ring of minimum 250 mm width made of 3 mm thick Sheet on window cover for antitheft arrangement at 2500 mm height from base plate, M.S base plate of size 320 mm x 320 mm x 20 mm thick, Triple Overhang G.I bracket made of 3.60 mm thick M.S pipe with 400 mm long top galvanized M.S tube of suitable dia. to accommodate the fittings, on existing RCC foundation i/c S/F of 4 Nos. M-24 x 750 mm long (150 mm top threaded portion), G.I foundation bolts (L Type) & nuts (EN 8-grade) with 3 Nos. and2 Nos. washer along with 2 Nos. templates/Anchor plate of size 320 mm x 320 mm x 4 mm thick, making connections, interconnections with suitable size of copper wire with thimble/lugsin the connector box, earthing, marking, numbering of pole etc. complete as per drawing & technical specifications attached including following accessories mounted on inbuilt control box having flush cover with 2 Nos. mounting strips with tapped holes:- a) 6 mm thick phenolic laminated sheet/ bakelite sheet inside the window mounted on the existing mounting strips inside the flush door. b) S/F of 40 Amp terminal block suitable for 16 sq. mm conductor- 4 Nos. & shorting links-5 Nos. on DIN Channel i/c P/F DIN Channel of suitable length- 2 Nos. on existing laminated sheet. c) Terminal suitable for 6-SWG G.I. wire/ 1.5 sq. mm wire. d) 6 Amp, SP MCB, 10 KA, ‘C’ Series – 3 Nos. including mounting on DIN Channel, earth stud 2 Nos. welded at suitable height i/c washers & nuts etc. e) Suitable arrangement for saddling of incoming/ outgoing cables i/c lugs/thimbles etc. as required.
2Supply, erection, testing and commissioning of HOT dip galvanized octagonal steel pole of 11 mtr. height made out of 3 mm thick sheet PCD 320 mm, having bottom 200 mm A/F & top 100 mm A/F with built in connector box of size 500 mm x 120 mm with ring of minimum 250 mm width made of 3 mm thick Sheet on window cover for antitheft arrangement at 2500 mm height from base plate, M.S base plate of size 320 mm x 320 mm x 20 mm thick, Double Overhang G.I bracket made of 3.60 mm thick M.S pipe with 400 mm long top galvanized M.S tube of suitable dia. to accommodate the fittings, on existing RCC foundation i/c S/F of 4 Nos. M-24 x 750 mm long (150 mm top threaded portion), G.I foundation bolts (L Type) & nuts (EN 8-grade) with 3 Nos. and2 Nos. washer along with 2 Nos. templates/Anchor plate of size 320 mm x 320 mm x 4 mm thick, making connections, interconnections with suitable size of copper wire with thimble/lugsin the connector box, earthing, marking, numbering of pole etc. complete as per drawing & technical specifications attached including following accessories mounted on inbuilt control box having flush cover with 2 Nos. mounting strips with tapped holes:- a) 6 mm thick phenolic laminated sheet/ bakelite sheet inside the window mounted on the existing mounting strips inside the flush door. b) S/F of 40 Amp terminal block suitable for 16 sq. mm conductor- 4 Nos. & shorting links-5 Nos. on DIN Channel i/c P/F DIN Channel of suitable length- 2 Nos. on existinglaminated sheet. c) Terminal suitable for 6-SWG G.I. wire/ 1.5 sq. mm wire. d) 6 Amp, SP MCB, 10 KA, ‘C’ Series – 2 Nos. including mounting on DIN Channel, earth stud 2 Nos. welded at suitable height i/c washers & nuts etc. e) Suitable arrangement for saddling of incoming/ outgoing cables i/c lugs/thimbles etc. as required.
3Providing and laying in position, M25 reinforced cement concrete foundation of size 750 mm long x 750 mm wide and 1800 mm deep i/c excavation of earth, refilling, providing cutting, bending and placing in position reinforcement of cold twisted bar of 12 mm dia. 1900 mm long (approx.)-8 Nos. and reinforcement ring of cold twisted bar of 8 mm dia. 2900 mm long (approx.)-10 Nos. (With 150 mm spacing) i/c centering & shuttering as required positioning of foundation bolts and providing 63 mm (OD)-2 Nos. DWC pipe 1 mtr. long each for cable entry and exit etc. complete as required.
4Providing and laying in position, M25 reinforced cement concrete foundation of size 1000 mm long x 600 mm wide and 1800 mm deep i/c excavation of earth, refilling, providing cutting, bending and placing in position reinforcement of cold twisted bar of 12 mm dia. 1900 mm long (approx.)-8 Nos. and reinforcement ring of cold twisted bar of 8 mm dia. 3200 mm long (approx.)-10 Nos. (With 150 mm spacing) i/c centering & shuttering as required positioning of foundation bolts and providing 63 mm (OD)-2 Nos. DWC pipe 1 mtr. long each for cable entry and exit etc. complete as required.
5Supply, installation, testing and commissioning of 210 watt LED street light fitting made up of pressure die cast aluminium housing (IP-66 protection and IK07 impact resistance) complete with all accessories including making connection etc. complete as required and as per technical specification attached. LED street light fixture of not more than 210 watt and lumens output not less than 27100 rating.
6Supplying and drawing of 3 x 1.5 sq. mm size of 1.1 KV grade FRLS PVC insulated copper conductor single core cable in the existing surface/recessed steel conduit as required.
7Supplying of following sizes of XLPE aluminium conductor armoured power cable of 1.1 KV grade as per technical specification attached. 4 x 16 sq. mm
8Supplying of following sizes of XLPE aluminium conductor armoured power cable of 1.1 KV grade as per technical specification attached. 3.5 x 35 sq. mm
9Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following size direct in ground includingexcavation, sand cushioning, protective covering and refilling the trench etc. as required. Note:- Excavation shall also include pacca cutting wherever applicable as per site requirement and nothing extra shall be paid on this account.
10Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 63 mm dia. (OD-63 mm & ID-51 mm nominal) Note:- Excavation shall also include pacca cutting wherever applicable as per site requirement and nothing extra shall be paid on this account.
11Supply, boring and laying of HDPE DWC pipes (ISI) marked of the 90 mm dia. size confirming to IS:4984 with pressure rating of 6KG/Sq.cm by trench less technology with no dig. method by making bore hole in horizontal direction across the road with boring equipment i/c jointing, cleaning, rodding of pipe performing mandrel test providing suitable covers on mouth of pipes, excavation of pits of required size & depth and laying of cables in the pipe etc. complete as required.
12Laying of one number PVC insulated and PVC sheeted/XLPE power cable of 1.1 KV grade of following size in the existing RCC/HUME/Metal/DWC pipe as required. Up to 35 sq. mm
13Overhead laying of 4 x 16 sq. mm XLPE aluminium conductor armoured power cable of 1.1 KV grade with fixing of cable on street light pole by shackle insulator i/c clamp, Rod, nuts and bolts etc. for support of insulator on the pole and connection to the existing LED fitting by IPC connector i/c connection, testing etc. complete as required.
14Providing and fixing 200 A rating and 36KA breaking capacity FPMCCB (Ics= Icu) with thermomagnetic release and terminal spreaders inside a suitable size hot press moulded SMC junction box of inside size 350 mm x 270 mm x 190 mm, side hinged door type with provision for 3 phase cable entry, exit & external bracket for fixing on wall including drilling holes, making connections, testing etc. complete as required.
15Supply installation, testing & commissioning of floor mounted free standing type L.T. cubicle main feeder pillar duly compartmentalized (outdoor type) made out of 2 mm thick MS CRCA sheet, 7-tank process powder coated with 4 nos. x 600 mm long legs made of M.S angle iron of size 40 mm x 40 mm x 5 mm thick along with frame & legs suitably grouted in foundation i/c connection inter connection of the accessories mounted there on with suitable size of copper wire/strip with thimble/lugs, earthing the body of the feeder pillar i/c supplying & fixing of the following items and as per technical specification enclosed. a) 100 A, 36KA, FPMCCB (Ics= Icu)-1 No (incomer). b) Volt meter (0-500V) 96 Sq. mm with selector switch- 1 Set, c) Ammeter (0-100A) 96 Sq. mm with selector switch & 100/5 Amp ratio CTS- 1 Set d) Indication Lamp (RYB) with control HRC fuse with fuse fitting- 1 Set, e) 63 A, 16KA, FPMCCB (Outgoing circuit) (Ics= Icu) - 3 Nos, f) 6 amp SP MCB-1 No., g) 3 Pole Power Contactor of AC-3 rating 100 Amp. -1 No., h) Astronomical Time switch-1 No., i) Auto/Manual toggle switch-1 No., j) 100 amp, 4 strip aluminium busbar-1 Set, k) Danger Notice plate-1 No., l) 6 Pin 15 A Switch & Socket outlet-1 Set m) LED Lighting inside the feeder pillar, Note:- PCC(1:2:4) foundation height of 750 mm duly plastered & finished having top outer edges 30 cm beyond all round the edges of 40 x 5 angle iron frame shall be made asper site requirement for which nothing extra shall be paid.
16Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade as required. 4 x 16 sq. mm (28 mm)
17Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ x 35 sq. mm (32 mm)
18Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia. including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
19Providing and fixing 25 mm x 5 mm G.I. strip in 40 mm dia. G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
20Providing and fixing 25 mm x 5 mm G.I. strip on surface or in recess for connection etc. as required.
21Providing and fixing 6 SWG dia. G.I. wire on surface or in recess for loop earthing along with existing surface/recessed conduit/sub main wiring/cable as required.
22Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm x 50 cm at the top with a thickness of 10 cm including inscription duly engraved as required.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail