Tender For Comprehensive Maintenance And Repair Replacement Of Fire Alarm System And Fire Fighting System Including Allied Works At Icgs Malkapuram Under Age(I)(Cg) Vizag, visakhapatnam-Andhra Pradesh

Military Engineer Services-MES has published Tender For Comprehensive Maintenance And Repair Replacement Of Fire Alarm System And Fire Fighting System Including Allied Works At Icgs Malkapuram Under Age(I)(Cg) Vizag. Submission Date for this Tender is 29-07-2023. Alarm Systems Tenders in visakhapatnam Andhra Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

38568577
Tender For Comprehensive Maintenance And Repair Replacement Of Fire Alarm System And Fire Fighting System Including Allied Works At Icgs Malkapuram Under Age(I)(Cg) Vizag
Open Tender
Indian
Andhra Pradesh
visakhapatnam
29-07-2023

Tender Details

Comprehensive Maintenance And Repair Replacement Of Fire Alarm System And Fire Fighting System Including Allied Works At Icgs Malkapuram Under Age ( I ) ( Cg ) Vizag

Key Value

Document Fees
INR 500 /-
EMD
INR 29900.0 /-
Tender Value
INR 14.95 Lakhs /-

BOQ Items

NAME OF WORK: COMPREHESIVE MAINTENANCE AND REPAIR REPLACEMENT OF FIRE ALARM SYSTEM AND FIRE FIGHTING SYSTEM INCLUDING ALLIED WORKS AT ICGS MALKAPURAM UNDER AGE(I)(CG) VIZAG
Sl. No. Item Description
1Repair/Routine maintenance including carrying out daily check of addressable fire alarm system located at OTM Complex and Sport Complex installed with EST make.The contractor shall carryout maintenance only through OEM/OES service provider of approved Edward representative in order to readdress detectors in monthly basis and recomissioing of detectors frequently, The service also need to be included Scope of Contract: (i). The period of the AMC shall be for a period as per MES Contract. (ii). The Frequency and scope of visits to the site for routine or scheduled maintenance visits will be quarterly. (iii). A supervised fire drill shall be carried out as per client requirement. (iv). A Service Engineer will report to site, within 4 – 8 working hours, from the Time of Complaint Logging. (v). Any work, deemed outside the scope of the AMC, shall be charged extra. (vi). Training to the User Team will be given Half –Yearly based on Client requirement. (vii). In case of any failure of material/Components, Suitable components will be replaced on chargeable basis. (viii). Device cleaning will be done by SIGA – Pro as per OEM, and maintenance Date will be changed as per standard for the Dirty Devices.
2Repair/Routine maintenance including carrying out daily check offire fighting system complete with electronic control panel consisting of zones in CGC Building, Pandya, Kalinga, C1 & C2 buildings including attendance of alarm personnel to attend the fire alarm system faults, testing, checking including replacement of unserviceable components other than mentioned in schedule “A” The fire fighting system consisting the following:- (a)   Indicators (b)   Electronic hooter (c)   Manual call points (d)   Smoke detector (e)   Heat detector (f)    Electronic fire control panel (g)   Main/Zone cards (h)   Battery of Fire panel DC supply (J) All wiring and cable connections (k) Fire diesel pump (l)Main Fire pump (m)Booster pump
3M & L for attending break down of pipe line bursting/creaks including removal of broken pipe pieces of various lengths through gas cutting/manual cutting as per site requirement including testing for the arresting leakages for the 200 mm size of MS pipe complete all as specified and directed by Engr-in- Charge. Notes :- a) Necessary labour, T&P is demed to be included in the quoted rate. b)Excavation work, pipe lenghts will be meaured and paid separately.
4Supply only MS ERW pipe of 150 mm dia, 5.4 mm thickness all as directed by Engr-in-Charge.
5Supply only MS ERW pipe of 100 mm dia, 5.4 mm thickness all as directed by Engr-in-Charge.
6Supply only MS ERW pipe of 80 mm dia, 4.84 mm thickness all as directed by Engr-in-Charge.
7Supply and replacement of damaged/defective/unserviceable fire brigade inlet connection 4 way complete all as specified and as and as directed.
8Supply and replacement of damaged/defective/unserviceable fire brigade inlet connection 2 waycomplete all as specified and as directed.
9Supply and replacement fire hydrant landing valve GM type A single outletof 63 mm dia withnew hydrant confirming to IS 5290 with PVC blank cap and MS or GI chaincomplete all as specified and as directed.
10Supply and replacement fire hydrant landing valve GM type B ( Double head outlet) of 63 mm dia withnew hydrant confirming to IS 5290 with PVC blank cap and MS or GI chaincomplete all as specified and as directed.
11Supply and replacement damaged /defective/unserviceable ABS plastic 3/4" shut off nozzle suitable for 19/20 mm hosecomplete all as specified and as directed.
12Supply and fixing 150 mm Dia damaged/defective/unserviceable sluice valve class PN 1.6 including taking down the old Sluice valvecomplete all as specified and as directed by Engr-in-Charge.
13Supply and fixing 100 mm Dia damaged/defective/unserviceable sluice valve class PN 1.6 including taking down the old Sluice valvecomplete all as specified and as directed by Engr-in-Charge.
14Supply and fixing 80 mm Dia damaged/defective/unserviceable sluice valve class PN 1.6 including taking down the old Sluice valvecomplete all as specified and as directed by Engr-in-Charge.
15Supply and replacement damaged/defective/unserviceable Cast Iron Non Return valve 150 mm dia with necessary rubber gasket, bolts, nuts and washer completeall as specified and directed by Engr-in-Charge.
16Supply and replacement damaged/defective/unserviceable Cast Iron Non Return valve 100 mm dia with necessary rubber gasket, bolts, nuts and washer completeall as specified and directed by Engr-in-Charge.
17Supply and replacement damaged/defective/unserviceable Cast Iron Non Return valve 80 mm dia with necessary rubber gasket, bolts, nuts and washer completeall as specified and directed by Engr-in-Charge.
18Supply &fixingin repair presure gauge glycerine filled with 15 mm inlet connection dial size 100 mm of pressure range 0 to 14Kg/cm2 with 15mm isolation valve with G.I. nipplecompleteall as specified and directed by Engr-in-Charge.
19Supply &fixingin repair presure gauge glycerine filled with 15mm inlet connection dial size 200 mm of pressure range 0to 21Kg/cm2 with 15mm isolation valve with G.I. nipple completeall as specified and directed by Engr-in-Charge.
20Repair/Servicing of fire hydrant landing valve type "A/B" of 63 mm dia, including spindle thread machine, washers replacementmnt, checkout, packing serving complete to arrest leakage and proper function of valvecompleteall as specified and directed by Engr-in-Charge.
21Material and labour for cleaning of over head terrace tank of capacity 25000 ltrs by pumping out the accumulated water in the bottom and removing the complete site from the sumps and depositing and levelling as directed and cleaning with bleachingpowder and wire brushing the sumps after scrapping completely without disturbing the water supply to the area including painting and due date of cleaning on the sump wall and applying one coat of white wash to entire sump externally as well as internally complete all as directed by Engr-in-Charge
22Supply and replacement CP hose reel 15 m complete all as specified and directed by Engr-in-Charge.
23Supply and replacement 15 mm bore gun metal gate valve with iron wheel head screwed both ends completeall as specified andas directed.
24Supply and replacement 20 mm bore gun metal gate valve with iron wheel head screwed both ends completeall as specified andas directed.
25Supply and Fix in repairs fire fighting RRL hose pipe of 63mm, ISI marked, IS 63 (type A),15m long fitted with male and female gun metal coupling ISI marked, IS 903 complete all as specied and directed.
26Supply and Fix in repairs gunmetal branch pipe with long nozzle suitable for 63 mm dia RRL hose pipe, ISI marked, complete all as specied and directed.
27Supply and Fix in repairs outside hose box cabinet made out of 18 gauge MH sheet of size as per site reqirement but not less than 800mm X 600nun X 250mm with double leafed glazed shutters (glazed with 4mm thick transperent fiber sheet) and door frame made out of 16 guage MS sheet painted fire red outside and brilliant white inside and concealed in wall complete all as specied and directed for housing two number RRL hose each 15m long, one number branch pipe with nozzle , first aid hose and single outlet hydrantvalve etc and must have the legend " FIRE HOSE" painted prominently in graphic style and all as specified and directed
28Supply and replacementment of 4 mm thick sheet glass for fire hose boxes of size 0.20 x 0.20 m complete all as specified and directed by Engr-in-Charge.
29Supplyand fix hose reel drum of 20 mm dia and 30 mtr length hose pipe conformingto IS-5132 including gun metal nozzle suitable valve all as directed.
30Repair and maintenance fire service main pump multi stage up to 100 HPhaving at 90 mtrs head multi stage pump of horizontal split casing running at 1450 RPM coupled with upto 100 HP diesel engine including servicing by replacing unserviceable items of gland packing, bearings and charging lubricants for smooth running including servicing of upto 100 hp diesel engine by replacing filters, lubricant oil including defective parts like coupling, oil air filters, servicing of radiator, replacementment exhaust gasket, replacementment of diesel supply and return pipes from tank to engine, battery leads and checking of chaging circuit complete including base frame and pipe lines upto inside pump room of approved colour after preparation of existing surface complete all as specified and directed .
31Repair and maintenance of fire service main pump multi stage upto 100 HP having at 90 mtrs head multi stage pump of horizontal split casing running at 1450 RPM coupled with upto 100 HP AC induction motor including servicing by replacing unserviceable items of gland packing, bearings, gaskets, nuts, bolts and charging lubricants for smooth running including painting of pumpset, base frame and pipe lines upto inside pump room of approved colour after preparation of existing surface complete all as specified and directed
32Repair and maintenance of fire service jockey pump multi stage havingupto 180 LPM at 90 mtrs head multi stage pump of horizontal split casing running at 2900 RPM coupled with upto5.5 HP AC induction motor including servicing by replacing unserviceable items of gland packing, bearings, gaskets, nuts, bolts and charging lubricants for smooth runningincluding painting of pumpset, base frame and pipe lines upto inside pumproom of approved colour after preparation of existing surface complete all as specified and directed.
33Repair and maintenance of fire serviceTerrace/booster/priming pump multi stage having 900 LPM at 36 mtrs head ,horizontal split casing running at 2900 RPM coupled withAC induction motor including servicing by replacing unserviceable items of gland packing, bearings, gaskets, nuts, bolts and charging lubricants for smooth runningincluding painting of pumpset, base frame and pipe lines upto inside pumproom of approved colour after preparation of existing surface complete all as specified and directed.
34Carrying out general and routine maintenance "B" check including replacement of filters such as oil filters, fuel filters, cooling elements and complete with "O" rings and drain out the engine oil and fillingup with the new engine oil including testing up to 100 kVA DG sets complete all as specified and directed by the Engr- in- charge. Note- The quoted rate includes replacement of fuel filter, oil filter,Lub filter , tank Cleaning and checking all electrical connection as per the satisfaction of Engineer- in-charge
35Dismantling of fuel injector pump from DG Pump Set, transporting to workshop for calibrating and replacement of wornout parts like TD piston,service kit including all types of filter and including filling of new engine oil 15W40 required,compressor spring,cam bush,alternator bush, supplier pump,TR pin bush, and packing kit including pressure setting and connecting lathe work complete and refixing the same after proper cleaning of DG Sets of Capacity 100 KVA all as Specified an directed by Engineer-in-charge.
36S&F in repairs rubber gasket 500x500mm size 6mm thick suitable for submersible/mono block pump sets & motors complete all as specified & directed.
37S&F ball valve with brass spindle of 25mm dia complete all as specified
38S&F ball valve with brass spindle of 50 mm dia complete all as specified
39Supplying, installing, testing and commissioning castiron body, ISI marked, BUTTERFLY VALVE 150 mm dia as per IS 13095, ISI Marked with necessary fittings as perspecification. Details : The Butterfly valve shall suitable for waterworks and tested to minimum of 20 kg/cm2 pressure. The body shall of cast iron conforming to IS:210 in circular shape and of high strength to take the minimum water pressure of 10kg/cm2 . The disk shall be heavy duty cast iron with anticorrosive epoxy or nickelcoatingfor the following sizes : Notes :- (i) The valve seat shall be of high grade elastomer or nitrile rubber. The valve in closed position shall have complete contact between the seat and the disc thoughout the perimeter. The elastomer rubber shallhave a long life & shall not give away on continuous water pressue. The shaft shall be on EN 8 grade carbon steel. (ii) the valve shall be fitted between two flanges on upper side of pipe flanges. The valve edge rubber shall be projected outside such that they are wedged within the pipe flanges toprevent leakages. (iii) The valves shall be suppied with manual gear operated opening/closing system by lever. Make- Audco/Kirloskar/Honeywell
40All as per Srl Item No. 39 here-in-before but100 mm Dia bore
41All as per Srl Item No. 39 here-in-before but80 mm Dia bore
42All as per Srl Item No. 39 here-in-before but65 mm Dia bore
43Supply and fixin repairs Foot valve cast iron body both ends flanged suitable for 150mm bore CI pipeconnection all as specified and directed. Make -Kirloskar/Kartar/SIR/AUDICO
44Supply and fixing in repair approved quartezoid bulb 15 mm dia sprinkler pendent type , IS 15106 chrome plated crossette plate, with temperature rating 68 degree with universal deflector as approved by T.A.C complete with all necessary connections complete all as specified and directed.
45Supply Only analogue addressable multisensor detector (Photo + Thermal) with base with galvanised steel, back box and all mounting accessories complete as specifed and directed
46Supply Only analogue smoke detector, with galvanised steel back box all mounting accessories complete as specifed and directed
47Supply only addressable Dual Action Manual Pull staions inside for providing MS box of suitable size for concealing the manual call point in the wall and with mounting accessoriesall as specified
48Supply onlyaddressable Riser Modules in a suitable gavanised steel junction box with mounting accessoriesall as specified
49Supply onlyaddressable control relayModulewith 230 V 2 A where required in a suitable gavanised steel junction box with mounting accessoriesall as specified
50Supply onlyaddressable riserModulefor Hooter in a suitable gavanised steel junction box with mounting accessoriesall as specified
51Supply onlyElectronic Hooterinclude provide MS box suitable size for concealing the hooter in the wall mounting accessories all as specified
52Supply only Conventional Dual Action Manual Pull staions inside for providing MS box of suitable size for concealing the manual call point in the wall and with mounting accessoriesall as specified
53Supply onlyElectronic Hooterinclude provide PVC box suitable size for concealing the hooter in the wall mounting accessories all as specified
54Supply only EST network card for addressable fire alarm control panel
55Supply only EST make, power supply unit for EST 3 addressable fire alarm control panel
56Supply onlylead acid 12v 7 Ah batteries with warranty and battery terminal pins
57Supply only 12v 150Ahbatteries for DG setwith warranty and battery terminal pins
58Supply and fixing of micro processed based 8 zone conventional fire alarm control panel with standards NFPA 72 can operate up to 30 detectors per zone, Board should consist of RS 485 ,2 programmable relay, support port for class B style input devices with networkable ability the above price includes two batteries, installations, commissioning, and networking with main integration network.
59S&F in repair of manual call point glass/fibre flip cover transparent typefixed to surface mounted MCP complete all as specified.